1、BSI Standards PublicationBS EN 15254-6:2014Extended application of resultsfrom fire resistance tests Non-loadbearing wallsPart 6: Curtain wallingBS EN 15254-6:2014 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 15254-6:2014.The UK participation in its preparati
2、on was entrusted to TechnicalCommittee FSH/22/-/7, Non loadbearing separating elements.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for it
3、s correctapplication. The British Standards Institution 2014. Published by BSI StandardsLimited 2014ISBN 978 0 580 76523 0ICS 13.220.50; 91.060.10Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Po
4、licy and Strategy Committee on 31 January 2014.Amendments issued since publicationDate Text affectedBS EN 15254-6:2014EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15254-6 January 2014 ICS 13.220.50; 91.060.10 English Version Extended application of results from fire resistance tests - Non-lo
5、adbearing walls - Part 6: Curtain walling Application tendue des rsultats dessais de rsistance au feu - Murs non porteurs - Partie 6: Murs rideaux Erweiterter Anwendungsbereich der Ergebnisse von Feuerwiderstandsprfungen - Nichttragende Wnde - Teil 6: Vorhangfassaden This European Standard was appro
6、ved by CEN on 9 November 2013. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
7、 standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language
8、and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hun
9、gary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CEN
10、ELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2014 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15254-6:2014 EBS EN 15254-6:2014EN 15254-6:2014 (E) 2 Contents Page Foreword 3 1 Scope 4 2 Normative references 4 3 Term
11、s and definitions .4 4 Principles 5 4.1 General principles5 4.2 Use of test evidence 5 4.3 Analysis of test results .5 5 General rules 5 5.1 Fire resistance classification 5 5.2 Combination of extended application5 5.3 Overrun time .5 6 Specific rules for curtain walling type B .6 6.1 General 6 6.2
12、Rules for the complete construction .6 6.3 Framing system .7 6.4 Fire resistant translucent or transparent infill panels .8 7 Specific rules for curtain walling type A .9 7.1 General 9 7.2 Rules for the complete construction .9 7.3 Framing system 10 7.4 Fire resistant translucent or transparent infi
13、ll panels 10 8 Report of the extended application analysis . 10 8.1 Contents of the extended application report . 10 8.2 Review of the extended application report 11 Annex A (normative) Radiation calculation . 14 A.1 General . 14 A.2 Rectangular fire resistant translucent or transparent infill panel
14、s . 14 A.3 Circular fire resistant translucent or transparent infill panels . 15 A.4 Other shapes of fire resistant translucent or transparent infill panels with EW-classification . 15 BS EN 15254-6:2014EN 15254-6:2014 (E) 3 Foreword This document (EN 15254-6:2014) has been prepared by Technical Com
15、mittee CEN/TC 127 “Fire Safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 2014, and conflicting national standards shall be withdr
16、awn at the latest by July 2014. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given
17、to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of 89/106/EEC. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Bel
18、gium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switz
19、erland, Turkey and the United Kingdom. BS EN 15254-6:2014EN 15254-6:2014 (E) 4 1 Scope This European Standard provides guidance and, where appropriate, defines procedures for variations of certain parameters and factors associated with the design of curtain walling according to EN 13830 which have b
20、een tested in accordance with EN 1364-3 and classified according to EN 13501-2 (curtain walling type B according to 3.2), components of curtain walling type A or type B according to 3.1 and 3.2, e.g. spandrel panels, which have been tested in accordance with EN 1364-4, and classified according to EN
21、 13501-2. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including
22、 any amendments) applies. EN 1363-1, Fire resistance tests - Part 1: General Requirements EN 1363-2, Fire resistance tests - Part 2: Alternative and additional procedures EN 1364-3:2014, Fire resistance tests for non-loadbearing elements Part 3: Curtain walling Full configuration (complete assembly)
23、 EN 1364-4:2014, Fire resistance tests for non-loadbearing elements Part 4: Curtain walling Part configuration EN 13119, Curtain walling - Terminology EN 13501-2, Fire classification of construction products and building elements Part 2: Classification using data from fire resistance tests, excludin
24、g ventilation services EN 13830, Curtain walling - Product standard EN ISO 13943, Fire safety - Vocabulary (ISO 13943) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1, EN 1363-2, EN 1364-3, EN 1364-4, EN 13119, EN 13830, EN ISO 13943 and the fo
25、llowing apply. 3.1 curtain walling Type A for definition see EN 1364-3 3.2 curtain walling Type B for definition see EN 1364-3 3.3 vertically faceted curtain walling curtain walling with a vertical and a sloped part without fixing/bracket at the joint (see Figure 1) BS EN 15254-6:2014EN 15254-6:2014
26、 (E) 5 4 Principles 4.1 General principles Extended application is a prediction of the expected fire resistance performance of a fire resistant curtain walling or its components. It may be based either on interpolation between or extrapolation from test data according to EN 1364-3 and/or EN 1364-4.
27、Curtain walling function as integral systems in which the individual components (e.g. frames and fixing of the framing system (anchoring), infill panels, perimeter seals and vertical linear gap seals) are combined in such a way that they are effective in meeting the defined fire resistance criteria.
