ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf

上传人:wealthynice100 文档编号:465257 上传时间:2018-11-27 格式:PDF 页数:5 大小:103.14KB
下载 相关 举报
ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf_第1页
第1页 / 共5页
ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf_第2页
第2页 / 共5页
ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf_第3页
第3页 / 共5页
ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf_第4页
第4页 / 共5页
ASTM C1601-2008 Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: C 1601 08Standard Test Method forField Determination of Water Penetration of Masonry WallSurfaces1This standard is issued under the fixed designation C 1601; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of

2、last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This test method covers the field determination of waterpenetration of a masonry wall surface under specific water fl

3、owrate and air pressure conditions. This test is intended for use onany masonry wall surface that can be properly instrumentedand tested within the requirements of this standard.1.2 This test method is not identical to and the results arenot directly comparable with the laboratory standard TestMetho

4、d E 514.1.3 Surface penetration, as determined by this test method,is defined as the amount of water passing through the wallsurface exposed to testing per unit time per unit area. Thisproperty is not directly comparable to overall water penetrationand leakage, which are typically defined as the amo

5、unt of watertravelling completely through a masonry system.1.4 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.5 This standard may invo

6、lve hazardous materials, opera-tions, or equipment. This standard does not purport to addressall of the safety problems associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory l

7、imitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 1232 Terminology of MasonryE 514 Test Method for Water Penetration and LeakageThrough Masonry3. Terminology3.1 For definitions of terms used in this test method, refer toTerminology C 1232.4. Significance and Use4.1 This non-destru

8、ctive test method contains proceduresand equipment requirements to quantitatively determine thesurface penetration of water at a single location on a masonrywall. It is not designed to determine the overall water penetra-tion and leakage of a masonry system.4.2 Excessive water penetration of masonry

9、 may degrademasonry wall performance with respect to thermal conductiv-ity, durability, efflorescence, staining, corrosion of embeddedmetal items, and water leakage.4.3 This test may be used to evaluate masonry walls in-situor for field mock-up testing. Common applications of thismethod have been co

10、mparison of water penetration rates ofwalls before and after repairs, and testing the efficacy ofcoatings. Alternative procedures are also provided to simulatethe effect of local climatology on water penetration of masonrywall surfaces.4.4 The outer surface of all masonry walls will experiencewater

11、penetration when subjected to wind-driven rain. Theresistance to water penetration is dependent on materials,workmanship, design, and maintenance. Some wall typesaccommodate large volumes of water penetration, withoutdeleterious effects, through the presence of properly designedand installed drainag

12、e systems including flashing and weepholes. Use of this standard without consideration of the overallwall system may lead to incorrect conclusions regardingperformance.4.5 It is the intent of this standard that a sheet of water bedeveloped and maintained on the wall surface during testing. Insome ca

13、ses, due to the surface texture of the masonry, theapplication of a coating, or other factors, a sheet of water willnot consistently form. In those cases, results of this test methodwill likely be inaccurate.4.6 This test method is similar to but distinct from thelaboratory Test Method E 514. This f

14、ield test method isdesigned to test in-situ walls. E 514 laboratory test method isdesigned to test laboratory wall specimens. This test methoddetermines water penetration of the masonry at its surface. TestMethod E 514 measures the water that has penetrated into andthrough the masonry specimen and i

15、s collected. Direct com-parison of results from this test method and Test Method E 514are inappropriate.1This test method is under the jurisdiction of ASTM Committee C15 onManufactured Masonry Units and is the direct responsibility of SubcommitteeC15.04 on Research.Current edition approved Nov. 1, 2

16、008. Published November 2008. Originallyapproved in 2004. Last previous edition approved in 2006 as C 1601 06.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the st

17、andards Document Summary page onthe ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5. Apparatus5.1 Test ChamberUse a test chamber similar to thatshown in

18、 Fig. 1. Provide a rectangular opening with aminimum area of 12 ft2(1.08 m2) with a minimum dimensionof 24 in. (0.6 m) for each side of the opening (Note 1). Seal thecontact surface between the frame of the chamber and the testarea to prevent loss of water and maintain air pressure. Coverthe face of

19、 the chamber with a tough, transparent materialcapable of withstanding the test pressure (Note 2). Provide a34-in. (19-mm) diameter, corrosion-resistant, water spray pipewith a single line of 0.04-in. (1.0-mm) diameter holes spaced 1in. (25 mm) apart, starting within 1 in. (25 mm) of each end(Note 3

20、). Position the water spray pipe within the chamber sothat the water impinges the wall perpendicular to the wall notmore than 1.5 in. (40 mm) below the interior top of the testchamber.NOTE 1A size of 36 in. (0.9 m) wide and 48 in. (1.2 m) high iscommon.NOTE 2Transparent plastic sheets316 to14 inch (

21、5 to 6 mm) thickhave been shown to perform well. Plexiglast and Lexant are twoproducts that have been used.NOTE 3Clean-outs at the end of the spray bar to facilitate cleaning thespray bar are common.5.2 Fixtures and Appurtenances to ChamberFixtures andappurtenances to the chamber include an air line

22、 with manom-eter or pressure gauge able to read air pressure to within 0.50lb/ft2(24 Pa), a water line with valves, a flow meter in thewater supply line able to read flow within 0.02 gpm (4.5 L/h),and a water drain pipe at the bottom of the chamber. The wateris stored in a calibrated reservoir with

23、a minimum volume of 3gal. (13 L), with graduations to allow readings within 0.015 gal(0.055 L) (Note 4). Pump water from the reservoir to the spraybar. Return water which drains from the bottom of the chamberdirectly to the reservoir.NOTE 4Use of a cylindrical reservoir having dimensions of approxi-

24、mately 4 to 8 inches (100 to 200 mm) in diameter by 5 ft. (1.5 m) or talleris common.5.3 Other equipment includes devices for handling andmounting the chamber and measuring time, water quantities,and ambient temperature.6. Hazards6.1 The use of this test method requires careful design ofboth air cha

25、mber and support of the wall system to avoidpossible injury due to equipment or masonry failure. Assurethat the chamber and its attachment to the wall are adequate forthe applied pressures during testing.6.2 Water penetration resulting from this test can causesaturation of adjacent materials and lea

26、kage into occupiedspaces of the buildings. Take into consideration the effects ofpotential water infiltration and leakage.7. Procedure7.1 Mounting ChamberAttach the test chamber with me-chanical fasteners using sufficient pressure to form an air- andwater-resistant seal (Note 5).NOTE 5Use of a gaske

27、t or sealant at the contact surface is common.FIG. 1 Water Surface Penetration Test SystemC16010827.2 SealingIf needed, apply a perimeter sealant betweenthe chamber and wall surface to ensure that leakage does notoccur at the interface. Allow the sealant to cure sufficiently toensure adequate bond a

28、nd water resistance.7.3 Application of Air Pressure and Water FlowAdjustthe water flow rate to 3.4 gal/ft2/h (138 L/m2/h) times the areaof the chamber opening. Simultaneously, increase the airpressure within the chamber to 10 lb/ft2(500 Pa). Check forleakage from the perimeter of the chamber. If lea

29、kage occurs,stop the test, reseal, and re-start the procedure.7.3.1 During the test, note the flow pattern of the water overthe masonry surface. If a complete sheet of water is observed,report it as “sheet flow”. If the water runs down the surface inpatterned or random rivuleted streams or in any ot

30、her mannerthat leaves portions of the wall surface un-wetted, report it as“incomplete sheet flow” and document the pattern of flow withsketches drawn to scale. Monitor the water flow pattern duringthe testing and report any changes.NOTE 6It is the intent of this standard that a sheet of water bedeve

31、loped and maintained on the wall surface during testing. In somecases, due to the surface texture of the masonry, the application of acoating, or other factors, a sheet of water will not consistently form. Inthose cases, results of this test method will likely be inaccurate.7.4 PreconditioningMainta

32、in the water flow rate andpressure specified in 7.3 for 30 minutes prior to starting thetest. During the last five minutes of this period, adjust the waterflow rate and air pressure to the specified test parameters.7.5 Standard Test ConditionsPerform this test using awater flow rate of 3.4 gal/ft2/h

33、 (138 L/m2/h) and an air pressureof 10 lb/ft2(500 Pa). The test duration shall be not less thanfour hours after the preconditioning period.7.6 Alternate Test ConditionsSpecial condition testingspecified to model different water flow rates or chamber airpressures are acceptable. Procedures for specif

34、ying the testingparameters using local climatological data are provided in 7.6.1and 7.6.2.7.6.1 Testing Parameter Determination Using LocalWeather DataThis procedure utilizes local weather data(wind speeds and rainfall intensity) to produce testing param-eters (water flow rate, air pressure, and dur

35、ation of test) forwater chamber testing of vertical surfaces. The conversion isaccomplished using a numerical approach. The weather datacan be obtained from various sources, including the NationalClimatological Data Center. This procedure does not addressthe methods used to select weather data nor d

36、oes it address thesignificance of using those data in chamber testing.7.6.2 Water Flow Rates and Air Pressures7.6.2.1 Determine the angle of rainfall, u, for each timeperiod using wind speed, rainfall intensity, and interpolatingusing values in Table 1.Atime period is the length of time overwhich th

37、e water and air pressures are held constant. A test mayconsist of one or more time periods.7.6.2.2 Calculate water flow rate for each period using:Q05 0.0104 I tanu A (1)where:Q0= water flow rate (gpm)I = rainfall intensity (in/h)u = rainfall angle, measured from vertical (degrees)A = area of test c

38、hamber opening (ft2)The flow rate, Q0, shall not be less than that required toproduce streams of water from the spray bar which impact thesurface of the test area.7.6.2.3 Determine the air pressure for each period:P05 0.00256V2(2)where:P0= air pressure (lb/ft2)V = wind speed (mph)7.6.3 Duration of T

39、est7.6.3.1 Real-Time Tests: Use the time duration of theweather data to be simulated, water flow rates and air pressuresfor each period within the duration as determined in 7.6.2.2 and7.6.2.3.7.6.3.2 Compressed Time Tests: Use shorter time periodsthan actual weather data and modified water flow rate

40、s and airpressures based on the shortened periods. Determine the flowrate for each period using:Q 5 Q0D0D(3)where:Q = water flow rate (gpm)Q0= the water flow rate from Eq 1 (gpm)D = the duration to be used for the test (h)D0= the duration of weather data to be simulated (h)TABLE 1 Angle of Rainfall,

41、 u, in Degrees Measured from Vertical, for Selected Wind Speeds and Rainfall IntensitiesWindSpeed, V(mph)Rainfall Intensity, / (in/h)0.01 0.04 0.16 0.60 1.60 4.00 10.000 0.0 0.0 0.0 0.0 0.0 0.0 0.01.5 41.3 19.2 9.9 7.2 5.5 4.2 3.93 60.8 34.6 19.3 14.2 10.8 8.4 7.85 71.7 48.8 30.1 22.9 17.6 13.9 12.9

42、7.5 77.7 59.7 40.9 32.2 25.4 20.3 18.910 80.9 66.6 49.2 40.1 32.3 26.3 24.515 83.8 73.6 59.7 51.2 43.2 36.3 34.220 85.4 77.7 66.6 59.1 51.5 44.4 42.225 86.4 80.2 71.0 64.6 57.6 50.9 48.635 87.4 82.9 76.0 71.0 65.3 59.5 57.550 88.1 85.0 80.0 76.4 72.1 67.5 65.875 88.8 86.6 83.3 80.7 77.7 74.4 73.2C16

43、01083Determine air pressure for each period using:P 5 P0 SD0DD2(4)where:P = air pressure (lb/ft2)P0= the air pressure from Eq 2 (lb/ft2)7.6.3.2.1 The test pressure, P, shall not exceed that capacityof the chamber and its anchorage to the wall.7.6.3.3 For tests involving multiple compressed time peri

44、-ods, maintain the same number of periods for the compressedtest as for the weather data to be simulated.8. Record of ObservationsMake observations and measurements during the pre-conditioning and each test period as follows:8.1 Record the initial water flow rate, air pressure within thechamber, and

45、 water level within the reservoir at the beginningof the test after the specified preconditioning period.8.2 Report the water flow pattern as described in 7.3.1.8.3 Record the water level in the reservoir, air pressure, andwater flow rate at the beginning of, at the end of, and at5-minute (maximum)

46、intervals throughout each test period.8.4 Record the amount and time at which water is added toreplenish the reservoir. Simultaneously, record the new waterlevel with each addition of water to the reservoir.8.5 Note and photograph visible lateral and vertical migra-tion of dampness outside the chamb

47、er. Note leakage fromadjacent areas. Note signs of interior moisture or leakagewhere accessible. Note any interruptions in testing includinglength of time and reason.9. Calculations9.1 Calculate water loss, to the nearest 0.025 gal (0.1 L),from the reservoir at each recorded time interval.9.2 Plot t

48、he loss of water versus time.9.3 Calculate surface penetration in gal/ft2/hr (L/m2/hr) foreach period of testing by performing a linear regression fitusing all data for that period versus time and dividing the rateof water loss by the area of the chamber opening.10. ReportReport the following:10.1 T

49、he project name and address of the building;10.2 Date, time, and temperature during the test;10.3 Dates and results of previous tests of same area, ifapplicable;10.4 Name(s) and address(es) of individual(s) performingthe test;10.5 Description of the construction of the area testedincluding surface coatings, masonry type, wall assembly struc-tural system, condition of the masonry surface (see Note 7),chamber location including elevation, floor level and positionrelative to wall ends or openings in the structure, and repairsperformed prior to each test;NOTE 7Example

展开阅读全文
相关资源
猜你喜欢
  • ASTM A729 A729M-2009 Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理合金钢轴的标准规范》.pdf ASTM A729 A729M-2009 Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理合金钢轴的标准规范》.pdf
  • ASTM A729 A729M-2009(2014) Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《货物运输和电气铁路用热处理合金钢轴的标准实施规程》.pdf ASTM A729 A729M-2009(2014) Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《货物运输和电气铁路用热处理合金钢轴的标准实施规程》.pdf
  • ASTM A729 A729M-2009e1 Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《用于公共交通及电气化铁路的热处理合金钢轴的标准规格》.pdf ASTM A729 A729M-2009e1 Standard Specification for Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《用于公共交通及电气化铁路的热处理合金钢轴的标准规格》.pdf
  • ASTM A729 A729M-2015 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理碳素合金钢轴的标准规格》.pdf ASTM A729 A729M-2015 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理碳素合金钢轴的标准规格》.pdf
  • ASTM A729 A729M-2015e1 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《货物运输和电气铁路用热处理碳和合金钢轴的标准实施规程》.pdf ASTM A729 A729M-2015e1 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《货物运输和电气铁路用热处理碳和合金钢轴的标准实施规程》.pdf
  • ASTM A729 A729M-2017 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理碳素合金钢轴的标准规格》.pdf ASTM A729 A729M-2017 Standard Specification for Carbon and Alloy Steel Axles Heat-Treated for Mass Transit and Electric Railway Service《公共运输和电气铁路运输用热处理碳素合金钢轴的标准规格》.pdf
  • ASTM A732 A732M-2005 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures.pdf ASTM A732 A732M-2005 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures.pdf
  • ASTM A732 A732M-2009 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures《升.pdf ASTM A732 A732M-2009 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures《升.pdf
  • ASTM A732 A732M-2014 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures《升.pdf ASTM A732 A732M-2014 Standard Specification for Castings Investment Carbon and Low Alloy Steel for General Application and Cobalt Alloy for High Strength at Elevated Temperatures《升.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ASTM

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1