ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf

上传人:appealoxygen216 文档编号:437017 上传时间:2018-11-14 格式:PDF 页数:30 大小:429.19KB
下载 相关 举报
ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf_第1页
第1页 / 共30页
ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf_第2页
第2页 / 共30页
ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf_第3页
第3页 / 共30页
ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf_第4页
第4页 / 共30页
ANSI ISA TR12.21.01-2004 Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations.pdf_第5页
第5页 / 共30页
亲,该文档总共30页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、 TECHNICAL REPORT ANSI/ISATR12.21.012004 (R2013) Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations ANSI Technical Report prepared by ISA Approved 1 September 2013 ANSI/ISA-TR12.21.01-2004 (R2013) Use of Fiber Optic Systems in Class I Hazardous (Classified) Locations ISBN: 978-0-

2、876640-30-2 Copyright 2013 by the International Society of Automation (ISA). All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means (electronic mechanical, p

3、hotocopying, recording, or otherwise), without the prior written permission of the Publisher. ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, North Carolina 27709 3 ANSI/ISA-TR12.21.01-2004 (R2013) Copyright 2013 ISA. All rights reserved. Preface This preface, as well as all footnotes

4、and annexes, is included for information purposes and is not part of ANSI/ISA-TR12.21.01-2004 (R2013). This document has been prepared as part of the service of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subj

5、ect to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549 -8411; Fax (919) 549-8288; E-mail

6、: standardsisa.org. The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefi

7、ts to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommend

8、ed practices, and technical reports to the greatest extent possible. IEEE/ASTM SI 10, American National Standard for Metric Practice, and future revisions, will be the reference guide for definitions, symbols, abbreviations, and conversion factors. It is the policy of ISA to encourage and welcome th

9、e participation of all concerned individuals and interests in the development of ISA standards, recommended practices, an d technical reports. Participation in the ISA standards-making process by an individual in no way constitutes endorsement by the employer of that individual, of ISA, or of any of

10、 the standards, recommended practices, and technical reports that ISA develops. CAUTION ISA DOES NOT TAKE ANY POSITION WITH RESPECT TO THE EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS ASSERTED IN CONNECTION WITH THIS DOCUMENT, AND ISA DISCLAIMS LIABILITY FOR THE INFRINGEMENT OF ANY PATENT RESULTING FR

11、OM THE USE OF THIS DOCUMENT. USERS ARE ADVISED THAT DETERMINATION OF THE VALIDITY OF ANY PATENT RIGHTS, AND THE RISK OF INFRINGEMENT OF SUCH RIGHTS, IS ENTIRELY THEIR OWN RESPONSIBILITY. PURSUANT TO ISAS PATENT POLICY, ONE OR MORE PATENT HOLDERS OR PATENT APPLICANTS MAY HAVE DISCLOSED PATENTS THAT C

12、OULD BE INFRINGED BY USE OF THIS DOCUMENT AND EXECUTED A LETTER OF ASSURANCE COMMITTING TO THE GRANTING OF A LICENSE ON A WORLDWIDE, NON-DISCRIMINATORY BASIS, WITH A FAIR AND REASONABLE ROYALTY RATE AND FAIR AND REASONABLE TERMS AND CONDITIONS. FOR MORE INFORMATION ON SUCH DISCLOSURES AND LETTERS OF

13、 ASSURANCE, CONTACT ISA OR VISIT WWW.ISA.ORG/STANDARDSPATENTS. OTHER PATENTS OR PATENT CLAIMS MAY EXIST FOR WHICH A DISCLOSURE OR LETTER OF ASSURANCE HAS NOT BEEN RECEIVED. ISA IS NOT RESPONSIBLE FOR IDENTIFYING PATENTS OR PATENT APPLICATIONS FOR WHICH A LICENSE MAY BE REQUIRED, FOR CONDUCTING INQUI

14、RIES INTO THE LEGAL VALIDITY OR SCOPE OF PATENTS, OR DETERMINING WHETHER ANY LICENSING TERMS OR CONDITIONS PROVIDED IN CONNECTION WITH SUBMISSION OF A LETTER OF ASSURANCE, IF ANY, OR IN ANY LICENSING AGREEMENTS ARE REASONABLE OR NON-DISCRIMINATORY. ISA REQUESTS THAT ANYONE REVIEWING THIS DOCUMENT WH

15、O IS AWARE OF ANY PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE DOCUMENT NOTIFY THE ISA STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER. ANSI/ISA-TR12.21.01-2004 (R2013) 4 Copyright 2013 ISA. All rights reserved. ADDITIONALLY, THE USE OF THIS DOCUMENT MAY INVOLVE HAZARDOUS MATERIALS,

