1、 Errata NFPA 72National Fire Alarm and Signaling Systems Code2016 Edition Reference: Table 14.4.3.2, item 22(b) and 21.6.2.1.2 Errata No: 72-16-1 The Technical Committee on Protected Premises Fire Alarm and Signaling Systems, the Technical Committee on Testing and Maintenance of Fire Alarm and Signa
2、ling Systems, and the Correlating Committee on Fire Alarm and Signaling Systems note the following errors in the 2016 edition of NFPA 72, Fire Alarm and Signaling Systems Code. 1. In Table 14.4.3.2, item 22(b), in the “Method” column, correct the cross reference to read as follows: For initial and r
3、eacceptance testing, measure Verify audible information to be distinguishable and understandable and in compliance with 14.4.11 14.4.10. 2. In 21.6.2.1.2(B)(4) and (5) correct the cross references to read as follows: 21.6.2.1.2* Floor Identification. (A) The output signal(s) shall identify each floo
4、r to be evacuated. (B) The identified floors shall be a contiguous lock of floors including the following: (4) Two floors above the highest floor identified by 21.6.2.1.2(CB)(1) through 21.6.2.1.2(CB)(3). (5) Two floors below the lowest floor identified by 21.6.2.1.2(CB)(1) through 21.6.2.1.2(CB)(3)
5、. Issue Date: February 27, 2018 (Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/docinfo) Copyright 2018 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION