1、BRITISH STANDARDBS EN 54-17:2005Fire detection and fire alarm systems Part 17: Short-circuit isolatorsThe European Standard EN 54-17:2005 has the status of a British StandardICS 13.220.20g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g
2、55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58Licensed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIBS EN 54-17:2005This British Standard was published under the authority of the Standards Policy and Strategy Committee on 25 Jan
3、uary 2006 BSI 25 January 2006ISBN 0 580 47596 4National forewordThis British Standard is the official English language version of EN 54-17:2005. The UK participation in its preparation was entrusted by Technical Committee FSH/12, Fire detection and alarm systems, to Subcommittee FSH/12/3, Control an
4、d indicating equipment, which has the responsibility to: aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep UK interests informed; monitor related international and European developm
5、ents and promulgate them in the UK.A list of organizations represented on this subcommittee can be obtained on request to its secretary.Cross-referencesThe British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under th
6、e section entitled “International Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standards Online.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct applicati
7、on.Compliance with a British Standard does not of itself confer immunity from legal obligations.Summary of pagesThis document comprises a front cover, an inside front cover, the EN title page, pages 2 to 41 and a back cover.The BSI copyright notice displayed in this document indicates when the docum
8、ent was last issued.Amendments issued since publicationAmd. No. Date CommentsLicensed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 54-17December 2005ICS 13.220.20English VersionFire detection and fire alarm systems - Pa
9、rt 17: Short-circuitisolatorsSystmes de dtection et dalarme incendie - Partie 17:Isolateurs de court-circuitBrandmeldeanlagen - Teil 17: KurzschlussisolatorenThis European Standard was approved by CEN on 26 October 2005.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
10、stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard
11、exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bo
12、dies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR
13、STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2005 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 54-17:2005: ELicensed Copy: Wang Bin, na, Tue Apr
14、11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 2 Contents page Foreword. 3 Introduction 5 1 Scope 6 2 Normative references . 6 3 Terms and definitions. 6 4 Requirements 7 5 Tests. 10 Annex A (informative) Examples for the functional test procedure 23 Annex B (informative) Apparatu
15、s for impact test 30 Annex ZA (informative) Relationship of this European Standard with the Construction Products Directive 89/106/EEC 32 Bibliography . 41 Licensed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 3 Foreword This European Standard (EN 54-
16、17:2005) has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm systems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by June 2
17、006, and conflicting national standards shall be withdrawn at the latest by December 2008. This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationshi
18、p with EU Directive(s), see informative Annex ZA, which is an integral part of this European Standard. This European Standard has been prepared in co-operation with the CEA (Comit Europen des Assurances) and with EURALARM (Association of European Manufacturers of Fire and Intruder Alarm Systems). In
19、formation on the relationship between this European Standard and other standards of the EN 54 series is given in Annex A of EN 54-1:1996. EN 54 “Fire detection and fire alarm systems” consists of the following parts: Part 1: Introduction Part 2: Control and indicating equipment Part 3: Fire alarm de
20、vices Sounders Part 4: Power supply equipment Part 5: Heat detectors - Point detectors Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionization Part 10: Flame detectors - Point detectors Part 11: Manual call points Part 12: Smoke detectors - Line detectors usi
21、ng an optical light beam Part 13: Compatibility assessment of system components Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance Part 15: Point type multi-sensor fire detectors Part 16: Voice alarm control and indicating equipment Part 17: Short-circuit isol
22、ators Licensed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 4 Part 18: Input/output devices Part 20: Aspirating smoke detectors Part 21: Alarm transmission and fault warning routing equipment Part 22: Line-type heat detectors Part 23: Fire alarm devic
23、es - Visual alarms Part 24: Components of voice alarm systems Loudspeakers Part 25: Components using radio links and system requirements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: A
24、ustria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. Licensed Copy: Wang Bin, na,
