1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationDigital addressable lighting interface Part 207: Particular requirements for control gear LED modules (device type 6)BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHI
2、NA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSINational forewordThis British Standard is the UK implementation of EN 62386-207:2009. It isidentical to IEC 62386-207:2009.The UK participation in its preparation was entrusted by Technical CommitteeCPL/34, Lamps and related equipment, to Sub
3、committee CPL/34/3, Auxiliariesfor lamps.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. BSI 2010 ISBN 978 0 580
4、 57542 6 ICS 29.140.50; 29.140.99Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 January 2010Amendments issued since publicationAmd. No. Date Text affectedBRI
5、TISH STANDARDBS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSIEUROPEAN STANDARD EN 62386-207 NORME EUROPENNE EUROPISCHE NORM November 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisat
6、ion Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62386-207:2009 E ICS 29.140.50; 29.140.99 English
7、version Digital addressable lighting interface - Part 207: Particular requirements for control gear - LED modules (device type 6) (IEC 62386-207:2009) Interface dclairage adressable numrique - Partie 207: Exigences particulires pour les appareillages de commande - Modules de DEL (dispositifs de type
8、 6) (CEI 62386-207:2009) Digital adressierbare Schnittstelle fr die Beleuchtung - Teil 207: Besondere Anforderungen an Betriebsgerte - LED-Module (Gertetyp 6) (IEC 62386-207:2009) This European Standard was approved by CENELEC on 2009-09-01. CENELEC members are bound to comply with the CEN/CENELEC I
9、nternal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELE
10、C member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. C
11、ENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slova
12、kia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSIEN 62386-207:2009 - 2 - Foreword The text of document 34C/888/FDIS, future edition 1 of IEC 62386-207, prepared by
13、SC 34C, Auxiliaries for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 62386-207 on 2009-09-01. This standard is to be used in conjunction with EN 62386-101 and EN 62386-102, which contain general requirements for th
14、e relevant product type (control gear or control devices). The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2010-06-01 latest date by which the national standards conflicting w
15、ith the EN have to be withdrawn (dow) 2012-09-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 62386-207:2009 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes
16、have to be added for the standards indicated: IEC 60598-1 NOTE Harmonized as EN 60598-1:2008 (modified). IEC 60669-2-1 NOTE Harmonized as EN 60669-2-1:2004 (modified). IEC 60921 NOTE Harmonized as EN 60921:2004 (not modified). IEC 60923 NOTE Harmonized as EN 60923:2005 (not modified). IEC 60925 NOTE
17、 Harmonized as EN 60925:1991 (not modified). IEC 60929 NOTE Harmonized as EN 60929:2006 (not modified). IEC 61347-1 NOTE Harmonized as EN 61347-1:2008 (modified). IEC 61347-2-3 NOTE Harmonized as EN 61347-2-3:2001 (not modified). IEC 61547 NOTE Harmonized as EN 61547:1995 (not modified). IEC 62034 N
18、OTE Harmonized as EN 62034:2006 (not modified). CISPR 15 NOTE Harmonized as EN 55015:2006 (not modified). _ BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI- 3 - EN 62386-207:2009 Annex ZA (normative) Normative references to inte
19、rnational publications with their corresponding European publications The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any
20、amendments) applies. NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 62386-101 2009 Digital addressable lighting interface - Part 101: General requirements - System EN 62386-101 20
21、09 IEC 62386-102 2009 Digital addressable lighting interface - Part 102: General requirements - Control gearEN 62386-102 2009 BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI 2 62386-207 IEC:2009 CONTENTS INTRODUCTION.6 1 Scope.7
22、 2 Normative references .7 3 Terms and definitions .7 4 General 8 5 Electrical specification8 6 Interface power supply .8 7 Transmission protocol structure8 8 Timing 8 9 Method of operation .8 10 Declaration of variables10 11 Definition of commands 11 12 Test procedures .17 Annex A (informative) Exa
23、mples of algorithms .43 Bibliography44 Figure 1 Application extended configuration command sequence example.11 Figure 2 “QUERY FEATURES” 18 Figure 3 “QUERY SHORT CIRCUIT”19 Figure 4 “QUERY OPEN CIRCUIT” 20 Figure 5 “QUERY LOAD DECREASE”21 Figure 6 “QUERY LOAD INCREASE” .22 Figure 7 “QUERY CURRENT PR
24、OTECTOR ACTIVE: Underload” 23 Figure 8 “QUERY CURRENT PROTECTOR ACTIVE: Overload” 24 Figure 9 “QUERY THERMAL SHUT DOWN” 25 Figure 10 “QUERY THERMAL OVERLOAD”.26 Figure 11 “Query control gear information”.27 Figure 12 “REFERENCE SYSTEM POWER” 28 Figure 13 “REFERENCE SYSTEM POWER: 100 ms-timeout” 29 F
25、igure 14 “REFERENCE SYSTEM POWER: Command in-between” 30 Figure 15 “REFERENCE SYSTEM POWER: 15 minutes timer” 31 Figure 16 “REFERENCE SYSTEM POWER: failed”32 Figure 17 “ENABLE / DISABLE CURRENT PROTECTOR” .33 Figure 18 “SELECT DIMMING CURVE” .34 Figure 19 “FAST FADE TIME”35 Figure 20 “Reset State /
26、Persistent Memory”37 Figure 21 “ENABLE DEVICE TYPE: Application extended commands”.38 Figure 22 “ENABLE DEVICE TYPE: Application extended configuration commands 1”.39 Figure 23 “ENABLE DEVICE TYPE: Application extended configuration commands 2”.40 Figure 24 “QUERY EXTENDED VERSION NUMBER” 41 BS EN 6
27、2386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI62386-207 IEC:2009 3 Figure 25 “RESERVED APPLICATION EXTENDED COMMANDS”.42 Table 1 Fast fade time .10 Table 2 Declaration of variables.10 Table 3 Summary of the application extended comman
28、d set 17 Table 4 Parameters for the test “REFERENCE SYSTEM POWER: Command in-between”.31 Table 5 Parameters for test “SELECT DIMMING CURVE”35 Table 6 Parameters for test “FAST FADE TIME” 36 Table 7 Parameters for test “ENABLE DEVICE TYPE: Application extended commands”.38 Table 8 Parameters for test
