DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf

上传人:progressking105 文档编号:671846 上传时间:2018-12-25 格式:PDF 页数:10 大小:487.58KB
下载 相关 举报
DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf_第1页
第1页 / 共10页
DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf_第2页
第2页 / 共10页
DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf_第3页
第3页 / 共10页
DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf_第4页
第4页 / 共10页
DIN EN 671-3-2009 Fixed firefighting systems - Hose systems - Part 3 Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose English version of DIN EN 67.pdf_第5页
第5页 / 共10页
点击查看更多>>
资源描述

1、July 2009DEUTSCHE NORM English price group 7No part of this standard may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 13.220.10!$Xl“1537393www.d

2、in.deDDIN EN 671-3Fixed firefighting systems Hose systems Part 3: Maintenance of hose reels with semi-rigid hose and hosesystems with lay-flat hoseEnglish version of DIN EN 671-3:2009-07Ortsfeste Lschanlagen Wandhydranten Teil 3: Instandhaltung von Schlauchhaspeln mit formstabilem Schlauch undWandhy

3、dranten mit FlachschlauchEnglische Fassung DIN EN 671-3:2009-07SupersedesDIN EN 671-3:2000-10www.beuth.deDocument comprises 10 pagesDIN EN 671-3:2009-07 2 National foreword This standard has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting systems” (Secretariat: BSI, United Kingdo

4、m). The responsible German body involved in its preparation was the Normenausschuss Feuerwehrwesen (Firefighting and Fire Protection Standards Committee), Technical Committee NA 031-03-05 AA Anlagen zur Lschwasserversorgung einschlielich Wandhydranten. Amendments This standard differs from DIN EN 67

5、1-3:2000-10 as follows: a) The standard has been editorially revised. b) Recommendations are now specified as requirements. c) Clause 3 “Terms and definitions” has been revised. d) Requirements have been included in clauses 6, 7 and 9. Previous editions DIN 14461-1: 1966-08, 1976-05, 1986-01 DIN EN

6、671-3: 2000-10 EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 671-3March 2009ICS 13.220.10 Supersedes EN 671-3:2000 English VersionFixed firefighting systems - Hose systems - Part 3: Maintenanceof hose reels with semi-rigid hose and hose systems with lay-flathoseInstallations fixes de lutte contr

7、e lincendie - Systmesquips de tuyaux - Partie 3: Maintenance des robinetsdincendie arms quips de tuyaux semi-rigides et despostes deau muraux quips de tuyaux platsOrtsfeste Lschanlagen - Wandhydranten - Teil 3:Instandhaltung von Schlauchhaspeln mit formstabilemSchlauch und Wandhydranten mit Flachsch

8、lauchThis European Standard was approved by CEN on 31 January 2009.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical

9、references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN membe

10、r into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latv

11、ia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: Avenue Marnix 17, B-1000 Brussels 20

12、09 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 671-3:2009: EEN 671-3:2009 (E) 2 Contents Page Foreword 3Introduction .41 Scope 52 Normative references 53 Terms and definitions .54 Routine checks by the responsible person 65 Recor

13、ds of hose reels and hose systems .66 Inspection and maintenance 66.1 Annual inspection and maintenance .66.2 Periodic inspection and maintenance for all hoses .77 Records of inspection and maintenance 78 Fire safety during inspection and maintenance .79 Rectification of defects .810 Maintenance and

14、 inspection label .8DIN EN 671-3:2009-07 EN 671-3:2009 (E) 3 Foreword This document (EN 671-3:2009) has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting systems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, eith

15、er by publication of an identical text or by endorsement, at the latest by September 2009, and conflicting national standards shall be withdrawn at the latest by September 2009. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN

16、and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 671-3:2000. EN 671 has the general title Fixed firefighting systems Hose systems and is in three parts: Part 1: Hose reels with semi-rigid hose; Part 2: Hose systems with lay-flat

17、hose; Part 3: Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czec

18、h Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. DIN EN 671-3:2009-07 EN 671-3:2009 (E) 4 Intr

19、oduction Hose reels and hose systems in proper condition provide a very effective firefighting facility with a continuous supply of water available immediately. They are especially valuable in an early stage of fire and can be operated efficiently by an untrained person. Hose reels and hose systems

20、will have a long service life but it shall be realized that their usefulness depends on maintenance to ensure instant readiness when required. DIN EN 671-3:2009-07 EN 671-3:2009 (E) 5 1 Scope This European Standard specifies requirements for inspection and maintenance of hose reels and hose systems

21、such that they continue to provide the service for which they were manufactured, supplied or installed i.e. to ensure a first emergency intervention to fight a fire before more powerful means can be implemented. This European Standard is applicable to hose reel and hose system installations in all t

22、ypes of buildings irrespective of the nature of use of the buildings. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced d