16、OPERATIONS OR EQUIPMENT. THE DOCUMENT CANNOT ANTICIPATE ALL POSSIBLE APPLICATIONS OR ADDRESS ALL POSSIBLE SAFETY ISSUES ASSOCIATED WITH USE IN HAZARDOUS CONDITIONS. THE USER OF THIS DOCUMENT MUST EXERCISE SOUND PROFESSIONAL JUDGMENT CONCERNING ITS USE AND APPLICABILITY UNDER THE USERS PARTICULAR CIR

17、CUMSTANCES. THE USER MUST ALSO CONSIDER THE APPLICABILITY OF ANY GOVERNMENTAL REGULATORY LIMITATIONS AND ESTABLISHED SAFETY AND HEALTH PRACTICES BEFORE IMPLEMENTING THIS DOCUMENT. THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE IMPACTED BY ELECTRONIC SECURITY ISSUES. THE COMMITTE

18、E HAS NOT YET ADDRESSED THE POTENTIAL ISSUES IN THIS VERSION. The following people served as members of ISA Subcommittee ISA12.21 which prepared this technical report: NAME COMPANY P. Kelly, ISA12.21 Chair UL LLC M. Coppler, Managing Director Det Norske Veritas Certification Inc. D. Baker P b) photo

19、chemical ignition due to photodissociation of oxygen molecules by radiation in the ultraviolet region; and c) direct laser induced breakdown of the gas at the focus of a strong beam, producing plasma and a shock wave, both of which acting as ignition sources. These three mechanisms require either re

20、latively high peak powers or ultraviolet radiation n ot commonly found in current practice. Although one should be aware of these other mechanisms, they are not addressed in this technical report. Explosive targets or targets that contain their own oxidizer are also outside the scope of this technic

21、al report. 5.4 Optical beam spatial and temporal characteristics greatly influence ignitability of explosive gas atmospheres. Table 1 summarizes the limiting beam strength parameters for igniting explosive gas atmospheres as a function of beam spatial and temporal characteristics. For a short durati

22、on optical pulse with a small beam diameter, the energy required to cause ignition reaches a minimum. For such a beam, limiting the pulse energy to levels below the minimum optical ignition energy will prevent ignitions, regardless of the peak power, peak power density, or energy density. Similar re

23、lationships apply to the other combinations of beam diameter and duration. As long as the optical beam does not exceed the limiting beam strength parameter for its particular temporal and spatial domain, the other beam strength parameters need not be considered. Table 1 Limiting beam strength parame

24、ters for igniting explosive gas atmospheres based on beam spatial and temporal characteristics. Short duration (pulsewidth 1 cm) Energy density Power density 19 ANSI/ISA-TR12.21.01-2004 (R2013) Copyright 2013 ISA. All rights reserved. 5.5 Optical ignition powers generally reach a minimum for beam di

25、ameters of about 50 m or less. Ignition of a carbon disulfide-air mixture has been reported using 24 mW optical power, which is significantly less than igniting powers observed to date for other explosive gas atmospheres. These explosive gas atmospheres generally ignite at power levels above 50 mW.

26、Explosive gas atmospheres that fall within Material Group D or Material Group IIA, and have an AIT above 200 C (T Codes T1-T3), generally ignite at power levels above 200 mW. 5.6 For large beam diameters incident on inert target layers, optical ignition power d ensities generally reach a minimum for

27、 beam diameters of about 1 cm or larger. Explosive gas atmospheres with no combustible solid targets present generally ignite at power densities above 10 mW/mm2. In one study of large beam areas ( 400 mm 2) incident on combustible coal dust layers, it was shown that combustible solids may pose a smo

28、ldering ignition hazard at relatively low beam power densities compared to power densities needed to ignite explosive gas atmospheres by laserheated inert targets. 5.7 Optical beams of intermediate dimensions can exceed the minimum optical ignition criteria without causing ignition. In the range of

29、large core diameter optical fibers (100 to 1000 m), studies indicate ignition threshold powers are above the absolute minimum opt ical igniting powers for explosive gas atmospheres. Threshold igniting powers observed to date for some explosive gas atmospheres were approximately proportional to beam

30、diameter over this range of beam diameters. Ignitions may be prevented for relatively powerful beams by controlling the beam diameter, such as with large core diameter ( 100 m) optical fiber. 5.8 Optical ignition energies for explosive gas atmospheres generally reach a minimum for pulse durations of

31、 about 100 s or less and beam diameters of about 100 m or less. The minimum optical ignition energies observed to date were about twice the corresponding electrical spark ignition energies. 5.9 Optical pulses of intermediate duration can exceed the minimum optical ignition criteria without causing i

32、gnition. In one study, optical pulse durations in the millisecond range required over 10 times as much energy to ignite explosive gas atmospheres as a 70 s optical pulse. Ignitions may be prevented even for relatively high-energy optical pulses by extending the duration and thus decreasing the peak

33、power of the pulse. 5.10 Periodic optical pulses (pulse trains) in explosive gas atmospheres are safe if the individual pulses and the average power over the period of transmission meet the safe criteria for pulses and continuous wave, respectively. 6 Protection concepts 6.1 Three protection concept

