REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf

上传人:孙刚 文档编号:1019659 上传时间:2019-03-21 格式:PDF 页数:9 大小:50.52KB
下载 相关 举报
REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf_第1页
第1页 / 共9页
REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf_第2页
第2页 / 共9页
REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf_第3页
第3页 / 共9页
REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf_第4页
第4页 / 共9页
REG UFGS-26 35 33 00 40-2013 POWER FACTOR CORRECTION EQUIPMENT.pdf_第5页
第5页 / 共9页
点击查看更多>>
资源描述

1、USACE / NAVFAC / AFCEC / NASA UFGS-26 35 33.00 40 (August 2013)-Preparing Activity: NASA SupersedingUFGS-26 35 33.00 40 (August 2010)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2013*SECTION TABLE OF CONTENTSDIVISION 26 - ELECTRICALSECTION 26 35 33.00 40PO

2、WER FACTOR CORRECTION EQUIPMENT08/13PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 QUALITY ASSURANCE1.4 PREDICTIVE TESTING AND INSPECTION TECHNOLOGY REQUIREMENTSPART 2 PRODUCTS2.1 FABRICATION2.2 COMPONENTS2.2.1 Metal-Enclosed Shunt Capacitor Equipment2.2.2 Pole Line Capacitors2.2.3 Metal-Enclosed Low

3、Voltage Capacitors2.2.4 Prevention of Corrosion2.3 FACTORY TESTINGPART 3 EXECUTION3.1 INSTALLATION3.2 FIELD TESTING- End of Section Table of Contents -SECTION 26 35 33.00 40 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFC

4、EC / NASA UFGS-26 35 33.00 40 (August 2013)-Preparing Activity: NASA SupersedingUFGS-26 35 33.00 40 (August 2010)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2013*SECTION 26 35 33.00 40POWER FACTOR CORRECTION EQUIPMENT08/13*NOTE: This guide specification co

5、vers the requirements for metal-enclosed shunt capacitor equipment. Drawings should show voltage and kilovar ratings and mounting and connection details.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new projec

6、t specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not br

7、ackets are present.Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: If Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS is not included in the project specification, ap

8、plicable requirements therefore should be inserted and the following paragraph deleted.*Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section.1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide SECTION

9、26 35 33.00 40 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wi

10、zards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted fro

11、m this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ASTM INTERNATIONA

12、L (ASTM)ASTM A1008/A1008M (2012a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake HardenedINSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)IEEE 18 (2012) Standa

13、rd for Shunt Power CapacitorsNATIONAL AERONAUTICS AND SPACE ADMINISTRATION (NASA)RCBEA GUIDE (2004) NASA Reliability Centered Building and Equipment Acceptance GuideU.S. GENERAL SERVICES ADMINISTRATION (GSA)FED-STD-595 (Rev C; Notice 1) Colors Used in Government Procurement1.2 SUBMITTALS*NOTE: Revie

14、w Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project.The Guide Specification technical editors have designated those items that require Government approval, due to their complexity or cri

15、ticality, with a “G.“ Generally, other submittal items can be reviewed by the Contractors Quality Control System. Only add a “G” to an item, if the submittal is sufficiently important or complex in context of SECTION 26 35 33.00 40 Page 3Provided by IHSNot for ResaleNo reproduction or networking per

16、mitted without license from IHS-,-,-the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Manageme

17、nt System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA pr

18、ojects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.for informat

19、ion only. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsConnection Diagrams; G; G, _Metal Enclosed Shunt Capacitor Equipm

20、ent; G; G, _Pole Line Capacitors; G; G, _Metal Enclosed Low-Voltage Capacitors; G; G, _Fabrication Drawings; G; G, _Capacitor Equipment; G; G, _Installation Drawings; G; G, _SD-03 Product DataMetal Enclosed Shunt Capacitor Equipment; G; G, _Pole Line Capacitors; G; G, _Metal Enclosed Low-Voltage Cap

21、acitors; G; G, _SD-06 Test ReportsHigh-Voltage Tests; G; G, _Insulation-Resistance Test; G; G, _Capacitance Value Test; G; G, _SECTION 26 35 33.00 40 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-SD-07 CertificatesCertificates for Capacitor E

22、quipment; G; G, _SD-08 Manufacturers InstructionsCapacitor Equipment ; G; G, _SD-10 Operation and Maintenance DataMetal-Enclosed Shunt Capacitor Equipment; G; G, _1.3 QUALITY ASSURANCESubmit certificates for capacitor equipment showing compliance with the referenced standards contained in this secti

23、on.1.4 PREDICTIVE TESTING AND INSPECTION TECHNOLOGY REQUIREMENTS*NOTE: The Predictive Testing and Inspection (PT&I) tests prescribed in Section 01 86 26.07 40 RELIABILITY CENTERED ACCEPTANCE FOR ELECTRICAL SYSTEMS are MANDATORY for all NASA _ assets and systems identified as Critical, Configured, or

