1、Cable trunking systems and cable ducting systems for electrical installationsPart 2-3: Particular requirements Slotted cable trunking systems intended for installation in cabinetsBS IEC 61084-2-3:2017BSI Standards PublicationWB11885_BSI_StandardCovs_2013_AW.indd 1 15/05/2013 15:06National forewordTh
2、is British Standard is the UK implementation of IEC 61084-2-3:2017. The UK participation in its preparation was entrusted to TechnicalCommittee PEL/213, Cable management.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport
3、 to include all the necessary provisions ofa contract. Users are responsible for its correct application. The British Standards Institution 2017.Published by BSI Standards Limited 2017ISBN 978 0 580 89674 3ICS 29.060.01; 29.120.10Compliance with a British Standard cannot confer immunity fromlegal ob
4、ligations.This Published Document was published under the authority of theStandards Policy and Strategy Committee on 30 April 2017.Amendments/corrigenda issued since publicationDate Text affectedBRITISH STANDARDBS IEC 61084-2-3:2017 2 IEC 61084-2-3:2017 IEC 2017 CONTENTS FOREWORD . 3 1 Scope 5 2 Nor
5、mative references 5 3 Terms and definitions 5 4 General requirements 6 5 General conditions for tests . 6 6 Classification . 7 7 Marking and documentation . 7 8 Dimensions 7 9 Construction 8 10 Mechanical properties 8 11 Electrical properties . 10 12 Thermal properties 10 13 Fire hazard 10 14 Extern
6、al influences 11 15 Electromagnetic compatibility 11 Annex A (informative) Types of cable trunking systems (CTS) and cable ducting systems (CDS) 17 Bibliography 18 Figure 101 Examples of pattern of fixing holes in the base of the slotted trunking length . 12 Figure 102 Examples of sizes for the fixi
7、ng holes . 13 Figure 103 Fixing distances for cable support test . 14 Figure 104 Arrangements for cable support test . 15 Figure 105 Arrangement for flame test . 16 BS IEC 61084-2-3:2017IEC 61084-2-3:2017 IEC 2017 3 INTERNATIONAL ELECTROTECHNICAL COMMISSION _ CABLE TRUNKING SYSTEMS AND CABLE DUCTING
8、 SYSTEMS FOR ELECTRICAL INSTALLATIONS Part 2-3: Particular requirements Slotted cable trunking systems intended for installation in cabinets FOREWORD 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising all national electrotechnical commit
9、tees (IEC National Committees). The object of IEC is to promote international co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical
10、Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in this preparatory work. International, governmental a
11、nd non-governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for Standardization (ISO) in accordance with conditions determined by agreement between the two organizations. 2) The formal decisions or agreeme
12、nts of IEC on technical matters express, as nearly as possible, an international consensus of opinion on the relevant subjects since each technical committee has representation from all interested IEC National Committees. 3) IEC Publications have the form of recommendations for international use and
13、 are accepted by IEC National Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any misinterpretation by any end user. 4) In order to promote i
14、nternational uniformity, IEC National Committees undertake to apply IEC Publications transparently to the maximum extent possible in their national and regional publications. Any divergence between any IEC Publication and the corresponding national or regional publication shall be clearly indicated
15、in the latter. 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any services carried out by independent certification bodies. 6) All
16、users should ensure that they have the latest edition of this publication. 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and members of its technical committees and IEC National Committees for any personal injury, property damage or
17、other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC Publications. 8) Attention is drawn to the Normative references cited in this publicatio
18、n. Use of the referenced publications is indispensable for the correct application of this publication. 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent rights. IEC shall not be held responsible for identifying any or all such pa
19、tent rights. International Standard IEC 61084-2-3 has been prepared by subcommittee 23A: Cable management systems, of IEC technical committee 23: Electrical accessories. This International standard is to be used in conjunction with IEC 61084-1:2017. The text of this standard is based on the followin
20、g documents: FDIS Report on voting 23A/829/FDIS 23A/835/RVD Full information on the voting for the approval of this standard can be found in the report on voting indicated in the above table. BS IEC 61084-2-3:2017 4 IEC 61084-2-3:2017 IEC 2017 This publication has been drafted in accordance with the
21、 ISO/IEC Directives, Part 2. This Part of the IEC 61084 series supplements or modifies the corresponding clauses of IEC 61084-1:2017 as follows: where no particular clause or subclause of IEC 61084-1 is mentioned, the corresponding clause or subclause applies as far as it is reasonable; where “addit
22、ion“, “modification“ or “replacement” is stated, the relevant text of IEC 61084-11 is to be adapted accordingly; subclauses, figures and tables which are additional to those in IEC 61084-1 are numbered starting from 101. In this standard, the following print types are used: requirements and definiti
23、ons: roman type; compliance statements: italic type. A list of all parts in the IEC 61084 series, published under the general title Cable trunking and cable ducting systems for electrical installations, can be found on the IEC website. The committee has decided that the contents of this publication
24、will remain unchanged until the stability date indicated on the IEC website under “http:/webstore.iec.ch“ in the data related to the specific publication. At this date, the publication will be reconfirmed, withdrawn, replaced by a revised edition, or amended. BS IEC 61084-2-3:2017IEC 61084-2-3:2017
25、IEC 2017 5 CABLE TRUNKING SYSTEMS AND CABLE DUCTING SYSTEMS FOR ELECTRICAL INSTALLATIONS Part 2-3: Particular requirements Slotted cable trunking systems intended for installation in cabinets 1 Scope This part of the IEC 61084 series specifies requirements and tests for cable trunking systems (CTS)
26、and cable ducting systems (CDS) intended for the accommodation, and where necessary for the electrically protective separation, of insulated conductors, cables and possibly other electrical equipment in electrical and/or communication systems installations. The maximum voltage of these installations
27、 is 1 000 V AC and 1 500 V DC. Slotted cable trunking systems are intended for mounting inside cabinets in electrical and/or communication system installations. This document does not apply to conduit systems, cable tray systems, cable ladder systems, power track systems or equipment covered by othe
28、r standards. NOTE Wherever reference is made in this document to IEC 61084-1:2017, this does not apply to cable ducting systems. 2 Normative references This clause of Part 1 is applicable, except as follows: Addition: IEC 60228:2004, Conductors of insulated cables IEC 60695-11-5:2004, Fire hazard te
29、sting Part 11-5: Test flames Needle-flame test method Apparatus, confirmatory test arrangement and guidance1IEC 61084-1:2017, Cable trunking systems and cable ducting systems for electrical installations Part 1: General requirements 3 Terms and definitions This clause of Part 1 is applicable, except
30、 as follows: Addition: 3.101 slotted cable trunking system system comprising a slotted trunking length and possibly other slotted cable trunking system components for the accommodation and laying in of insulated conductors or cables intended for use in a cabinet or similar _ 1This publication was wi
31、thdrawn. BS IEC 61084-2-3:2017 6 IEC 61084-2-3:2017 IEC 2017 3.102 slotted cable trunking system component part of the system which includes a) slotted trunking length; b) trunking fitting; c) fixing device; d) system accessory Note 1 to entry: The above mentioned system components are not necessari
32、ly included all together in a system. Different combinations of system components can be used. 3.103 slotted trunking length trunking length with slotted walls and with cover(s) which may be integral part of the base and/or may be slotted 3.104 slotted wall wall with openings allowing cables to pass
33、 through Note 1 to entry: The openings can be with open or closed boundary and may have different shapes, normally designed to maintain wiring in position. 3.105 wall finger part of a slotted wall between two consecutive slots with open boundary 3.106 break-out line line which may be available on th
34、e walls of a trunking length to facilitate the breaking of walls or parts thereof, such as a wall finger 4 General requirements This clause of Part 1 is applicable, except as follows: Replacement: Slotted cable trunking systems shall be so designed and constructed that where required they ensure rel
