1、 Tentative Interim Amendment NFPA 13 Standard for the Installation of Sprinkler Systems 2016 Edition Reference: 17.2.3.5.6, A.17.2.3.5 and A.17.3.3.5 TIA 16-1 (SC 15-8-14 / TIA Log #1165) Note: Text of the TIA was issued and approved for incorporation into the document prior to printing. 1. Revise s

2、ection 17.2.3.5.6 to read as follows: 17.2.3.5.6 The minimum operating pressure shall be either 30 psi (2.0 bar) or 60 psi (4.1 bar) based upon the applicable storage and ceiling height for the installation as follows: a) 30 psi (2.0 bar) for storage heights up to 25 ft (7.6 m) with a maximum ceilin

3、g height of 30 ft (9.1 m) b) 60 psi (4.1 bar) for storage heights up to 25 ft. (7.6 m) with a maximum ceiling height of 40 ft (12.2 m). 2. Revise section A.17.2.3.5 to read as follows: A.17.2.3.5 The Fire Protection Research Foundation conducted a series of full-scale fire tests at Underwriters Labo

4、ratories to develop protection criteria for the rack storage of exposed expanded Group A plastic commodities. The tests are documented in the report, “Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers.” The criteria for exposed expanded plastics a

5、re based on Tests 2, 3, 7 and 8 of the series, which investigated a 40 ft (12.2 m) ceiling with a range of storage heights. The tests used K-25.2 intermediate-temperature ESFR sprinklers with vertical barriers attached to the rack uprights at nominal 16 ft (4.9 m) apart. Vertical barriers of sheet m

6、etal and 38 -in. plywood were both investigated. In Tests 1 through 6, transverse flue spaces between commodities were blocked. Comparing the results of Test 6 with blocked transverse flue spaces and Test 7 with no blocking of transverse flue spaces, the number of operated sprinklers decreased from

7、11 to 7 and improved suppression of the fire. The criteria for exposed expanded plastics are based on Tests 9 and 10 of the series, which investigated a 30 ft (9.1 m) ceiling with a range of storage heights. The tests used K-25.2 intermediate-temperature ESFR sprinklers with vertical barriers attach

8、ed to the rack uprights at 16 ft (4.9 m) (nominal) apart. Vertical barriers of 3 8 -in. plywood was investigated. The area limitation between the vertical barriers and aisles indicated in 17.3.3.5.9.2 will limit the depth of a multiple-row rack arrangement. The hose stream allowance and water supply

9、 duration requirements considered the burning characteristics of the exposed expanded plastic commodity that generates a high rate of heat release very quickly, but the commodity involved in the combustion process is then quickly consumed after fire suppression or control is achieved. 3. Revise sect

10、ion A.17.3.3.5 to read as follows: A.17.3.3.5 The Fire Protection Research Foundation conducted a series of full-scale fire tests at Underwriters Laboratories to develop protection criteria for the rack storage of exposed expanded Group A plastic commodities. The tests are documented in the report,

11、Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers.” The criteria for exposed expanded plastics are based on Tests 2, 3,7 and 8 of the series, which investigated a 40 ft (12.2 m) ceiling with a range of storage heights. The tests used K-25.2 inter

12、mediate-temperature ESFR sprinklers with vertical barriers attached to the rack uprights at nominal 16 ft (4.9 m) apart. Vertical barriers of sheet metal and 3 8 -in. plywood were both investigated. In Tests 1 through 6, transverse flue spaces between commodities were blocked. Comparing the results

13、of Test 6 with blocked transverse flue spaces and Test 7 with no blocking of transverse flue spaces, the number of operated sprinklers decreased from 11 to 7 and improved suppression of the fire. The area limitation between the vertical barriers and aisles indicated in 17.3.3.5.9.2 will limit the de

14、pth of a multiple-row rack arrangement. The hose stream allowance and water supply duration requirements considered the burning characteristics of the exposed expanded plastic commodity that generates a high rate of heat release very quickly, but the commodity involved in the combustion process is then quickly consumed after fire suppression or control is achieved. Issue Date: August 18, 2015 Effective Date: September 7, 2015 (Note: For further information on NFPA Codes and Standards, please see www.nfpa.org/codelist) Copyright 2015 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION

展开阅读全文
相关资源
猜你喜欢
  • DS ISO 3305-1989 Plain end welded precision steel tubes Technical conditions for delivery《光端焊接精密钢管材 交货的技术条件》.pdf DS ISO 3305-1989 Plain end welded precision steel tubes Technical conditions for delivery《光端焊接精密钢管材 交货的技术条件》.pdf
  • DS ISO 3306-1989 Plain end as-welded and sized precision steel tubes Technical conditions for delivery《焊接光端钢管和精密钢管 交货的技术条件》.pdf DS ISO 3306-1989 Plain end as-welded and sized precision steel tubes Technical conditions for delivery《焊接光端钢管和精密钢管 交货的技术条件》.pdf
  • DS ISO 3320-1989 Fluid power systems and components Cylinder bores and piston rod diameters Metric series《液压传动系统和元件 油缸内径和活塞杆直径 米制系列》.pdf DS ISO 3320-1989 Fluid power systems and components Cylinder bores and piston rod diameters Metric series《液压传动系统和元件 油缸内径和活塞杆直径 米制系列》.pdf
  • DS ISO 3339-0-1988 Tractors and machinery for agriculture and forestry Classification and terminology Part 0 Classification system and classification《农业和林业拖拉机和机械 分类和术语 第0部分 分类系统和分类.pdf DS ISO 3339-0-1988 Tractors and machinery for agriculture and forestry Classification and terminology Part 0 Classification system and classification《农业和林业拖拉机和机械 分类和术语 第0部分 分类系统和分类.pdf
  • DS ISO 334-1993 Solid mineral fuels Determination of total sulfur Eschka method《固体矿物燃料 总含硫量的测定 埃斯卡法》.pdf DS ISO 334-1993 Solid mineral fuels Determination of total sulfur Eschka method《固体矿物燃料 总含硫量的测定 埃斯卡法》.pdf
  • DS ISO 3371-1989 Modular units for machine tool construction Rotary tables and multi-sided centre bases for rotary tables《机床结构的组合件 旋转工作台和旋转工作台的多边中心支座》.pdf DS ISO 3371-1989 Modular units for machine tool construction Rotary tables and multi-sided centre bases for rotary tables《机床结构的组合件 旋转工作台和旋转工作台的多边中心支座》.pdf
  • DS ISO 3401-1992 Cigarettes Determination of alkaloid retention by the filters Spectrometric method《香烟 过滤嘴生物碱截留量的测定 光谱测定法》.pdf DS ISO 3401-1992 Cigarettes Determination of alkaloid retention by the filters Spectrometric method《香烟 过滤嘴生物碱截留量的测定 光谱测定法》.pdf
  • DS ISO 3476-1989 Modular units for machine tool construction Tenon drive and flanges for mounting multi-spindle heads《机床结构的组合件 多轴头安装的榫和法兰盘》.pdf DS ISO 3476-1989 Modular units for machine tool construction Tenon drive and flanges for mounting multi-spindle heads《机床结构的组合件 多轴头安装的榫和法兰盘》.pdf
  • DS ISO 3494-1980 Statistical interpretation of data Power of tests relating to means and variances《数据的统计分析 有关平均数和方差数的检验的功效》.pdf DS ISO 3494-1980 Statistical interpretation of data Power of tests relating to means and variances《数据的统计分析 有关平均数和方差数的检验的功效》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1