1、December 2016 English price group 12No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 91.140.10!%D“2599133www.din.deD
2、IN EN 14037-5Free hanging heating and cooling surfaces for water with a temperature below 120 C Part 5: Open or closed heated ceiling surfaces Test method for thermal output;English version EN 140375:2016,English translation of DIN EN 14037-5:2016-12An der Decke frei abgehngte Heiz und Khlflchen fr
3、Wasser mit einer Temperatur unter 120 C Teil 5: Offene oder geschlossene Deckenheizflchen Prfverfahren fr die Wrmeleistung;Englische Fassung EN 140375:2016,Englische bersetzung von DIN EN 14037-5:2016-12Panneaux rayonnants de chauffage et de aliments avec une eau une temprature infrieure 120 C Parti
4、e 5: Mthode dessai pour la dtermination de la puissance thermique des surfaces de plafond de chauffage ouverts ou ferms;Version anglaise EN 140375:2016,Traduction anglaise de DIN EN 14037-5:2016-12www.beuth.deDocument comprises 23 pagesDTranslation by DIN-Sprachendienst.In case of doubt, the German-
5、language original shall be considered authoritative.12.16rafrachissementDIN EN 14037-5:2016-12 2 A comma is used as the decimal marker. National foreword This document (EN 14037-5:2016) has been prepared by Technical Committee CEN/TC 130 “Space heating appliances without integral heat sources” (Secr
6、etariat: UNI, Italy). The responsible German body involved in its preparation was DIN-Normenausschuss Heiz- und Raumlufttechnik (DIN Standards Committee Heating and Ventilation Technology), Working Committee NA 041-01-69-52 AK Deckenstrahlplatten (SpA CEN/TC 130/WG 7). EUROPEAN STANDARD NORME EUROPE
7、NNE EUROPISCHE NORM EN 14037-5 September 2016 ICS 91.140.10 English Version Free hanging heating and cooling surfaces for water with a temperature below 120 C - Part 5: Open or closed heated ceiling surfaces - Test method for thermal output Panneaux rayonnants de chauffage et de rafrachissement alim
8、ents avec une eau une temprature infrieure 120 C - Partie 5: Mthode dessai pour la dtermination de la puissance thermique des surfaces de plafond de chauffage ouverts ou ferms An der Decke frei abgehngte Heiz- und Khlflchen fr Wasser mit einer Temperatur unter 120 C - Teil 5: Prfverfahren fr die Wrm
9、eleistung von offenen oder geschlossenen Deckenheizflchen This European Standard was approved by CEN on 18 March 2016. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without
10、any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other lang
11、uage made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmar
12、k, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE F
13、OR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2016 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14037-5:2016 EEN 14037-5:2016 (E
14、) 2 Contents Page European foreword 3 Introduction . 4 1 Scope . 5 2 Normative references . 5 3 Terms and definitions 5 4 Symbols and units 6 5 Testing of thermal output . 7 6 Test methods . 9 7 Carrying out the measurement . 9 7.1 General . 9 7.2 Test design 9 7.3 Connection of the test sample to t
15、he measuring circuit . 9 7.4 Mass flow . 9 7.5 Test temperature 10 7.6 Reference room temperature . 10 7.7 Steady-state conditions . 10 7.8 Heat output 10 7.9 Result of measurement characteristic equation 10 7.10 Standard output . 11 7.11 Interpolation of values of the thermal output 11 8 Upper insu
16、lation 11 9 Test report . 11 9.1 General 11 9.2 Data 11 10 Examples for the determination of the active length of different ceiling mounted heating surfaces . 13 Annex A (informative) Specimen of the test report for heating capacity 18 Bibliography 21 DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 3 Eur
17、opean foreword This document (EN 14037-5:2016) has been prepared by Technical Committee CEN/TC 130 “Space heating appliances without integral heat sources”, the secretariat of which is held by UNI. This European Standard shall be given the status of a national standard, either by publication of an i
18、dentical text or by endorsement, at the latest by March 2017, and conflicting national standards shall be withdrawn at the latest by March 2017. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held
19、responsible for identifying any or all such patent rights. The European Standard EN 14037, Free hanging heating and cooling surfaces for water with a temperature below 120C, consists of the following parts: Part 1: Pre-fabricated ceiling mounted radiant panels for space heating - Technical specifica
20、tions and re-quirements Part 2: Pre-fabricated ceiling mounted radiant panels for space heating - Test method for thermal output Part 3: Pre-fabricated ceiling mounted radiant panels for space heating - Rating method and evaluation of radiant thermal output Part 4: Pre-fabricated ceiling mounted rad
21、iant panels for space heating - Test method for cooling capacity Part 5: Open or closed heated ceiling surfaces - Test method for thermal output According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Sta
22、ndard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portu-gal, Romania, Slovakia, Slovenia,
23、Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 4 Introduction This European Standard results from the recognition, that heated and chilled ceiling radiant panels falling into the field of application hereinafter stated are traded on the basis of
24、 their thermal output. For evaluating and comparing different heated and chilled ceiling surfaces it is therefore necessary to refer to a heating stipulated value. As installations with ceiling mounted radiant panels can also be used in practice for space cooling, it is nec-essary to have a test met
25、hod for evaluating the cooling capacity. Installations with different free hanging heating and cooling surfaces need, for the use of space heating a test method for evaluating the heating out-put. The test method differs from the method for ceiling mounted radiant panels. DIN EN 14037-5:2016-12 EN 1
26、4037-5:2016 (E) 5 1 Scope This European Standard describes the test method and the test installation for determining the thermal out-put of ceiling mounted heating surfaces according to the specifications 3.1, 3.2. and 3.3. This part applies to determine thermal output when chilled ceilings accordin
27、g to EN 14240 are also used for heating. NOTE Test results according to this part cannot be compared with results according EN 140372 because great discrepancies are given at open ceilings, convective components and heating surfaces without upper insulation. 2 Normative references The following docu
