1、BRITISH STANDARDBS EN 14384:2005Pillar fire hydrantsThe European Standard EN 14384:2005 has the status of a British StandardICS 13.220.10g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g

2、38g50g51g60g53g44g42g43g55g3g47g36g58BS EN 14384:2005This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 November 2006 BSI 2006ISBN 0 580 49516 7National forewordThis British Standard was published by BSI. It is the UK implementation of EN 143

3、84:2005.The UK participation in its preparation was entrusted by Technical Committee FSH/17, Fire brigade equipment, to Subcommittee FSH/17/1, Hydrants, hydrant systems, couplings and indicator plates.A list of organizations represented on FSH/17/1 can be obtained on request to its secretary.This pu

4、blication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations.Amendments issued since publicationAmd. No. Date CommentsEUROPEAN STANDARDNORME EUROPEN

5、NEEUROPISCHE NORMEN 14384July 2005ICS 13.220.10English versionPillar fire hydrantsPoteaux dincendie berflurhydrantenThis European Standard was approved by CEN on 20 June 2005.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this Euro

6、peanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, F

7、rench, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Repub

8、lic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATION

9、EUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2005 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14384:2005: EEN 14384:2005 (E) 2 Contents Page Foreword 3 Introduction4 1 Scope .5 2 Normative

10、references .5 3 Terms and definitions.6 4 Design requirements 7 4.1 Dimensions7 4.2 Shell .8 4.3 Elastomers.8 4.4 Obturator main valve .9 4.5 Materials including lubricants in contact with water intended for human consumption 9 4.6 Leaktightness and mechanical strength .9 4.7 Components of the opera

11、ting system .10 4.8 Closing direction.10 4.9 Opening turns .10 4.10 Resistance of the hydrant to operating loads.10 4.11 Operating mechanism 11 4.12 Inlet connections.11 4.13 Outlets .11 4.14 Drainage and venting systems 11 4.15 Security housing.12 4.16 Internal and external corrosion resistance .12

12、 4.17 Colour 12 4.18 Resistance to disinfection products12 4.19 Hydrants for non-potable water systems12 4.20 Hydraulic characteristics12 5 Test methods.13 5.1 General 13 5.2 General dimensions13 5.3 Flow characteristics13 6 Designation, marking and additional data 15 6.1 Designation .15 6.2 Marking

13、 of hydrants15 6.3 Additional hydrant data 16 7 Evaluation of conformity 17 7.1 General 17 7.2 Initial type testing17 7.3 Factory product control (FPC) .18 Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive (89/106/EEC).22 ZA.

14、1 Scope and relevant clauses .22 ZA.2 Procedure for the attestation of conformity of pillar fire hydrants .23 ZA.3 CE marking24 ZA.4 Certificate and Declaration of Conformity.26 Bibliography.27 EN 14384:2005 (E) 3 Foreword This European Standard (EN 14384:2005) has been prepared by Technical Committ

15、ee CEN/TC 192 “Fire service equipment”, the secretariat of which is held by BSI, in cooperation with CEN/TC 164 “Water supply“ and CEN/TC 69 “Industrial Valves”. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at

16、the latest by January 2006, and conflicting national standards shall be withdrawn at the latest by January 2006. This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directi

17、ve(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this European Standard. This is one of a series of standards for fire hydrants. This is the first edition of this European Standard. No International Standard exists for pillar fire hydrants. Accordi

18、ng to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania

19、, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EN 14384:2005 (E) 4 Introduction The purpose of a fire hydrant installation is to provide a connection (i.e. hydrant) to the water main to which the firefighter can connect

20、firefighting equipment. Pillar fire hydrants consist of one or more valves and connection outlets in a column shape, which emerges from below ground level, intended primarily to supply water for firefighting and also may be used by water utilities (as defined in 3.3). This European Standard is in co

21、nformity with the general requirements already established by CEN/TC 164 in the field of water supply. In respect of potential adverse effects on the quality of water intended for human consumption caused by the product covered by this European Standard: 1) this European Standard provides no informa

