1、 2012 Standard for Air-Conditioning, Heating and Refrigerating Equipment Nameplate Voltages AHRI Standard 110 Price $5.00 (M) $10.00 (NM) Copyright 2012, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY

2、RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with nationally recognized safety requirements appropriate for products covered by this standard. AHRI, as a manufacturers trade association, uses its best efforts to develop s

3、tandards employing state-of-the-art and accepted industry practices. However, AHRI does not certify or guarantee safety of any products, components or systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted under its standards will be non

4、-hazardous or free from risk. Note: This standard supersedes AHRI Standard 110-2002. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions. 1 Section 4. Voltage Rating Requirements . 2 Section 5. Equipment Performance Requirements 6 Section 6. Conformance Co

5、nditions 6 TABLES Table 1. Standard Nominal System Voltages for 60Hz Systems in the U.S.A. 3 Table 2. Standard Nominal System Voltages for 50Hz and 60Hz Systems (For non U.S.A. systems only) 5 Table 3. AC Three Phase Systems with Nominal Voltage Above 1kV and not Exceeding 35kV at 50Hz and 60Hz (For

6、 non U.S.A. systems only) 6 APPENDICES Appendix A. References - Normative 7 Appendix B. References - Informative. 7 AHRI STANDARD 110-2012 1 AIR-CONDITIONING, HEATING AND REFRIGERATING EQUIPMENT NAMEPLATE VOLTAGES Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for air-

7、conditioning, heating and refrigerating equipment: definitions; voltage rating requirements; equipment performance requirements; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors, and user

8、s. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. 1.2 The provisions herein are recommendations intended for implementation only through reference by other authoritative documents. Section 2. Scope 2.1 Scope. This standard applies to 50 Hz and 60

9、 Hz electrical voltage ratings and operating limits as applied to air-conditioning, heating and refrigerating equipment, heat pumps, and electric furnaces as well as components. 2.1.1 Exclusions. Voltages less than 100V AC are not included in this standard. Section 3. Definitions All terms in this d

10、ocument shall follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.1.1 Shall. Where “

11、shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.1.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.2 Voltages. 3.2.1 Equipment Nameplate Voltage Rat

12、ing. The nominal Utilization Voltage marked on the equipment nameplate by the manufacturer (Tables 1 and 2). 3.2.2 Low Voltage. The Nominal System Voltage with the range between 100V and 1kV AC according to ANSI C84.1. 3.2.3 Medium Voltage. The Nominal System Voltage with the range between 1kV and 3

13、5kV AC according to IEEE 1585. Note: For the purposes of this standard, 1kV is included under Medium Voltage. 3.2.4 Nominal System Voltage. A nominal value assigned to the electric power supply system for the purpose of conveniently designating its voltage class. 3.2.5 Service Voltage. The voltage a

14、t the point where the electric systems of the supplier and the user are connected. AHRI STANDARD 110-2012 2 3.2.6 Utilization Voltage. The voltage at the line terminals of the utilization equipment. 3.3 Y. The transformer coil configuration. Section 4. Voltage Rating Requirements 4.1 Standard System

15、 Voltage Relationships. Tables 1 and 2 present the basic relationships between standard Nominal System Voltages and Utilization Voltages for air-conditioning, heating and refrigeration equipment and components. (Data derived from ANSI C84.1). 4.2 Application of Voltage Ranges. (See ANSI C84.1). 4.2.

16、1 Range A-Service Voltage. Electric supply systems are designed and operated so that most Service Voltages are within the limits specified for this range. The occurrence of Service Voltages outside of these limits should be infrequent and should be handled as a special occurrence. 4.2.2 Range A-Util

17、ization Voltage. User systems are to be designed and thus must operate acceptably between the minimum and maximum Utilization Voltage Range A. Utilization equipment shall be designed and rated to give acceptable performance throughout this range, per the applicable AHRI Standard. 4.2.3 Range B-Servi

18、ce and Utilization Voltages. This range includes voltages above and below Range A limits that necessarily result from practical design and operating conditions on supply or user systems or both. Although such conditions are a part of practical operations, they are typically limited in extent, freque

19、ncy and duration. When they occur, corrective measures are typically undertaken within a reasonable time to improve voltages to meet Range A requirements. Insofar as practical, utilization equipment shall be designed to give acceptable performance in the extremes of this range of Utilization Voltage

20、, although not necessarily equal performance as in Range A. 4.2.3.1 Exception. For 208V systems only, motor driven equipment shall be designed to start and operate satisfactorily under rated load conditions at the extremes of Range B, but not necessarily under maximum load conditions. For rated and