28、ments, in whole or in part, are normatively referenced in this document and are indis-pensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 14037-1:2016, Pre-fab
29、ricated ceiling mounted radiant panels for space heating - Technical specifications and requirements EN 14037-2:2016, Pre-fabricated ceiling mounted radiant panels for space heating - Test method for thermal output EN ISO/IEC 17025:2005, General requirements for the competence of testing and calibra
30、tion laboratories (ISO/IEC 17025:2005) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14037-1:2016 and the following apply. 3.1 open or closed ceiling surface open or closed active and non-active elements of chilled ceilings, which are additionally u
31、sed for heating, which are part of suspended ceilings and generally constructed modular from industrially prefabricated el-ements 3.2 free hanging sail surface composed of one or more elements of a cooling installation which is additionally used for heating Note 1 to entry: Depending on the use of t
32、he sails they can be covered with thermal insulation or noise absorption material. 3.3 suspended ceiling with integrated heating elements single closed elements which are used for heating and are thermally insulated on the upper side, integrated in closed hanging ceilings and combined with non-activ
33、e elements 3.4 mean radiant temperature temperature in a defined point of the room resulting from the radiation of all surrounding surfaces and of the heated ceiling surface DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 6 3.5 standard temperature difference of heated ceiling surfaces mean water tempera
34、ture 35C and reference room temperature 20C, determined temperature difference 15 K 3.6 active heated ceiling surface relating to thermal output of heated ceiling surfaces 3.7 module 1 m2active surface of a heated ceiling surface 4 Symbols and units For the purposes of this document, the symbols and
35、 units given in EN 14037-1:2016 and the following apply. Table 1 Symbols and units No. Quantity Symbol Unit 1 Installation surface Aim22 Active surface Aam23 Total active surface Aatotm24 Constant of the characteristic equation of the active surface KactW/K nact5 Constant of the characteristic equat
36、ion of the module KactMW/(m2K nact) 6 Constant of the characteristic equation of the installation sur-face KtotW/K ntot7 Exponent of the characteristic equation of the active surface nact- 8 Exponent of the characteristic equation of the installation sur-face ntot- 9 Active area ratio Ra- 10 Modular
37、 thermal output LW/m211 Standard modular thermal output aLsW/m212 Standard temperature difference of a heated cooling surface when heating (15 K) aTsK a “s” indicates that the value is in standard conditions. DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 7 5 Testing of thermal output The test is carrie
38、d out in a testing system, which consists of a closed booth with controlled temperatures of the inside surfaces plus a set of two master panels built according to EN 14037-2:2016, Clause 6. Differing from the definitions of the test booth according to EN 14037-2:2016, the ceiling and the upper part
39、of the vertical walls of the test booth shall be insulated until 0,5 m (0,02 m) below the ceiling with a specific thermal resistance of 2,5 (m K)/W. The method for measuring the thermal output consists of the measurement of mass flow and enthalpy dif-ference between inlet and outlet (by weighing met
40、hod). Other measurement methods shall guarantee in minimum the precision obtained by weighing method. The natural convection within the test booth shall not be affected by additional means. All laboratories that make tests according to this standard have to make comparable measurements with the othe
41、r laboratories (according to EN 14037-2:2016, Clause 6). DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 8 Dimension in meter Key 1 test booth 2 insulation 3 test specimen 4 edge insulation plate 5 measuring point of air temperature 6 measuring point of Globe temperature hv distance from the lower surfac
42、e to the test item to the insulated ceiling of the test booth Figure 1 Example of a test booth with arrangement of a closed heated ceiling and the temperature measuring points DIN EN 14037-5:2016-12 EN 14037-5:2016 (E) 9 6 Test methods The test method shall be carried out according to EN 14037-2:201
43、6, Clause 7. 7 Carrying out the measurement 7.1 General The natural convection inside the test booth shall not be influenced by additional means. 7.2 Test design The test sample shall be installed in the test booth according to the instructions of the manufacturer. The arrangement of the sample shal
44、l be symmetrical if possible otherwise as much regular as possible. In case of closed ceilings (see 3.1 and 3.3) filling parts have to be installed when the projected surface is smaller than the test booth. The filling parts shall be thermally insulated according to Clause 5. The total standard heat
45、 output of the installed sample shall be minimum 400 W and the active surface shall cover at least 15 % of the total ceiling of the test booth (approx. 2,2 m2). The active area ratio shall be calculated with: aaiARA= (1) where Rathe active area ratio; Aathe active surface, it consists of the sum of
46、the connected surface elements, that are projected on the floor and connected to the heating system, overlapping surfaces will be single evaluated. Aithe installation surface. At closed ceiling surfaces the active area ratio shall be declared together with the standard output value. The distance fro
47、m the lower surface of the test item to the insulated ceiling of the test booth hv(void behind the item including the height of the test item) shall not exceed 300 mm. 7.3 Connection of the test sample to the measuring circuit After installation and connection to the measuring circuit, the test samp
48、le and the water circuit shall be care-fully vented. During the test, the measuring circuit shall be free of air inclusions. The procedure of venting is to be described in the working instructions of the test laboratory. If the connecting pipes are not an element of the standard installation, but ar
49、e intended for the test, they shall be provided with a maximum thermal conductivity of 4 W/(m2 K). 7.4 Mass flow The water flow rate shall be regulated so that the result of the difference between inlet and outlet tempera-ture shall be 4 K 0,2 K at a temperature difference of 20 K 2 K. During the test for measuring the three points of the characteristic equation, the mass flow rate shall be constant at each measuring point and shall not differ more than 5 % from one point to another. DIN EN 1403