28、 In this document in addition to rules for the complete construction rules are defined for the components of curtain walling which are separately characterised as the framing system, the fixing of the framing system (anchoring), the infill panels and its fixing methods, the perimeter seal and the ve
29、rtical linear gap seals as well as the supporting construction (floor and walls). 4.2 Use of test evidence The applicant for the extended application shall either be the “owner” (i.e. sponsor) of all test data being submitted for the extension, or have written permission from the owner to use the su
30、bmitted test evidence. 4.3 Analysis of test results In order to maximise the extended field of application, it is important that the test reports shall record details of any premature integrity and / or insulation failure. Where a series of tests have been conducted, the field of extended applicatio
31、n shall be based on the lowest performance achieved from the complete series of tests unless premature failure has been attributed to one or more specific construction parameter variations. Where it has been possible, to identify specific parameter failures, the extended application for all other co
32、nstruction parameter variations can be based on the performance achieved after isolating the premature failure(s). 5 General rules 5.1 Fire resistance classification In the extended application, an increase in the classification time (e.g. from 30 min to 45 min) and changes to the fire resistance cl
33、assification (e.g. from E to EW to EI) are not permitted. 5.2 Combination of extended application Each extended application shall be the subject of a separate evaluation. Within this application it is allowed to produce a combination of extensions provided these combinations can be substantiated by
34、the supporting test evidence. 5.3 Overrun time For some rules to be applicable an overrun time in the fire test result compared to the envisaged classification time is required. The required overrun time is shown in Table 1. The overrun time is required for the following criteria: E classification:
35、integrity BS EN 15254-6:2014EN 15254-6:2014 (E) 6 EW classification: integrity and radiation EI classification: integrity and insulation Table 1 Overrun time Classification Time Overrun time 20 min minimum 3 min 30, 45 and 60 min minimum 6 min 90 min minimum 10 % of the classification time 6 Specifi
36、c rules for curtain walling type B 6.1 General Minimum one test according to EN 1364-3 is required. The assessment of the extended field of application may be based on additional test results from EN 1364-4 or EN 1364-3. The rules given in 6.2 to 6.4 apply to stick constructions only except where st
37、ated otherwise. Rules which result in higher weight of the curtain walling are only applicable if the fixing of the framing system used in practice has been designed for the higher load. The measured temperature at the fixing of the framing system shall be taken into account. 6.2 Rules for the compl
38、ete construction 6.2.1 Width for curtain walling with classification EW Test results are also valid for curtain walling with classification EW extending over one or more fire separating walls with a higher distance between the fire separating walls than the width of the tested construction if in add
39、ition to the criteria given in EN 1364-3 the radiation criterion is fulfilled for the resulting larger area. The radiation criterion shall be assessed using the rules given in A.1. The result of a calculation for a width equalling three times the tested width or minimum 9 m, whatever is larger, is a
40、pplicable to any larger width. An increase in width is only permitted by replicating the tested construction (especially type and dimensions of infill panels) in the same arrangement as tested. 6.2.2 Span length for curtain walling with classification EW Test results are also valid for curtain walli
41、ng with classification EW for a higher span length than used in the test if in addition to the criteria given in EN 1364-3 the radiation criterion is fulfilled for the resulting larger area. The radiation criterion shall be assessed using the rules given in A.1. This rule applies also to unitised co
42、nstructions. 6.2.3 Installation angle (vertical/sloped) Test results cover all installation angles between the maximum and minimum angle used in tests. This rule applies also to unitised constructions. 6.2.4 Vertically faceted curtain walling Test results cover all angles between vertically adjacent
43、 infill panels between the maximum and minimum angle used in tests. This rule applies also to unitised constructions. BS EN 15254-6:2014EN 15254-6:2014 (E) 7 6.2.5 Horizontally faceted curtain walling For corners and facet angles not covered by the rules given in EN 1364-3 the following rules apply:
44、 EI classification: Results from tests of faceted specimens according to EN 1364-3 using the test configurations A and B or alternatively E as illustrated in EN 1364-3:2014, Figure 8 and from minimum one test of a straight specimen cover all angles between horizontally adjacent infill panels at the
45、common mullion from 45 to 315 (see Figure 2) with classification EI (o i). E, EW classification: Results from tests of faceted specimens according to EN 1364-3 using the test configurations A, B, C and D or alternatively E and F as illustrated in EN 1364-3:2014, Figure 8 and from minimum one test of
46、 a straight specimen cover all angles between horizontally adjacent infill panels at the common mullion from 45 to 315 (see Figure 2) with classification E (o i) or EW (o i) respectively. 6.2.6 Inclusion of doors and/or windows Doors and/or windows may be included into a curtain walling and the rule
47、s of the EN 15269 series may be used provided an additional test as required by the standards of the EN 15269 series was conducted using the intended curtain walling as the associated supporting construction with the dimensions d 200 mm (see Figure 3). NOTE Dimensions d 500 mm are recommended. The f
48、ield of application of the classified curtain walling may be used when doors and/or windows are included in the curtain walling provided the test(s) including door(s) and/or window(s) has been conducted with internal fire exposure and surface S1 exposed to the fire as defined in EN 1364-3 and EN 136
49、4-4, and the smallest mullion size has been used in case of timber framing, or the largest mullion size has been used in case of metal framing These rules apply also to unitised constructions. 6.3 Framing system 6.3.1 Dimension of mullions and transoms All dimensions of mullions and transoms are covered between maximum and minimum tested. 6.3.2 Connection between mullions and transoms 6.3.2.1 Connection geometry For angles between mullions and transoms between a minimum of 80 degrees and a maximum of 100 degrees, see EN 1364-3. For an