ASHRAE 170 ERTA-2014 Ventilation of Health Care Facilities.pdf

上传人:sumcourage256 文档编号:454199 上传时间:2018-11-23 格式:PDF 页数:2 大小:32.60KB
下载 相关 举报
ASHRAE 170 ERTA-2014 Ventilation of Health Care Facilities.pdf_第1页
第1页 / 共2页
ASHRAE 170 ERTA-2014 Ventilation of Health Care Facilities.pdf_第2页
第2页 / 共2页
亲,该文档总共2页,全部预览完了,如果喜欢就下载吧!
资源描述

1、2014 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE/ASHE STANDARD 170-2013 Ventilation of Health Care Facilities July 16, 2014 The corrections listed in this errata sheet apply to ANSI/ASHRAE/ASHE Standard 170-2013. The first printing is identified on the outside back cover as “Product co

2、de: 86515 12/13”. The shaded item has been added since the previously published errata sheet dated February 27, 2014 was distributed. Page Erratum Inside Front Cover ASHRAE Standing Standard Project Committee 170. In the footnote to the project committee membership, delete the duplicate “her” in the

3、 second sentence. 6 Table 6.7.2 Supply Air Outlets. Change Note a in Table 6.7.2 as shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.) Notes: a. Refer to the 2009 2013 ASHRAE HandbookFundamentals, Chapter 20 (see ASHRAE 20092013b in Informative Appendix B

4、), for definitions related to outlet classification and performance. 9 Table 7.1 Design Parameters. Add the attached entries under Diagnostic and Treatment in Table 7.1. These new entries were added by Addendum l to Standard 170-2008 currently published on the ASHRAE website at https:/www.ashrae.org

5、/standards-research-technology/standards-addenda but were inadvertently missed in the 2013 edition. (Note: Additions are shown in underline.)10 Table 7.1 Design Parameters. Revise Treatment room under Diagnostic and Treatment in Table 7.1 to delete Note “(x)” as shown below. Note “(x)” does not appl

6、y and was included in error. (Note: Deletions are shown in strikethrough.) Function of Space DIAGNOSTIC AND TREATMENTTreatment room (x) 16 Informative Appendix B Informative References and Bibliography. Update Informative Appendix B as shown below. (Note: Additions are shown in underline and deletio

7、ns are shown in strikethrough.) ASHRAE. 2009. ASHRAE Handbook Fundamentals, Chapter 20, “Space Air Diffusion.” Atlanta: ASHRAE. ASHRAE. 2013a. ASHRAE HandbookFundamentals, Chapter 21, “Duct Design.” Atlanta: ASHRAE. ASHRAE. 2013b. ASHRAE HandbookFundamentals, Chapter 20, “Space Air Diffusion.” Atlan

8、ta: ASHRAE. ASHRAE. 2013c. HVAC Design Manual for Hospitals and Clinics, 2nd Edition. Atlanta: ASHRAE. 2014 ASHRAE. All rights reserved. TABLE 7.1 Design Parameters Function of Space Pressure Relationship to Adjacent Areas (n) Minimum Outdoor ach Minimum Total ach All Room Air Exhausted Directly to

9、Outdoors (j) Air Recirculated by means of Room Units (a) Design Relative Humidity (k), % Design Temperature (l), F/C DIAGNOSTIC AND TREATMENT Dialysis treatment area NR 2 6 NR NR NR 72-78/22-26 Dialyzer reprocessing room Negative NR 10 Yes No NR NR Nuclear medicine hot lab Negative NR 6 Yes No NR 70-75/21-24 Nuclear medicine treatment room Negative 2 Yes NR NR 70-75/21-24

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1