22、tion as to whether the product may be used without restriction in any of the Member States of the EU or EFTA, 2) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national regulations concerning the use and/or the characteristics of this product remain in

23、 force. EN 14384:2005 (E) 5 1 Scope This European Standard specifies the minimum requirements, test methods, marking and evaluation of conformity for pillar hydrants for fire fighting purposes: to be installed in a water distribution system; sizes DN 80, DN 100 and DN 150; suitable for an allowable

24、operating pressure, PFA, of PN 16 with or without drain facility; having vertical or horizontal, flanged, socket or spigot inlet; with one or two outlets and having outlets to national requirements; globe (screw down) or gate valve type. This European Standard also provides for the evaluation of con

25、formity of the pillar fire hydrants to the requirements of this European Standard. This European Standard applies to fire hydrants for potable and non potable water and for filtered water. Additional requirements may apply for other liquids. Couplings connected to outlets are outside the scope of th

26、is European Standard and should conform to national requirements. 2 Normative references The following referenced documents are indispensable for the application of this European Standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referen

27、ced document (including any amendments) applies. EN 681-1, Elastomeric seals Material requirements for pipe joint seals used in water and drainage applications Part 1: Vulcanized rubber EN 1074-1:2000, Valves for water supply Fitness for purpose requirements and appropriate verification tests Part 1

28、: General requirements EN 1074-2:2000, Valves for water supply Fitness for purpose requirements and appropriate verification tests Part 2: Isolating valves EN 1074-6:2004, Valves for water supply Fitness for purpose requirements and appropriate verification tests Part 6: Hydrants EN 1092-1, Flanges

29、and their joints Circular flanges for pipes, valves, fittings and accessories, PN designated Part 1: Steel flanges EN 1092-2, Flanges and their joints Circular flanges for pipes, valves, fittings and accessories, PN designated Part 2: Cast iron flanges EN 1503-1, Valves Materials for bodies, bonnets

30、 and covers Part 1: Steels specified in European Standards EN 1503-3, Valves Materials for bodies, bonnets and covers Part 3: Cast irons specified in European Standards EN ISO 9001:2000, Quality management systems Requirements (ISO 9001:2000) EN 14384:2005 (E) 6 3 Terms and definitions For the purpo

31、ses of this European Standard, the following terms and definitions apply. 3.1 hydrant connection to a water supply system including an isolating valve EN 1074-6:2004 3.2 fire hydrant hydrant designed to supply water for fire fighting during all phases of the fire 3.3 pillar fire hydrant fire hydrant

32、 with column shape, which emerges from below ground level, intended primarily to supply water for firefighting and also may be use by water utilities 3.4 dry pillar fire hydrant pillar fire hydrant, the column of which empties automatically when the main valve is closed 3.5 wet pillar fire hydrant p

33、illar fire hydrant, the column of which remains full of water 3.6 break system mechanism which allows the above ground part of the hydrant to separate from the below ground part when subjected to impact whilst maintaining the seal of the main valve 3.7 obturator movable component of the valve whose

34、position in the fluid flow path permits, restricts or obstructs the fluid flow (see EN 736-2) 3.8 loose obturator device for controlling flow out of a pipeline but which prevents flow into a pipeline 3.9 shell pressure-containing envelope of the valve NOTE It normally comprises the body and, when in

35、cluded in the design, a bonnet or cover and the body bonnet or body cover joint (see EN 736-2). 3.10 DN nominal size alphanumeric designation of the size of pipework components used for reference purposes. It comprises the letters DN followed by a dimensionless round number which is loosely related

36、to the effective dimensions, in millimetres, of the bore or external diameter of the end connections EN 1074-1:2000 3.11 PN nominal pressure alphanumeric designation used for reference purposes and related to a combination of numerical and dimensional characteristics of a component of a pipe system.