24、 Mission Essential. If the system is non-critical, non-configured, and not mission essential, use sound engineering discretion to assess the value of adding these additional test and acceptance requirements. See Section 01 86 26.07 40 RELIABILITY CENTERED ACCEPTANCE FOR ELECTRICAL SYSTEMS for additi

25、onal information regarding cost feasibility of PT&I.*This section contains systems and/or equipment components regulated by NASAs Reliability Centered Building and Equipment Acceptance Program. This program requires the use of Predictive Testing and Inspection (PT&I) technologies in conformance with

26、 RCBEA GUIDE to ensure building equipment and systems installed by the Contractor have been installed properly and contain no identifiable defects that shorten the design life of a system and/or its components. Satisfactory completion of all acceptance requirements is required to obtain Government a

27、pproval and acceptance of the Contractors work.Perform PT&I tests and provide submittals as specified in Section 01 86 26.07 40 RELIABILITY CENTERED ACCEPTANCE FOR ELECTRICAL SYSTEMS.PART 2 PRODUCTS2.1 FABRICATIONSubmit connection diagrams indicating the relations and connections of the following it

28、ems by showing the general physical layout of all controls, the interconnection of one system (or portion of system) with another, and internal tubing, wiring, and other devices.Submit fabrication drawings for the following items consisting of fabrication and assembly details to be performed in the

29、factory.SECTION 26 35 33.00 40 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.2 COMPONENTSSubmit catalog data and equipment and performance data for the following items including life, test, system functional flows, safety features, and mech

30、anical automated details.2.2.1 Metal-Enclosed Shunt Capacitor EquipmentMetal-enclosed shunt capacitor equipment for connection to 2,400-, 6,900-, and 13,200/13,800-volt, three-phase, 60-hertz circuits consists of a complete assembly of capacitor units including buses, connectors, current-limiting fu

31、ses, ventilating fans, switching devices, and controls housed in a weatherproof NEMA 3R metal enclosure in accordance with IEEE 18. Provide control and protective devices in accordance with Section 26 05 70.00 40 HIGH VOLTAGE OVERCURRENT PROTECTIVE DEVICES and Section 26 05 71.00 40 LOW VOLTAGE OVER

32、CURRENT PROTECTIVE DEVICES.Provide capacitor units consisting of polypropylene film and aluminum foil sections with series-parallel connections and discharge resistors contained in hermetically sealed welded steel cases with mounting flanges, immersed in a nonflammable liquid dielectric impregnant.

33、Capacitor housings are bonded zinc-coated steel, resistant to corrosion, weather, and abrasion. Seal two insulating bushings with clamp tunnel connectors to the case of each unit and electrically connected to the capacitor section assembly. Ensure characteristics of capacitor bushings are in accorda

34、nce with IEEE 18. Provide discharge resistors that reduce the residual voltage of the capacitor unit to 50 volts or less within 5 minutes after disconnection from the source of supply. Each capacitor has an individual insulating fuse. Ensure capacitors operate satisfactorily at 135 percent of rated

35、kilovars (kvar), 110 percent of rated voltage, and at ambient temperatures between minus 40 degrees to plus 46 degrees C minus 40 degrees to plus 115 degrees F. Ensure voltage and kvar ratings for enclosed outdoor capacitor units rated at 60-hertz is in accordance with IEEE 18. Capacitors for harmon

36、ic filter application or systems with high harmonic content are EXTREME duty, 55 degree C 131 degree F temp rating, 125 percent continuous over-voltage capability, 15kA fault handling capability, 100KA transient current withstand capability, and meets IEEE 18.Place pad-mounted capacitor equipment in

37、 weatherproof, self-supporting, ventilated unit sheet metal compartments joined together to form a continuous structure, with hinged access doors, base and roof sections, roof seam covers, and end trims. Provide flanged access doors that close against rubber or similar weatherproof gasketing materia

38、l. Provide ventilated openings with filtered louvers and stainless steel screened vents. Equip doors with latches, stops, and door-locking mechanism. Ensure base section is unit construction and supports capacitor equipment 100 millimeter 4-inches 150 millimeter 6-inches above the concrete foundatio

39、n. Design the base for jacking and skidding. Provide lifting lugs for unloading and moving equipment.Construct sheet metal enclosures from cold-rolled carbon-steel sheets of commercial quality with stretcher-level flatness not less than 3.0 millimeter 11 gage, in accordance with ASTM A1008/A1008M. R

40、einforce each compartment with structural members and welded together. Grind welds to a smooth flat surface before painting. Provide capacitor equipment with a ground terminal for grounding the stationary structure and equipment.Provide capacitor compartments with racks for mounting individual capac

