1、 COE CEAGS 16740A I 3515711i5 0534472 688 R . DEPARTMENT OF THE ARMY CEAGS-16740A (December 1994) U.S. ARMY CORPS OF ENGINEERS Superseding CEAGS 16740A (October 1992) ABRIDGED GUIDE SPECIFICATION FOR MILITARY CONSTRUCTION . SECTION 16740A TELEPHONE SYSTEM, PRE-WIRING 12/94 PART 1 GENERAL NOTE: See A

2、dditional Notes A through D. 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. designation only. The publications are referred to in the text by basic ELECTRONIC INDUSTRIES ASSOCIATION (EIA) EIA 568 EIA TSB 36 EIA TSB 40-A (1991) Commercial Buil

3、ding Telecommunications Wiring Standard (1991) Additional Cable Specifications for Unchielded Twisted Pair Cables (1994) Additional Transmission Specifications for Unshielded Twisted-Pair Connecting Hardware INSULATED CABLE ENGINEERS ASSOCIATION (ICEA) ICEA S-80-576 (1988) Communications Wire and Ca

4、ble for wiring of Premises NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 70 (1993) National Electrical Code UNDERWRITERS LABORATORY (UL) UL 50 1.2 SYSTEM DESCRIPTION (1992; Rev thru Nov 1994) Enclosures for Electrical Equipment A telecommunications wiring system consisting of inside plant cables

5、and other auxiliary equipment shall be provided. 1.3 SUBMITTALS Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Government approval is required for submittals with a designation; submittals having an lfFIOIt designation are for information only. The

6、following shall be submitted in accordance with Section 01300 SUBMITTAL DESCRIPTIONS: SD-04 Drawings Telephone Pre-wiring System; GA. Detail drawings shall include a complete list of equipment and material, including manufacturers descriptive and technical literature, performance charts and curves,

7、catalog cuts, and installation instructions. Detail drawings shall contain complete wiring diagrams and any other details required to demonstrate that the system has been coordinated and will properly function when connected to the dial central office. shall show proposed layout and equipment relati

8、onship to other parts of the work including clearance for maintenance and operations. Drawings System drawings showing final configuration, including location, type, gauge, and block and terminal assignment of inside wiring, and floor plan layout for the equipment room, after installation. SD-06 Ins

9、tructions Manufacturers Recommendations; GA. Where installation procedures, or any part thereof, are required to be in accordance with the recommendations of the manufacturer of the material being installed, printed copies of these recommendations shall be provided prior to installation. Installatio

10、n of the item will not be allowed to proceed until the recommendations are received and approved. SD-09 Reports Test Reports; I* Test reports in booklet form showing field tests performed to prove compliance with the specified performance criteria, upon completion and testing of the installed system

11、 SD-14 Certificates Horizontal Cables; 3. Backbone Cables; I* - 1. Connecting Hardware; I* Telecommunication Outlets; 3. Communication Cabinets; Manufacturers certificate indicating compliance with transmission and reliability requirements. conform to the standards or publications and requirements

12、of CFR, EIA, ICEA and UL, certificates shall be provided attesting that the items furnished under this section of the specification conform to the specified requirements. Where equipment or materials are specified to 1.4 DELIVERY AND STORAGE Equipment delivered and placed in storage shall be stored

13、with protection from the weather, humidity and temperature variation, dirt and dust, or other contaminants. PART 2 PRODUCTS Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-COE CEAGS Lb740A 3535789 0533474 450 H 2.1 STANDARD PRODUCTS Materials and equ

14、ipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products and shall be the manufacturers latest standard design that has been in satisfactory use for at least 2 years prior to bid opening. 2.2 WIRING SYSTEM The category for cable, jacks and blocks s

15、hould be the same throughout each circuit and system. Specify more than two categories only if providing two systems requiring different categories. general, Category 3 (up to 1OMHz transmission) should be used for voice circuits and Category 5 (up to 1OOMHz) should be used for data circuits. Verify

16、 this criteria with the user. In For specialized circuits such as pay phones in dorms and other sleeping quarters coordinate with the local telephone company. For applications where cables will not be in conduit, and are in a plenum environment, specify Type 2 for horizontal cable and Type 4 for bac

17、kbone cable. If in conduit, or not in a plenum, Type 1 for horizontal cable and Type 3 for backbone cable should be specified. Ensure that the NEC 60 percent maximum conduit fill is considered when sizing cables. When sizing the cables and determining the category, keep in mind whether the system is