35、iable support, accommodation and segregation of the insulated conductors and/or cables contained therein. Equipment associated with or incorporated in a system component but which is not a system component, shall and need only comply with the relevant standard of this equipment, if any. However it m
36、ay be necessary to include such equipment in a test arrangement for the purpose of testing its interface with the slotted cable trunking system. Compliance is checked by carrying out all the tests specified. 5 General conditions for tests This clause of Part 1 is applicable. BS IEC 61084-2-3:2017IEC
37、 61084-2-3:2017 IEC 2017 7 6 Classification This clause of Part 1 is applicable, except as follows. 6.2 According to resistance to impact for installation and application Not applicable. 6.1 According to temperatures Table 2 of Part 1 is not applicable. 6.5 According to electrical continuity charact
38、eristic Not applicable. 6.6 According to electrical insulating characteristic Not applicable. 6.7 According to degrees of protection provided by enclosure according to IEC 60529:1989 Not applicable. 6.9 According to the system access cover retention Not applicable. Additional subclauses: 6.101 Accor
39、ding to the intended installation positions 6.101.1 Mounted on vertical or horizontal surface 6.101.2 Mounted on vertical or horizontal surface except in a cover down position 7 Marking and documentation This clause of Part 1 is applicable. 8 Dimensions This clause of Part 1 is applicable, except as
40、 follows. Additional subclause: 8.101 The preferred solution for fixing holes, if any, in the base of the slotted trunking lengths according to the different trunking widths as shown in Figure 101 is as follows: trunking lengths with a nominal width less or equal to 12,5 mm should preferably have on
41、e row of small holes only, as shown in Figure 102 b); trunking lengths with a nominal width greater than 12,5 mm and less or equal to 62,5 mm, should preferably have one row of holes only, alternately as shown in Figure 102 a) and in Figure 102 b); trunking lengths with a nominal width greater than
42、62,5 mm should preferably have two or more rows of holes alternately as shown in Figure 102 a) and in Figure 102 b), positioned BS IEC 61084-2-3:2017 8 IEC 61084-2-3:2017 IEC 2017 at a distance of 25 mm or 50 mm apart, symmetrically located from the trunking centre line. 9 Construction This clause o
43、f Part 1 is applicable, except as follows. 9.2 Apparatus mounting Not applicable. 9.5 Accessible conductive parts Not applicable. 9.6 Equipotential bonding Not applicable. 9.7 Access to live parts Not applicable. 9.8 Inlet openings Not applicable. 9.9 Membranes Not applicable. 9.10 Cable restrainer
44、Not applicable. 9.11 Cable anchorage Not applicable. 10 Mechanical properties This clause of Part 1 is applicable, except as follows. 10.2 Cable support test Replacement by the following additional subclauses: 10.2.101 General test conditions Each test is made on one new sample of slotted trunking l
45、ength having a length of (250 5) mm. Before the test non-metallic and composite slotted trunking lengths are aged at the temperature declared according to Table 3 of Part 1 with a tolerance of 2C for (168 4) h continuously. BS IEC 61084-2-3:2017IEC 61084-2-3:2017 IEC 2017 9 The sample is securely fi
46、xed, using 10 mm external diameter flat metallic washers and appropriate metallic screws to a rigid smooth support such as a plywood board 16 mm thick. When 10 mm external diameter is too large, suitable smaller washer and appropriate screw are used. Fixing(s) are positioned as shown in Figure 103 a
47、t (200 5) mm centres along the length of the sample. Within the width of the sample: for trunking with a width less than 50 mm, one fixing is used as shown in Figure 103 a); for trunking with a width equal or greater than 50 mm, two fixings are used as shown in Figure 103 b). If the manufacturers in
48、structions require the use of cable retainers or dividers, these are fitted according to the manufacturers instructions. Cable retainers, if any, are symmetrically fixed along the length. The sample is subjected to an evenly distributed load of 0,8 g/mm2of the declared usable area for cables, per me
49、tre length. The load is distributed between the compartments proportionally to the declared usable area. The load consists of copper insulated conductors or cables complying with class 5, Table 3 of IEC 60228:2004, or flexible insulated conductors or cables of similar mass per meter. To allow for settlement of the sample, a pre-load of 10 % of the load is applied and removed after (300 30) s. The measurement apparatus is then calibrated to zero. In