37、 It comprises the letters PN followed by a dimensionless round number EN 1074-1:2000 EN 14384:2005 (E) 7 3.12 allowable maximum operating pressure PMA maximum hydrostatic pressure including surge that a component can withstand from time to time in service EN 1074-1:2000 3.13 allowable operating pres

38、sure PFA maximum hydrostatic pressure that a component can withstand continuously in service EN 1074-1:2000 3.14 allowable test pressure PEA maximum hydrostatic pressure that a newly installed component can withstand for a relatively short duration when either fixed above ground level or laid and ba

39、ckfilled underground in order to ensure the integrity and tightness of the pipeline (see EN 1074-1) 3.15 flow coefficient Kv (Cv) rate of flow in cubic metres per hour that will cause a differential pressure of one bar through the fire hydrant (see EN 736-3) 4 Design requirements 4.1 Dimensions Dime

40、nsions (see Figure 1) shall be as follows: H 300 mm. The nominal outlet angle a shall be 60 a 90. All the outlets shall be within an included nominal angle b of 180, and shall allow all the hose couplings to be fitted at the same time. The tolerances on the nominal angles a and b shall be 5. General

41、 dimensions shall be measured according to 5.2. EN 14384:2005 (E) 8 2H IH 2abb1Key 1 Ground H1 Distance from outlet to ground 2 Point of connection to the water supply H2 Distance from top of hydrant to point of a Nominal outlet angle connection to water supply b Nominal outlets included angle Figur

42、e 1 General dimensions 4.2 Shell The shell of the pillar fire hydrants shall be made of the materials given in Table 1. Table 1 Shell materials Material Reference standard Flake graphite cast iron EN 1503-3 Spheroidal graphite cast iron EN 1503-3 Steel EN 1503-1 4.3 Elastomers All elastomeric seals

43、within the hydrant shall comply with EN 681-1. They shall be either type WA for cold potable water use or suitable for the fluid with which they come into contact (see 4.6). EN 14384:2005 (E) 9 4.4 Obturator main valve Any design of the main valve shall be accepted provided that it meets the require

44、ments of this European Standard. The manufacturer shall declare if the design of the hydrant permits the obturator to be replaced in situ. NOTE For safety reasons the replacement should be carried out when the fire hydrant is not under pressure. 4.5 Materials including lubricants in contact with wat

45、er intended for human consumption Pending the introduction of a common European Approvals Scheme E.A.S., all materials including lubricants in the construction of a hydrant, that are likely to come into contact with water for human consumption, shall comply with the national regulations in the count

46、ry of use. 4.6 Leaktightness and mechanical strength 4.6.1 General The hydrant shall be suitable for use at the relevant pressures shown in Table 2, and shall meet the requirements of 4.6.2 to 4.6.4. Table 2 Pressures PN PFA MPa (bar) PMA MPa (bar) PEA a(1) MPa (bar) 16 1,6 (16) 2,0 (20) 2,5 (25) aP

47、EA only applies to valves not in the closed position. 4.6.2 Shell and all pressure containing components (including steam seals) 4.6.2.1 Leaktightness When tested in accordance with Annex A of EN 1074-1:2000, using the values of PEA from Table 2, there shall be no visible sign of leakage past the va

48、lve. NOTE This is equivalent to rate “A“ as defined in EN 1074-1:2004. 4.6.2.2 Mechanical strength Having successfully passed the leak tightness test, additionally, the hydrant shall not present any sign of defect. 4.6.3 Obturator 4.6.3.1 Leaktightness When tested in accordance with Annex B of EN 10

49、74-1:2000, using the value 1,1 PFA from Table 2, there shall be no visible sign of leakage past the valve. NOTE This is equivalent to rate “A“ as defined in EN 1074-1:2004. EN 14384:2005 (E) 10 4.6.3.2 Mechanical strength Having successfully passed the leak tightness test, additionally, the hydrant shall not present any sign of defect. 4.6.4 Operating cycles, endurance The requirements and test method shall be in accordance with EN 1074-6:2004, 5.5.1, by using the values given in Table 3 for t