1、Designation: F1825 03 (Reapproved 2013)Standard Specification forClampstick Type Live Line Tools1This standard is issued under the fixed designation F1825; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision.
2、A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification applies to the Clampstick type liveline tools to ensure manufacturing processes and materials arecompatible and no
3、 deterioration of components occur duringthe assembly process.1.2 This specification establishes the technical characteris-tics for clampsticks.1.3 This specification applies to clampsticks both hollowand foam-filled.1.4 The values stated in SI units are to be regarded as thestandard. The values giv
4、en in parentheses are for informationonly.1.5 The following safety hazards caveat pertains only to thetest portions of this specification: This standard does notpurport to address all of the safety concerns, if any, associatedwith its use. It is the responsibility of the user of this standardto esta
5、blish appropriate safety and health practices anddetermine the applicable of regulatory limitations prior to use.1.6 The use, maintenance, and in-service testing of thisequipment is beyond the scope of this specification.2. Referenced Documents2.1 ASTM Standards:2F711 Specification for Fiberglass-Re
6、inforced Plastic (FRP)Rod and Tube Used in Live Line ToolsF819 Terminology Relating to Electrical Protective Equip-ment for Workers3. Terminology3.1 Definitions Terminology used in this specification isin accordance with Terminology F819.3.2 Definitions of Terms Specific to This Standard:3.2.1 clamp
7、stick, na live line tool having a hand controlwith latching stops at the butt end mechanically connected byan insulating rod to a hook that retracts into a slotted ferrule atthe head end.3.2.1.1 DiscussionClampsticks are used by qualifiedworkers for high-voltage application of hot line clamps, groun
8、dclamps, operation of energized apparatus and the like. Clamp-sticks are sometimes referred to as “shotgun sticks” or “grip allsticks”. Clampsticks are designed to provide insulation to theuser while performing the above operations.3.2.2 design test, na test made on a sample treated asrepresentative
9、 of an industrial product. This test will notgenerally be repeated in quantity production.3.2.3 electrical test, na test to ensure that a product meetsminimum electrical requirements of a standard.3.2.4 FRP insulating tubes and rods, n fiberglass rein-forced plastic (FRP) products manufactured so th
10、at the tubesand rods produced will meet the electrical and mechanicalrequirements of this specification.3.2.5 hand control, nlower control of the clampstick andconnected to hook by an FRP rod.3.2.6 head ferrule, na nonmetallic structural part withslots to accept clamp bases of standard size and allo
11、w theclosing motion of the hook.3.2.7 mechanical test, na test to ensure that a productmeets minimum mechanical requirements of a standard.3.2.8 rear stop, na device or devices that stop the rear-ward motion of the hand control when the tool has reached itsfully retracted position.3.2.9 retract lock
12、, na locking means that allows the handcontrol to be positioned and releaseably latched between thesafety stop and rear stop and prevents movement toward thesafety stop.3.2.10 safety stop, na releasable latch that automaticallyand positively engages at partial retract to fully capture adevice.3.2.11
13、 visual inspection, na visual check made to detectdefects that impede the performance of product(s).1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee F18.35 on Tools gripall stick; shotgun
14、 stickASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such right
15、s, are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional s
16、tandardsand should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM C
17、ommittee on Standards, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/COPYRIGHT/).F1825 03 (2013)4