23、ocument (including any amendments) applies. EN 671-1:2001, Fixed firefighting systems Hose systems Part 1: Hose reels with semi-rigid hose EN 671-2:2001, Fixed firefighting systems Hose systems Part 2: Hose systems with lay-flat hose EN 694:2001, Fire-fighting hoses Semi-rigid hoses for fixed system

24、s 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 694:2001, EN 671-1:2001, EN 671- 2:2001 and the following apply. 3.1 competent person person with the necessary training and experience with access to the relevant tools, equipment and information, man

25、uals and knowledge of any special procedures recommended by the manufacturer, to be capable of carrying out the relevant maintenance procedures of this European Standard 3.2 maintenance combination of all technical and administrative actions including supervision actions, intended to retain an item,

26、 or restore it to a state in which it can perform a required function 3.3 responsible person person responsible for or having effective control over fire safety provisions adopted in or appropriate to the premises or the building NOTE Due to national regulations the responsible person could either b

27、e the user or the owner of the premises. 3.4 supplier party responsible for the product, process or service and able to ensure that the quality assurance is exercised NOTE The definition may apply to manufacturers, distributors, importers, assemblers, service organizations. DIN EN 671-3:2009-07 EN 6

28、71-3:2009 (E) 6 4 Routine checks by the responsible person Regular checks of all hose reels and hose systems shall be carried out by the responsible person or his representative at intervals depending on environmental circumstances and/or fire risk/hazard, to make sure that each hose reel or hose sy

29、stem is: a) located in the designated place; b) unobstructed, visible and has legible operating instructions; c) not obviously defective, corroded or leaking. The responsible person shall arrange for immediate corrective action, where necessary. The result of regular checks shall be recorded by the

30、responsible person. 5 Records of hose reels and hose systems In order to check conformity with the manufacturers instructions of the hose reel or hose system installation, the responsible person shall keep records of a plan showing the exact location and technical data of the installation. 6 Inspect

31、ion and maintenance 6.1 Annual inspection and maintenance The inspection and maintenance shall be carried out by the competent person. The hose shall be fully run out, put under building system pressure and the following points checked: a) the appliance is unobstructed and free from damage and compo

32、nents not corroded or leaking; b) operating instructions are clear and legible; c) the location is clearly marked; d) brackets for wall mounting are suitable for their purpose and are fixed and firm; e) the flow of water is steady and sufficient; NOTE The use of flow indicator and pressure gauge is

33、recommended. For lay flat hose systems this test can be done with another hose with the same specifications e.g. shorter length. f) pressure gauge, if fitted, is working satisfactorily and within its operating range; g) the entire length of hose shall be inspected for signs of cracking, distortion,

34、wear or damage; if the hose shows any signs of defect it shall be replaced or proof-tested to maximum working pressure; h) hose clips or bindings are of the correct type and are securely fastened; i) hose drums rotates freely in both directions; j) for swinging reels, check that the pivot rotates ea

35、sily and that the reel swings minimum required angles stated in Parts 1 and 2 of this European Standard; DIN EN 671-3:2009-07 EN 671-3:2009 (E) 7 k) on manual reels, check the manual stop valve is of correct type and that it operates easily and correctly; l) on automatic reels, check the correct ope

36、ration of the automatic valve and check for the correct operation of the isolating service valve; m) check the condition of the water supply pipe work, particular attention shall be paid to any flexible pipe work for signs of damage or wear; n) if fitted with a cabinet, check for signs of damage and

37、 check that the cabinet doors open freely; o) check that the nozzle is of the correct type and easy to operate; p) check the operation of any hose guide and ensure they are correctly and firmly fixed; q) leave the hose reel and hose system ready for immediate use; if any extensive maintenance is nec

38、essary the hose reel or hose system shall be labelled “OUT OF ORDER“ and the competent person shall inform the user/owner. 6.2 Periodic inspection and maintenance for all hoses Every 5 years all hoses shall be pressurized to maximum working pressure according to EN 671-1 and/or EN 671-2. 7 Records o

39、f inspection and maintenance The record shall include: a) date (year and month); b) result; c) extent and date of installation of replacement parts; d) if any further action is required; e) date (year and month) for the next inspection and maintenance; f) identification of each hose reel and/or hose

40、 system. After inspection and maintenance it is recommended that hose reel and hose system is protected with a security seal. After inspection and necessary corrective measures (6.1 and 6.2), hose reels and hose systems shall be marked “CHECKED“ by the competent person. A permanent record of all ins

41、pections, checks and tests shall be kept by the responsible person. 8 Fire safety during inspection and maintenance Because inspection and maintenance can temporarily reduce the effectiveness of fire protection: a) depending on the estimated fire hazard, only a limited number of hose reels and hose

