1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL 8Water Based Agent FireExtinguishersUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
2、REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL Standard for Safety for Water Based Agent Fire Extinguishers, UL 8Sixth Edition, Dated February 28, 2005Summary of TopicsThese revisions to ANSI/UL 8 include:Clarification of the Tamper Indicator and Locking Device TestNew Siphon Tube Attachme
3、nt Test - Polymeric MaterialsClarification of the Aging Test for Polymeric MaterialsSpecifications for Class K extinguishers to obtain a marine type designationText that has been changed in any manner or impacted by ULs electronic publishing system is markedwith a vertical line in the margin.The rev
4、ised requirements are substantially in accordance with Proposal(s) on this subject datedSeptember 10, 2010 and February 25, 2011.All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, ortransmitted in any form by any means, electronic, mechanical photocopyi
5、ng, recording, or otherwisewithout prior permission of UL.UL provides this Standard as is without warranty of any kind, either expressed or implied, including butnot limited to, the implied warranties of merchantability or fitness for any purpose.In no event will UL be liable for any special, incide
6、ntal, consequential, indirect or similar damages,including loss of profits, lost savings, loss of data, or any other damages arising out of the use of or theinability to use this Standard, even if UL or an authorized UL representative has been advised of thepossibility of such damage. In no event sh
7、all ULs liability for any damage ever exceed the price paid forthis Standard, regardless of the form of the claim.Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold ULharmless from and against any loss, expense, liability, damage, claim, or judgment (in
8、cluding reasonableattorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronicStandard on the purchasers computer system.The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, figures,and/or other elements of t
9、he Standard having future effective dates as indicated in the preface. The priortext for requirements that have been revised and that have a future effective date are located after theStandard, and are preceded by a SUPERSEDED REQUIREMENTS notice.JUNE 13, 2011 UL 8 tr1UL COPYRIGHTED MATERIAL NOT AUT
10、HORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 13, 2011 UL 8tr2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULULC StandardsCAN/ULC-S554Second EditionUnderwriters Laboratories Inc.ANSI/UL 8Si
11、xth EditionWater Based Agent Fire ExtinguishersFebruary 28, 2005(Title Page Reprinted: June 13, 2011)This harmonized standard has been jointly revised on June 13, 2011 to reflect updates to the standard.For this purpose, UL and ULC Standards have updated the Title Page and Preface dated June 13,2011
12、.ANSI/UL 8-2011UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCommitment for AmendmentsThis Standard is issued jointly by Underwriters Laboratories Inc. (UL) and ULC Standards.Amendments to this Standard will be made only after processing acc
13、ording to the Standards writingprocedures by UL and ULC Standards.UL and ULC Standards are separate and independent entities and each is solely responsible for itsoperations and business activities. The UL trade names and trademarks depicted in this document arethe sole property of Underwriters Labo
14、ratories Inc. The ULC trade names and trademarks depicted inthis document are the sole property of ULC Standards.ISSN 0317-526X Copyright 2010 Underwriters Laboratories of CanadaAll rights reserved.No part of this publication may be reproduced in any form, in an electronic retrieval system orotherwi
15、se, without the prior permission of the publisher.In Canada, written comments are to be sent to the ULC Standards Department, 200 440 LaurierAvenue West, Ottawa, Ontario K1R 7X6. Proposals should be submitted on a Standards RevisionRequest Form available from ULC Standards.Copyright 2011 Underwriter
16、s Laboratories Inc.ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standardshould be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regardingthose Standards shall remain the sole and exclusive property of UL.This ANSI/UL
17、 Standard for Safety consists of the Sixth Edition including revisions through June 13,2011. The most recent designation of ANSI/UL 8 as an American National Standard (ANSI) occurredon June 13, 2011. ANSI approval for a standard does not include the Cover Page, Transmittal Pages,Title Page (front an
18、d back), or the Preface.Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time.Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative StandardsDevelopment System (CSDS) at http:/.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
19、 REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSPreface .6INTRODUCTION1 Scope .72 Units of Measurement .73 Reference Publications 74 Components 75 Glossary .7CONSTRUCTION6 General 97 Cylinders .108 Joints .109 Caps, Valves, Closures, and Pressure Relief 1110 Gaskets and “O” rings .111
20、1 Gas Cartridges, Cylinders, and Regulators .1112 Pressure Gauges and Indicators 1213 Puncturing Mechanisms .1314 Tamper Indicators and Locking Devices .1315 Hose 1416 Couplings 1417 Nozzles and Discharge Valves .1418 Siphon Tubes 1519 Strainers .1520 Handles and Mounting Devices .1521 Hose Retainer
21、s Wheeled Extinguishers 1622 Running Gear Wheeled Extinguishers .1623 Expellant Gases 1624 Antioverfill tubes 1625 Extinguishing Agent .16PERFORMANCE26 General 16A27 Fire Tests 16A28 Tamper Indicator and Locking Device TestSection 28 deleted effective June 13, 2011 16A28A Tamper Indicator and Lockin
22、g Device Test 16A28A.1 Tamper Indicator 16A28A.2 Locking Device and Tamper Indicator 16B29 Handle and Mounting Device Test .16B30 Operation Test .1731 Discharge Duration Test .1732 Rate of Flow Test .1933 Discharge Range Test .1934 Intermittent Discharge Test 1935 Operating Temperature Limits Test .