18、 voice-only or voice-data. Use pin/pair configuration T568A unless the host facility has standardized on T568B NOTE: See Additional Note E. The wiring system shall be in conformance with EIA 568. 2.2.1 Horizontal Cables Horizontal cables between the telecommunication outlet and the connecting hardwa

19、re shall be in accordance with the requirements of EIA 568 for 100-ohm, unshielded, twisted-pair and shall be category 3 5 in conformance with EIA TSB 36. Type, per ICEA S-80-576, shall be as shown. 2.2.2 Backbone Cables Backbone cables between the entrance facility and telecommunication closets and

20、 equipment rooms shall be of the same category as the horizontal cable it serves. Cables shall be in accordance with the requirements of EIA 568 for 100-ohm, unshielded, twisted-pair and EIA TSB 36. Type, per ICEA S-80-576, shall be as shown. 2.2.3 Telecommunication Outlets Provided by IHSNot for Re

21、saleNo reproduction or networking permitted without license from IHS-,-,-COE CEAGS 36740A E 3515789 0533475 397 NOTE: Specify single-jack face plates for barracks and unaccompanied personnel housing projects. Wall and desk face plates shall come equipped with two modular jacks, with the top or left

22、jack labeled Ilvoicel and the bottom or right jack labeled IldataIl. Jacks shall comply with EIA 568 and EIA TSB 40-A and be the same category as the cable they terminate. shall be T568A per EIA 568. Jack pin/pair configuration 2.2.4 Telephone Backboard NOTE: Provide size on drawings. An ACX plywood

23、 backboard shall be provided, sized as shown, coated on both sides with two coats of insulating varnish as a minimum. 2.2.5 Communication Cabinets NOTE: Provide size on drawings. Cabinets shall conform to UL 50 and have boxes constructed of zinc-coated sheet steel with interior dimensions not less t

24、han shown on drawings. Trim shall be fitted with hinged door and flush catch. Doors shall provide maximum openings to the box interiors. provided with 19 mm (3/4 inch) ACX plywood backboard having a two-coat insulating varnish finish. Boxes shall be 2.2.6 Connecting Hardware NOTE: Requirements for p

25、rotecting or connecting hardware for termination of outside plant cables entering the facility should be provided in accordance with Section 16742 TELEPHONE SYSTEM OUTSIDE PLANT. * * Connecting and cross-connecting hardware shall be of the same category as the cabling they serve. 40-A and EIA 568. H

26、ardware shall be in accordance with EIA TSB PART 3 EXECUTION 3.1 INSTALLATION System components and appurtenances shall be installed in accordance with the manufacturerls instructions as specified or as shown. Installation work shall be done in accordance with the safety requirements set forth in th

27、e general requirements of NFPA 70. 3.2 WIRING SYSTEM INSTALLATION NOTE: Secure and classified areas should meet Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-COE CEAGS 16740A II 3535789 053LY76 223 requirements of NACSIM 5203 and DIAM 50-3 for cabl

28、e distribution and wiring. Wiring shall be installed in accordance with EIA 568, and as specified in Section 16415 ELECTRICAL WOM, INTERIOR. EIA 568, Appendix C shall be considered mandatory. Cables shall not be installed in the same cable tray, utility pole compartment, or floor trench compartment

29、with ac power cables. properly secured and neat in appearance. Cables not installed in conduit or wireways shall be 3.3 GROUNDING NOTE: Verify that a grounding point exists in the facility. If not, provisions for a ground should be added. Reference TM 5-811-9. The telecommunications equipment ground

30、 shall be connected to the Master Ground Bar (MGB) building ground electrical service equipment ground following the most direct route utilizing a minimum No. 6 gauge copper wire conductor. Total resistance of the conductor only shall be 0.005 ohms or less. 3.4 TESTING Notification of planned testin

31、g shall be given at least 14 days prior to any test. Personnel or the Contracting Officers onsite representative. Discrepancies noted during testing shall be corrected, and those tests rerun, within 14 days. Tests shall be witnessed by Government Quality Assurance 3.4.1 Test Reports A report detaili

32、ng the results of testing shall be delivered within 7 days after completion of each phase of testing. sign-off/completion sheets for each test indicating test results, reason for failure, and signature blocks for both the contractor and Government witness. The report shall contain 3.4.2 Tests Tests

33、shall verify block-to-jack continuity of pairs with no shorts, opens, crosses, reverses, splits, or grounds. Tests shall include measurement of attenuation, near-end crosstalk, and ambient noise. To ensure a successful cutover, 100 percent verification of subscriber records and cable locations for t