21、maximum load conditions, see the industry standards for the product concerned. It must be recognized that, because of conditions beyond the control of the supplier or user, or both, there will be infrequent and limited periods when sustained voltages outside of Range B limits will occur. Utilization

22、 equipment may not operate satisfactorily under these conditions, and protective devices may operate to protect the equipment. When voltages occur outside the limits of Range B, prompt corrective action is recommended. The urgency for such action will depend upon many factors, such as the location a

23、nd nature of load or circuits involved, and the magnitude and duration of the deviation beyond Range B limits. AHRI STANDARD 110-2012 3 Table 1. Standard Nominal System Voltages for 60 Hz Systems in the U.S.A. Voltage Class Nominal System Voltage Nameplate Voltage Marking Voltage Range A2Voltage Ran

24、ge B2Maximum Minimum Maximum Minimum Utilization and Service Voltage Service Voltage Utilization Voltage Utilization and Service Voltage Service Voltage Utilization Voltage Low Voltage 1,2,4Single Phase 120 115 126 114 108 127 110 104 208 or 240 208/230 (200/230) 252 197 187 254 191 180 208 208 (200

25、) 228 197 187 228 191 180 240 230 252 228 216 254 220 208 277 265 291 263 249 293 254 240 Three Phase5208 or 240 208/230 (200/230) 252 197 187 254 191 180 208 208 (200) 228 197 187 228 191 180 240 230 252 228 216 254 220 208 480 460 504 456 432 508 440 416 600 575 630 570 540 635 550 520 Medium Volt

26、age5Nominal System Voltage does not apply for the medium voltage range. 2340 4050/2340 4050 4680 6730 8110/4680 11700/6760 12160/7020 12870/7430 13460/7770 13460 20260/11700 22290/12870 22430 2520 4370Y/2520 4370 5040 7240 8730Y/5040 12600Y/7270 1309Y/7560 13860Y/8000 14490Y/8370 14490 21820Y/12600

27、2340 4050Y/2340 4050 4680 6730 8110Y/4680 11700Y/6760 12160Y/7020 12870Y/7430 13460Y/7770 13460 20260Y/11700 22290Y/12870 22430 216033740Y/216033740343203621031242032540 4400Y/2540 4400 5080 7260 8800Y/5080 12700Y/7330 13200Y/7620 13970Y/8070 14520Y/8380 14520 22000Y/12700 2280 3950Y/2280 3950 4560

28、6560 7900Y/4560 11400Y/6580 11850Y/6840 12504Y/7240 13110Y/7570 13110 19740Y/11400 21720Y/12540 21850 23690Y/13680 208033600Y/20803360034160359403118803AHRI STANDARD 110-2012 4 Notes for Table 1: 1) Minimum Utilization Voltages for 120 thru 600 volt combination lighting and power circuits servicing

29、cord - plug connected equipment are: Nominal System Voltage, V Range A, V Range B, V 120 110 106 208 191 184 240 220 212 277 254 245 480 440 424 600 550 530 2) It is recognized that there are in existence, power systems whose operating characteristics deviate from the voltage range limits of this ta

30、ble. It shall not be construed that nameplate voltage rated equipment, suitable for application to such systems and deviating from the values appearing in this table, may not be produced. 3) Utilization equipment does not generally operate directly at these voltages. For equipment supplied through t

31、ransformers, refer to limits for nominal system voltage of transformer output. 4) Motors are usually guaranteed to operate satisfactorily and to deliver their full power at the rated frequency and at a voltage 10% above or below their rating, or at the rated voltage. Some U.S. single-phase HVAC comp

32、onents that are dual-voltage rated (e.g., 208/230-1-60) may carry a minus 5% voltage allowance from the lower voltage rating of 208 volts. Equipment having more than one marked rated voltage, which is permitted to be connected to these voltages without individual adjustment, should have the voltages

33、 separated by a hyphen. Example: 208-230V; The equipment may be operated at these utilization voltages or at voltages between these values without individually adjusting for the difference between them. Equipment having more than one marked rated voltage, which requires rewiring or other adjustments

34、 made by the installer to the equipment to permit connection to these voltages, should have the voltages separated by an oblique stroke. Example: 208/230V; The equipment may be operated at these utilization voltages only if the installer makes the proper wiring or adjustment to the equipment for eac

35、h voltage as specified by the manufacturer. 5) For Medium Voltages. A) Three-phase three-wire systems are systems in which only the three-phase conductors are carried out from the source of the connection of loads. The source may be derived from any type of three-phase transformer connection, ground