23、19JUNE 13, 2011 CAN/ULC-S554 ANSI/UL 8 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL36 Temperature Cycling Test .2037 30-Day Elevated Temperature Test .2038 High-Temperature Exposure Test .2039 Abnormal Operation Test 2040 Hydrostatic Pres
24、sure Test .2040.1 Cylinders 2040.2 Discharge valves, caps, and closures .2240.3 Hose assemblies .2240.4 Gas cartridges .2240.5 Test method .2341 Vibration Test 2341.1 General .2341.2 Mounting of test sample .2441.3 Test orientation 2441.4 Variable frequency test .2441.5 Endurance test .2442 Roadabil
25、ity and Rough Usage Tests 2442.1 Roadability 2442.2 Rough usage 2542.3 Rough usage operation .2543 Siphon Pull Test Polymeric MaterialsSection 43 deleted effective June 13, 2011 .2643A Siphon Tube Attachment Test - Polymeric Materials .2643A.1 General 2643A.2 Press-fit type siphon tube assemblies 26
26、A43A.3 Threaded siphon tube assemblies .26A44 Aging Tests Polymeric Materials .26A44.1 General 26A44.2 Exposure to extinguishing agent test 26B44.3 Light and water test 2745 Elastomeric Parts Test 2746 Salt Spray Corrosion Test .2947 10-Day Moist Ammonia Air Stress Cracking Test .2948 Agent Exposure
27、 Test 3048.1 Disposable (nonrechargeable) fire extinguishers .3048.2 Rechargeable (refillable) fire extinguishers 3049 Servicing Tests .3150 One-Year Time Leakage Test 3151 Calibration Test Gauges and Indicators 3152 Burst Strength Test Gauges and Indicators 3253 Water Resistance Test Gauges and Ind
28、icators .3254 Leakage Test Gauges and Indicators 3255 Cycling Test Pressure Indicators 3356 Vibration Test Pressure Gauges and Indicators .3357 Overpressure Test Gauges .3358 Impulse Test Gauges 3359 Pressure Gauge Relief Test 3360 Nameplate Exposure Tests 3461 Nameplate Adhesion Test .3462 Nameplat
29、e Abrasion Test 3463 Antioverfill Tube Test 35JUNE 13, 2011CAN/ULC-S554 ANSI/UL 84UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPACKAGING64 General 35MANUFACTURING AND PRODUCTION TESTS65 General 3666 Hydrostatic Pressure Test .3666.1 Cylinde
30、rs 3666.2 Non-DOT or Non-TDGR gas cartridges .3666.3 Hoses and couplings .3767 Two-Year Leakage Test .37MARKING68 General 3769 Operating Instructions 38A70 Use Code Symbols .3971 Recharging instructions 4072 Identification of Contents 4073 Inspection Instructions .41RECORD TAGS AND MANUALS74 Record
31、Tag 4175 Manuals .41TABLESFIGURESANNEX AANNEX BJUNE 13, 2011 CAN/ULC-S554 ANSI/UL 8 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPrefaceThis is the harmonized UL and ULC Standard for Water Based Agent Fire Extinguishers. It is the Seconded
32、ition of CAN/ULC-S554, and the Sixth edition of ANSI/UL 8.This harmonized Standard was prepared by Underwriters Laboratories Inc., ULC Standards and theExtinguisher Technical Harmonization Committee.This Standard was formally approved by the ULC Committee on Portable Fire Extinguishers.Level of harm
33、onizationThis standard used an ISO format, but is not based on, nor shall it be considered equivalent to, an ISOstandard. This standard is published as an identical standard.An identical standard is a standard that is the same in technical content except for conflicts in Codes andGovernmental Regula
34、tions. Presentation shall be word for word except for editorial changes.InterpretationsThe interpretation by the SDO of an identical or equivalent standard shall be based on the literal text todetermine compliance with the standard in accordance with the procedural rules of the SDO. If more thanone
35、interpretation of the literal text has been identified, a revision shall be proposed as soon as possibleto each of the SDOs to more accurately reflect the intent.UL Effective DateAs of August 14, 2007 all products Listed or Recognized by UL must comply with the requirements in thisStandard, with the
36、 exception of Clauses 1.2, 27.1, 31.1 and 31.3 which become effective February 14,2011.A UL effective date is one established by Underwriters Laboratories Inc. and is not part of the ANSIapproved Standard.JULY 27, 2010.6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION W