34、he system shall be completed prior to cutover. ADDITIONAL NOTES NOTE A: For additional information on the use of all CEAGS, see CEAGS-01000A CEAGS GENERAL NOTES. NOTE B: This guide specification covers telephone system pre-wiring installed inside buildings. NOTE C: This guide specification is part o

35、f a series of abridged specifications (CEAGS) for use in Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-COE CEAGS Lb740A 3515749 0533477 LbT specifying small jobs, minor elements of larger jobs, or repair or maintenance type work, when brief specifi

36、cations with a minimum of controls will meet job requirements. This specification is based on CEGS-16740, December 1994. NOTE D: Most CEAGS have a counterpart in the CEGS system, and if a more detailed specification is required the CEGS should be used. Also, if additional information is needed for the use of CEAGS, the notes in the CEGS should be consulted. . - End of Section - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
  • ASHRAE 4742-2005 Coil Frosting and Defrosting Issues at Low Freezer Temperature Near Saturation Conditions《在低冷冻温度接近饱和的条件下的线圈结霜和除霜问题》.pdf ASHRAE 4742-2005 Coil Frosting and Defrosting Issues at Low Freezer Temperature Near Saturation Conditions《在低冷冻温度接近饱和的条件下的线圈结霜和除霜问题》.pdf
  • ASHRAE 4743-2005 Condensation Enhancement of R-22 by Twisted-Tape Inserts Inside a Horizontal Tube《R-22 扭带内插入横管的冷凝强化》.pdf ASHRAE 4743-2005 Condensation Enhancement of R-22 by Twisted-Tape Inserts Inside a Horizontal Tube《R-22 扭带内插入横管的冷凝强化》.pdf
  • ASHRAE 4744-2005 Determination of Dielectric Properties of Refrigerants《制冷剂RP-1074介电性能的测定》.pdf ASHRAE 4744-2005 Determination of Dielectric Properties of Refrigerants《制冷剂RP-1074介电性能的测定》.pdf
  • ASHRAE 4745-2005 Field Performance Assessment of VAV Control Systems to Determine the Longevity of Recommissioning《变风量控制系统场表现评核 以确定RP-1137再运行寿命》.pdf ASHRAE 4745-2005 Field Performance Assessment of VAV Control Systems to Determine the Longevity of Recommissioning《变风量控制系统场表现评核 以确定RP-1137再运行寿命》.pdf
  • ASHRAE 4746-2005 Measurement of Solubility Viscosity and Density of R-507A Refrigerant Lubricant Mixtures《R-507A制冷剂 润滑油混合物RP-1253 溶解度 粘度和密度的测量》.pdf ASHRAE 4746-2005 Measurement of Solubility Viscosity and Density of R-507A Refrigerant Lubricant Mixtures《R-507A制冷剂 润滑油混合物RP-1253 溶解度 粘度和密度的测量》.pdf
  • ASHRAE 4747-2005 Neural-Based Air-Handling Unit for Indoor Relative Humidity and Temperature Control《为室内相对湿度和温度控制而设的基于神经网络的空气处理机组》.pdf ASHRAE 4747-2005 Neural-Based Air-Handling Unit for Indoor Relative Humidity and Temperature Control《为室内相对湿度和温度控制而设的基于神经网络的空气处理机组》.pdf
  • ASHRAE 4748-2005 A Study for Evaluating Performance of Radiant Floor Cooling Integrated with Controlled Ventilation《评价地板辐射冷却与控制通气的一项研究》.pdf ASHRAE 4748-2005 A Study for Evaluating Performance of Radiant Floor Cooling Integrated with Controlled Ventilation《评价地板辐射冷却与控制通气的一项研究》.pdf
  • ASHRAE 4749-2005 A Survey Technique for Evaluating Heating Ventilating and Air-Conditioning Systems《评价供暖 通风 空调系统一项技术调查》.pdf ASHRAE 4749-2005 A Survey Technique for Evaluating Heating Ventilating and Air-Conditioning Systems《评价供暖 通风 空调系统一项技术调查》.pdf
  • ASHRAE 4750-2005 Determination of Building Materials′ Transport Properties for Modeling VOC Emissions《测定建材?建模挥发性有机化合物排放的运动性》.pdf ASHRAE 4750-2005 Determination of Building Materials′ Transport Properties for Modeling VOC Emissions《测定建材?建模挥发性有机化合物排放的运动性》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1