34、s are suggested to prevent ignitions by fiber optic terminal devices and cables in Class I hazardous (classified) locations. a) inherently safe optical radiation; b) protected optical fiber cables; and c) optical radiation interlock with optical fiber breakage. This list is not all-inclusive, other

35、protection concepts should be considered where appropriate such as ensuring an adequate target or an explosive gas atmosphere is not present. The classification of an area as a Division or Zone implies the frequency and duration that an explosive gas atmosphere may be present. Divisions are defined

36、in Article 500 of the NEC and Zones are defined in Article 505 of the NEC. ANSI/ISA-TR12.21.01-2004 (R2013) 20 Copyright 2013 ISA. All rights reserved. Protection concepts should be developed through an appropriate process hazard analysis (PHA), where potential failure modes leading to, and effects

37、of, ignition events are analyzed (AIChE 1992). PHAs include (but are not limited to) a) electrical area classification (source of hazard method); b) hazards and operability studies (HAZOPS); c) failure modes and effects analysis (FMEA) (IEC 60812); d) fault tree analysis; e) event tree analysis; and

38、 f) layers of protection analysis (LOPA). 6.2 Inherently safe optical radiation Visible, near infrared, or mid infrared radiation that is incapable of producing sufficient thermal energy under normal or specified fault conditions to ignite a specific hazardous atmospheric mixture is inherently safe.

39、 6.2.1 The inherently safe concept applies to unconfined radiation and does not require maintaining a target-free environment. Secondly, the concept is an energy limitation approach to safety, and studies indicate ignition of explosive gas atmospheres by an optically heated target requires the least

40、 amount of energy, power, or power density of the identified ignition mechanisms in the visible through mid infrared spectrum. 6.2.2 Research to date has concluded the values of visible, near infrared, and mid infrared beam strength, as called out in this clause, are safe. The safe values incorporat

41、e a modest safety factor on observed ignition values obtained under severe test conditions. a) an optical pulse energy equal to or less than the minimum spark ignition energy of the explosive gas atmosphere. A higher energy level is safe under the following conditions: 1. For an optical pulse durati

42、on greater than 1 ms and less than 1 s, an optical pulse energy equal to or less than 10 times the minimum spark ignition energy of the explosive gas atmosphere 2. For an optical pulse duration greater than 1 s, a peak power or peak power density equal to or less than the applicable value listed in

43、Table 2 b) optical powers or optical power densities equal to or less than the values listed in Table 2 c) an optical pulse train is safe if the individual pulses meet the safe energy criteria of 6.2.2 a) and either the average power or average power density meets the applicable value listed in Tabl

44、e 2 Table 2 Safe optical powers or safe optical power densities for Class I locations by Material Group and Temperature Class (T Code) Material Group A B C D D IIA IIA IIB IIC T Code T1-T6 T1-T6 T1-T6 T1-T3 T4-T6 T1-T3 T4-T6 T1-T6 T1-T6 Power (mW) 35 35 35 150 35 150 35 35 35 a Power Density b (mW/m

45、m2) 5 5 5 20 c 5 20 c 5 5 5 a A 15 mW power applies to carbon disulfide atmospheres. b Lower values for power density may apply for irradiated areas greater than 400 mm 2. c For irradiated areas greater than 30 mm2 and less than 400 mm2 where combustible solids may intercept the beam, the 5 mW/mm2 p

46、ower density limit applies. 21 ANSI/ISA-TR12.21.01-2004 (R2013) Copyright 2013 ISA. All rights reserved. 6.2.3 Ignition tests to demonstrate inherent safety may be advantageous under certain cases such as a) beams of intermediate dimensions or durations that may exceed the minimum optical ignition c

47、riteria but are still incapable of causing ignition; b) beams with complex time waveforms such that pulse energies, average power, or average power density are not easily resolved; or c) specific atmospheres, targets, or other test conditions that reflect specific applications that are demonstrably

48、less severe than test conditions studied to date. 6.2.4 Fiber optic terminal devices incorporating the inherently safe concept should provide over -power fault protection to prevent excessive beam strengths in Class I locations. Optical sources such as laser diodes or light-emitting diodes will fail

49、 if over-heated under over-power fault conditions. The thermal failure characteristic of certain optical sources may provide the necessary over-power fault protection. Electrical circuits such as intrinsically safe barriers placed between the optical source and the electrical power source can provide over-power fault protection. Fiber optic terminal devices may incorporate shutters or other automatic beam strength reduction devices (interlocks) when fault conditions are detected, also provi ding over-power fault protection. All forms of over-power

展开阅读全文
相关资源
  • ANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdfANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdf
  • ANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdfANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdf
  • ANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdfANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdf
  • ANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdfANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdf
  • ANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdfANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdf
  • ANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdfANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdf
  • ANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdfANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdf
  • ANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdfANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdf
  • ANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdfANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdf
  • ANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdfANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ANSI

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1