29、 “ENABLE DEVICE TYPE: Application extended configuration commands 1”.40 BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI 6 62386-207 IEC:2009 INTRODUCTION This first edition of IEC 62386-207 is published in conjunction with IEC 6
30、2386-101 and IEC 62386-102. The division of IEC 62386 into separately published parts provides for ease of future amendments and revisions. Additional requirements will be added as and when a need for them is recognised. This International Standard, and the other parts that make up the IEC 62386-200
31、 series, in referring to any of the clauses of IEC 62386-101 or IEC 62386-102, specify the extent to which such a clause is applicable and the order in which the tests are to be performed. The parts also include additional requirements, as necessary. All parts that make up IEC 62386-200 series are s
32、elf-contained and therefore do not include references to each other. Where the requirements of any of the clauses of IEC 62386-101 or IEC 62386-102 are referred to in this International Standard by the sentence “The requirements of IEC 62386-1XX, clause n apply”, this sentence is to be interpreted a
33、s meaning that all requirements of the clause in question of Part 101 or Part 102 apply, except any which are inapplicable to the specific type of lamp control gear covered by Part 207. All numbers used in this International Standard are decimal numbers unless otherwise noted. Hexadecimal numbers ar
34、e given in the format 0xVV, where VV is the value. Binary numbers are given in the format XXXXXXXXb or in the format XXXX XXXX, where X is 0 or 1; x in binary numbers means dont care. BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c)
35、BSI62386-207 IEC:2009 7 DIGITAL ADDRESSABLE LIGHTING INTERFACE Part 207: Particular requirements for control gear LED modules (device type 6) 1 Scope This International Standard specifies a protocol and test procedures for the control by digital signals of electronic control gear for use on a.c. or
36、d.c. supplies, associated with LED modules. NOTE Tests in this standard are type tests. Requirements for testing individual control gear during production are not included. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated ref
37、erences, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 62386-101:2009, Digital addressable lighting interface Part 101: General requirements System IEC 62386-102:2009, Digital addressable lighting interfa
38、ce Part 102: General requirements Control gear 3 Terms and definitions For the purposes of this document, the terms and definitions given in Clause 3 of IEC 62386-101:2009 and Clause 3 of IEC 62386-102:2009 shall apply, with the following additional definitions. 3.1 reference measurement process dur
39、ing which control gear determines the actual LED load with internal procedures and measurements NOTE The details of this process are a matter of detailed design of control gear and are outside the scope of this standard. 3.2 detection of load decrease recognition that the actual LED load is signific
40、antly below the load measured during a successful “reference measurement” NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the manufacturer and these criteria should be described in the manual. 3.3 detection of load increase recognition that the actua
41、l LED load is significantly above the load measured during a successful “reference measurement” NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the manufacturer and these criteria should be described in the manual. BS EN 62386-207:2009Licensed Copy:
42、Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI 8 62386-207 IEC:2009 3.4 current protector protective device switching off the output if the actual LED load differs by more than P from the load detected during the “reference measurement” NOTE The value P can only
43、 be specified by the manufacturer of the control gear and this value should be stated in the manual. 3.5 thermal overload scenario where the maximum permissible control gear temperature is exceeded 3.6 thermal shut down scenario where control gear switches off the LED because of a persistent thermal
44、 overload 3.7 light level reduction due to thermal overload reduction of light level with the objective of decreasing control gear temperature 4 General The requirements of Clause 4 of IEC 62386-101:2009 and Clause 4 of IEC 62386-102:2009 apply. 5 Electrical specification The requirements of Clause
45、5 of IEC 62386-101:2009 and Clause 5 of IEC 62386-102:2009 apply. 6 Interface power supply The requirements of Clause 6 of IEC 62386-101:2009 and Clause 6 of IEC 62386-102:2009 apply, if a power supply is integrated with the control gear. 7 Transmission protocol structure The requirements of Clause
46、7 of IEC 62386-101:2009 and Clause 7 of IEC 62386-102:2009 apply. 8 Timing The requirements of Clause 8 of IEC 62386-101:2009 and Clause 8 of IEC 62386-102:2009 apply. 9 Method of operation The requirements of Clause 9 of IEC 62386-101:2009 and Clause 9 of IEC 62386-102:2009 apply, except as follows
47、: Addition to Clause 9 of IEC 62386-102:2009: BS EN 62386-207:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:53, Uncontrolled Copy, (c) BSI62386-207 IEC:2009 9 9.9 Detection of load decrease If the actual LED load is significantly below the load measured during a successful
48、 “reference measurement”, the gear may switch off the lamp if this is necessary for its safe operation. The flag bit load decrease is to be set. 9.10 Detection of load increase If the actual LED load is significantly above the load measured during a successful “reference measurement”, the gear may s
49、witch off if this is necessary for its safe operation. The flag bit load increase is to be set. 9.11 Current protector If the actual LED load of the control gear differs by more than a defined amount P from the load detected during the reference measurement, the current protector becomes active and switches off the LED. The current protector shall not become active until there has been a successfu