41、itor units in one, two, or three tiers, with not more than two rows of units per SECTION 26 35 33.00 40 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-tier. Enclosures having one row of units per tier are accessible from one side only.Phase an

42、d neutral buses for the connection and interconnection of capacitor units are bare rigid solid copper busbar of rectangular cross section, insulated from the enclosure. Contact surfaces of all main bus and cable tap connections are silver plated and bolted together to ensure maximum conductivity.Pha

43、se and neutral buses for the connection to underground cables and capacitor units are bare rigid silver plated solid copper busbar of rectangular cross-section insulated from the enclosure. Contact surfaces of all main bus connections are silver plated and bolted together to ensure maximum conductiv

44、ity.Ensure each capacitor unit is individually fused with current-limiting fuses that have an interrupting rating of 50,000 amperes and provide visual indication of fuse operation.Provide top of capacity compartments with thermostatically controlled fans for forced-air ventilation of capacitor units

45、 Provide each enclosure section with two cooling fans. Select fan motors that are for 115-volt, single-phase, 60-hertz current and individually fused or thermally protected. Ensure thermostats control the operation of fans within prescribed temperature limits.For power entrance compartments, include an i

展开阅读全文
相关资源
猜你喜欢
  • NACE SP0191-1991 Application of Internal Plastic Coatings for Oilfield Tubular Goods and Accessories (Item No 21048)《内部塑料涂料在油田管材和附件上的应用 项目编号21048》.pdf NACE SP0191-1991 Application of Internal Plastic Coatings for Oilfield Tubular Goods and Accessories (Item No 21048)《内部塑料涂料在油田管材和附件上的应用 项目编号21048》.pdf
  • NACE SP0192-2012 Monitoring Corrosion in Oil and Gas Production with Iron Counts (Item No 21053).pdf NACE SP0192-2012 Monitoring Corrosion in Oil and Gas Production with Iron Counts (Item No 21053).pdf
  • NACE SP0195-1995 Recommended Practice Corrosion Control of Sucker Rods by Chemical Treatment (Item No 21069)《吸油杆化学处理腐蚀控制的推荐实施规程 项目编号21069》.pdf NACE SP0195-1995 Recommended Practice Corrosion Control of Sucker Rods by Chemical Treatment (Item No 21069)《吸油杆化学处理腐蚀控制的推荐实施规程 项目编号21069》.pdf
  • NACE SP0196-2015 Galvanic Anode Cathodic Protection of Internal Submerged Surfaces of Steel Water Storage Tanks (Item No 21077).pdf NACE SP0196-2015 Galvanic Anode Cathodic Protection of Internal Submerged Surfaces of Steel Water Storage Tanks (Item No 21077).pdf
  • NACE SP0198-2010 Control of Corrosion Under Thermal Insulation and Fireproofing Materials-A Systems Approach (Item No 21084)《在热绝缘和防火材料系统方法下的腐蚀控制 项目编号21084》.pdf NACE SP0198-2010 Control of Corrosion Under Thermal Insulation and Fireproofing Materials-A Systems Approach (Item No 21084)《在热绝缘和防火材料系统方法下的腐蚀控制 项目编号21084》.pdf
  • NACE SP0199-2009 Installation of Stainless Chromium-Nickel Steel and Nickel-Alloy Roll-Bonded and Explosion-Bonded Clad Plate in Air Pollution Control Equipment (Item No 21087)《不锈钢.pdf NACE SP0199-2009 Installation of Stainless Chromium-Nickel Steel and Nickel-Alloy Roll-Bonded and Explosion-Bonded Clad Plate in Air Pollution Control Equipment (Item No 21087)《不锈钢.pdf
  • NACE SP0200-2014 Standard Practice Steel-Cased Pipeline Practices (Item No 21091).pdf NACE SP0200-2014 Standard Practice Steel-Cased Pipeline Practices (Item No 21091).pdf
  • NACE SP0205-2005 Design Fabrication and Inspection of Tanks for the Storage of Petroleum Refining Alkylation Unit Spent Sulfuric Acid at Ambient Temperatures (Item No 21107)《环境温度下石.pdf NACE SP0205-2005 Design Fabrication and Inspection of Tanks for the Storage of Petroleum Refining Alkylation Unit Spent Sulfuric Acid at Ambient Temperatures (Item No 21107)《环境温度下石.pdf
  • NACE SP0206-2006 Internal Corrosion Direct Assessment Methodology for Pipelines Carrying Normally Dry Natural Gas (DG-ICDA) (Item No 21112)《管道运输正常干燥天然气(DG-ICDA)的内部腐蚀直接评估方法 项目编号2111.pdf NACE SP0206-2006 Internal Corrosion Direct Assessment Methodology for Pipelines Carrying Normally Dry Natural Gas (DG-ICDA) (Item No 21112)《管道运输正常干燥天然气(DG-ICDA)的内部腐蚀直接评估方法 项目编号2111.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1