37、ITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover the construction and performance, exclusive of performance during firetests, of portable water based agent fire extinguishers. These fire extinguishers are intended to be utilizedin accordance with the Standard for Portable Fir
38、e Extinguishers, NFPA 10 and with the National Fire Codeof Canada.1.2 The requirements for performance during fire testing of water based agent fire extinguishers arespecified in the Binational Standard for Rating and Fire Testing of Fire Extinguishers, ANSI/UL 711CAN/ULC-S508.1.3 As used in these r
39、equirements, the term extinguisher refers to all extinguishers or any part thereofcovered by these requirements, unless specifically noted otherwise.2 Units of Measurement2.1 The metric unit shall be designated as the official unit for purposes of this standard. Where values ofmeasurement are specif
40、ied in both SI and English units, either unit is used. In cases of dispute, the metricunit shall be used.3 Reference Publications3.1 See Annex A for a list of publications referenced in this standard. Any undated reference to a codeor standard appearing in the requirements of this standard shall be
41、interpreted as referring to the latestedition of that code or standard. When the latest edition of a standard is not the applicable standard, theappropriate edition is indicated accordingly in Annex A.4 Components4.1 Except as indicated in 4.2, a component of a product covered by this standard shall
42、 comply with therequirements for that component. A component shall comply with both the Underwriters Laboratories Inc.and the Underwriters Laboratories of Canada standards for the component.4.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteri
43、stic not required in the application of the component in theproduct covered by this standard, orb) Is superseded by a requirement in this standard.4.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.4.4 Specific components are incomplete in const
44、ruction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.5 Glossary5.1 For the purpose of this standard, the follow
45、ing definitions apply.FEBRUARY 28, 2005 CAN/ULC-S554 ANSI/UL 8 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.2 AGENT CONCENTRATE A concentrated agent that is intended to be diluted with water to form amixture used to extinguish fires.5.3
46、AGENT SOLUTION A mixture of the agent concentrate with water.5.4 CARTRIDGE OPERATED EXTINGUISHER A fire extinguisher in which the extinguishing agentand expellant gas are in separate cylinders.5.5 DISPOSABLE (NONRECHARGEABLE) FIRE EXTINGUISHER A fire extinguisher not capable ofnor intended to underg
47、o complete maintenance including internal inspection of cylinder, replacement ofparts and seals and hydrostatic testing.5.6 EFFECTIVE DISCHARGE The time of discharge of extinguishing agent from the extinguisheruntil gas point.5.7 EXPELLANT GAS A compressed or pressurized gas used to propel the extin
48、guishing agent froma single cylinder.5.8 EXTINGUISHER, DRY CHARGE TYPE An extinguisher in which the foam concentrate or additiveconcentrate is not mixed with the water until the extinguisher is activated. The water is stored in theextinguisher cylinder, and the concentrate is stored in a separate pa
49、rt of the extinguisher.5.9 EXTINGUISHER, LIQUID CHARGE TYPE An extinguisher in which a mixture of the foamconcentrate or additive concentrate and water is stored in the extinguisher cylinder.5.10 GALVANIC COMPATIBILITY Fire extinguisher cylinder and component parts which are notsusceptible to 10-day stress corrosion cracking, or corrosion from combination of dissimilar materials.5.11 GAS POINT The point in time when the discharge changes from extinguishing agent to a gasand extinguishing agen