36、ed or ungrounded. B) Three-phase four-wire systems are systems in which a grounded neutral conductor is also carried out from the source for connection of loads. Four-wire systems in Table 1 are designated by the phase-to-phase voltage, followed by the letter Y, which defines the transformer coil co

37、nfiguration, a slant line, and the phase-to-neutral voltage. AHRI STANDARD 110-2012 5 4.3 Nominal System Voltages for 50Hz and 60Hz Non U.S.A. Systems Only. For the standard Nominal System Voltages for 50Hz and 60Hz units for non U.S.A. systems only, see Table 2. Table 2. Standard Nominal System Vol

38、tages for 50Hz and 60Hz Systems (For non U.S.A. systems only) Systems Nominal Frequency (Hz) Voltage Highest Supply or Utilization Voltage Nominal Voltage Lowest Supply Voltage Lowest Utilization Voltage Nameplate Voltage Marking5Three-phase Four-wire or Three-wire Systems 50 253 230 207 198 230 253

39、/440 230/4001207/360 198/344 400/230 440/759 400/6902360/621 344/593 690/400 1100 1000 900 860 1000 60 132/229 120/208 108/187 103/179 208/120 264 2403216 206 240 253/440 230/4001207/360 198/344 400/230 305/528 277/480 249/432 238/413 480/277 528 480 432 413 480 382/660 347/600 312/540 298/516 600/3

40、47 660 600 540 516 600 Single-phase Three-wire Systems 60 132/264 120/2404108/216 103/206 240/120 Notes: There are many power systems throughout the world and this table lists the most common. 1) The value of 230/400 V is the result of the evolution of 220/380V and 240/415V systems which has been co

41、mpleted in Europe and many other countries. However, 220/380V and 240/415V systems still exist. 2) The value of 400/690 V is the result of the evolution of 380/660V systems which has been completed in Europe and many other countries. However, 380/660V systems still exist. 3) The value of 200V or 220

42、V is also used in some countries. 4) The values of 100/200V are also used in some countries on 50 Hz or 60 Hz systems. 5) The first number is phase to neutral voltage and the second number is phase to phase voltage. AHRI STANDARD 110-2012 6 4.4 AC Three Phase Systems with Nominal Voltage Above 1kV a

43、nd Not Exceeding 35kV at 50Hz and 60Hz (For non-U.S.A. systems only). For AC three phase systems with nominal voltage above 1kV and not exceeding 35kV at 50Hz and 60Hz in the U.S.A. only, see Table 3, which was derived from IEC Standard 60038. Table 3. AC Three Phase Systems With Nominal Voltage Abo

44、ve 1kV and not Exceeding 35kV at 50Hz and 60Hz (For non-U.S.A. systems only)1,2Highest Voltage Equipment (kV) Nominal System Voltage (kV) Nameplate Voltage Marking (kV) 3.633.33333.3 7.236.63636.6 12 11 10 11 17.5 - 15 15 24 22 20 22 36433430433 40.54- 35435 Notes: 1) It is recommended that in any o

45、ne country, the ratio between two adjacent nominal voltages should be not less than two. 2) In a normal system, the highest voltage and the lowest voltage do not differ by more than approximately 10% from the nominal voltage of the system. 3) These values should not be used for new public distributi

46、on systems. 4) The unification of these values is under consideration. Section 5. Equipment Performance Requirements 5.1 Equipment Standard Rating Requirements. Equipment standard rating tests, in accordance with equipment rating standards, shall be conducted at the Equipment Nameplate Voltage Ratin

47、g. For all dual nameplate voltage equipment covered by this standard, any Standard Rating tests shall be performed at both voltages or at the lower of the two voltages if only a single Standard Rating is to be published. Section 6. Conformance Conditions 6.1 Conformance. While conformance with this

48、standard is voluntary, conformance shall not be claimed or implied for products or equipment within the standards Purpose (Section 1) and Scope (Section 2) unless such product claims meet all of the requirements of the standard and all of the testing and rating requirements are measured and reported

49、 in complete compliance with the standard. Any product that has not met all the requirements of the standard shall not reference, state, or acknowledge the standard in any written, oral, or electronic communication. AHRI STANDARD 110-2012 7 APPENDIX A. REFERENCES - NORMATIVE A1 Listed here are all standards, handbooks and other publications essential to the formation and implementation of the standards. All references in this appendix are considered as part of the standard. A1.1 ANSI C84.1-2006, Electrical Power Systems and Equipment - Voltage