42、systems shall undergo extensive maintenance simultaneously in one particular area; DIN EN 671-3:2009-07 EN 671-3:2009 (E) 8 b) the provision of additional fire safety precautions and safety instructions shall be considered during the maintenance period and during periods when water supplies are shut

43、 down. 9 Rectification of defects Only components (for example hoses, nozzles, inlet stop valves) approved by the manufacturer/supplier of the hose reel or hose system shall be used to replace those components found to be defective. NOTE It is essential that all defects are rectified in the shortest

44、 possible time to ensure that the firefighting installation is restored in a satisfactory condition. 10 Maintenance and inspection label Maintenance and inspection data shall be recorded on a label which shall not cover any of the manufacturers marking. The following data shall be provided on the label: a) the wording CHECKED (see 7); b) name and address of the hose reel or hose system supplier (see 3.4); c) mark clearly identifying the competent person (see 3.1); d) date (year and month) when the maintenance was carried out (see 6.1 and 6.2). DIN EN 671-3:2009-07

展开阅读全文
相关资源
  • DIN EN 818-7-2008 Short link chain for lifting purposes - Safety - Part 7 Fine tolerance hoist chain Grade T (Types T DAT and DT)(includes Amendment A1 2008) Ge.pdfDIN EN 818-7-2008 Short link chain for lifting purposes - Safety - Part 7 Fine tolerance hoist chain Grade T (Types T DAT and DT)(includes Amendment A1 2008) Ge.pdf
  • DIN EN 1677-3-2008 Components for slings - Safety - Part 3 Forged steel self-locking hooks Grade 8(includes Amendment A1 2008) English version of DIN EN 1677-3 .pdfDIN EN 1677-3-2008 Components for slings - Safety - Part 3 Forged steel self-locking hooks Grade 8(includes Amendment A1 2008) English version of DIN EN 1677-3 .pdf
  • DIN EN 1677-2-2008 Components for slings - Safety - Part 2 Forged steel lifting hooks with latch Grade 8(includes Amendment A1 2008) English version of DIN EN 1.pdfDIN EN 1677-2-2008 Components for slings - Safety - Part 2 Forged steel lifting hooks with latch Grade 8(includes Amendment A1 2008) English version of DIN EN 1.pdf
  • DIN EN 1670-2007 Building hardware - Corrosion resistance - Requirements and test methods English version of DIN EN 1670 2007-06《建筑五金器具 耐腐蚀 要求和试验方法》.pdfDIN EN 1670-2007 Building hardware - Corrosion resistance - Requirements and test methods English version of DIN EN 1670 2007-06《建筑五金器具 耐腐蚀 要求和试验方法》.pdf
  • DIN EN 1656-2010 Chemical disinfectants and antiseptics - Quantitative suspension test for the evaluation of bactericidal activity of chemical disinfectants and.pdfDIN EN 1656-2010 Chemical disinfectants and antiseptics - Quantitative suspension test for the evaluation of bactericidal activity of chemical disinfectants and.pdf
  • DIN EN 1230-2-2018 Paper and board intended to come into contact with foodstuffs - Sensory analysis - Part 2 Off-flavour (taint) German version EN 1230-2 2009《用.pdfDIN EN 1230-2-2018 Paper and board intended to come into contact with foodstuffs - Sensory analysis - Part 2 Off-flavour (taint) German version EN 1230-2 2009《用.pdf
  • DIN EN 1176-7-2008 Playground equipment and surfacing - Part 7 Guidance on installation inspection maintenance and operation English version of DIN EN 1176-7 20.pdfDIN EN 1176-7-2008 Playground equipment and surfacing - Part 7 Guidance on installation inspection maintenance and operation English version of DIN EN 1176-7 20.pdf
  • DIN EN 1176-5-2008 Playground equipment and surfacing - Part 5 Additional specific safety requirements and test methods for carousels English version of DIN EN .pdfDIN EN 1176-5-2008 Playground equipment and surfacing - Part 5 Additional specific safety requirements and test methods for carousels English version of DIN EN .pdf
  • DIN EN 1159-1-2007 Advanced technical ceramics - Ceramic composites - Thermophysical properties - Part 1 Determination of thermal expansion (includes Corrigendu.pdfDIN EN 1159-1-2007 Advanced technical ceramics - Ceramic composites - Thermophysical properties - Part 1 Determination of thermal expansion (includes Corrigendu.pdf
  • DIN EN 1093-4-2008 Safety of machinery - Evaluation of the emission of airborne hazardous substances - Part 4 Capture efficiency of an exhaust system - Tracer m.pdfDIN EN 1093-4-2008 Safety of machinery - Evaluation of the emission of airborne hazardous substances - Part 4 Capture efficiency of an exhaust system - Tracer m.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > DIN

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1