25、Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 5 Introduction The purpose of short-circuit isolators is to limit the consequences of low parallel resistance faults between the lines of a transmission path of a fire detection and fire alarm system. This is normally achieved
26、 by connecting the transmission path in a loop configuration, separating sections of the loop with short-circuit isolators and introducing a means of detecting the presence of a fault, if its consequences (e.g. reduction in the line voltage) jeopardises the correct operation of components on the tra
27、nsmission path. The faulty section of the loop can then be switched out, between a pair of short-circuit isolators, allowing the rest of the loop to continue to function correctly. It is recognised that it is not possible for this component standard to specify all of the requirements for the functio
28、n of a short-circuit isolator in a system. The requirements for the functioning of a short-circuit isolator are dependent on the system operation, the other components associated with the transmission path (e.g. the control and indicating equipment and detectors.) and the transmission path parameter
29、s (e.g. line impedance and line loads) and will have to be verified in a system test. However, this component standard includes: a requirement that the manufacturer shall give all of the specifications, for the short-circuit isolator, needed by system designers to use the device correctly, in accord
30、ance with the system requirements, NOTE The system designer should ensure that only those short-circuit isolators having the necessary performance are chosen to meet the specific requirements of a given system design. tests to verify that the short-circuit isolator functions in accordance with these
31、 manufacturers specifications, and tests to verify the stability of the short-circuit isolator with respect to environmental and electromagnetic compatibility (EMC) conditions. Due to the many different concepts that can be used for the operation of short-circuit isolators, it is not possible to def
32、ine a precise functional test procedure applicable to all types. Instead, this European Standard requires that a functional test procedure is developed to verify the manufacturers specification and lists the most important points that have to be verified. To assist in developing such test procedures
33、, some example procedures are given in an informative annex. In view of the above, it is important that, in addition to meeting the requirements of this European Standard, short-circuit isolators are shown to operate correctly within the types of systems with which they are intended to be used. Lice
34、nsed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 6 1 Scope This European Standard specifies requirements, test methods and performance criteria for short-circuit isolators, for use in fire detection and fire alarm systems for buildings (see EN 54-1).
35、 Means of isolation or protection incorporated within control and indicating equipment (item B in Figure 1 of EN 54-1:1996) are not covered by this European Standard. 2 Normative references The following referenced documents are indispensable for the application of this European Standard. For dated
36、references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 54-1:1996, Fire detection and fire alarm systems Part 1: Introduction EN 50130-4:1995, Alarm systems Part 4: Electromagnetic compatibility - Produc
37、t family standard: Immunity requirements for components of fire, intruder and social alarm systems EN 60068-1, Environmental testing Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum 1988 + A1:1992) EN 60068-2-1, Environmental testing Part 2: Tests Tests A: Cold (IEC 60068-2-1:1990) EN 60
38、068-2-2, Basic environmental testing procedures Part 2: Tests Tests B: Dry heat (IEC 60068-2-2:1974 + IEC 60068-2-2A:1976) EN 60068-2-6, Environmental testing Part 2: Tests Test Fc: Vibration (sinusoidal) (IEC 60068-2-6:1995 + Corrigendum 1995) EN 60068-2-27, Basic environmental testing procedures P
39、art 2: Tests Test Ea and guidance: Shock (IEC 60068-2-27:1987) EN 60068-2-30, Environmental testing Part 2: Tests Test Db and guidance: Damp heat, cyclic (12 + 12 hour cycle) (IEC 60068-2-30:1980 + A1:1985) EN 60068-2-42, Environmental testing Part 2-42: Tests Test Kc: Sulphur dioxide test for conta
40、cts and connections (IEC 60068-2-42:2003) EN 60068-2-78, Environmental testing Part 2-78: Tests Test Cab: Damp heat, steady state (IEC 60068-2-78:2001) ISO 209-1:1989, Wrought aluminium and aluminium alloys Chemical composition and forms of products Part 1: Chemical composition 3 Terms and definitio
41、ns For the purposes of this European Standard, the terms and definitions given in EN 54-1:1996 and the following apply. 3.1 short-circuit isolator device, which may be connected into a transmission path of a fire detection and fire alarm system, to limit the consequences of low parallel resistance f
42、aults between the lines of this transmission path Licensed Copy: Wang Bin, na, Tue Apr 11 02:11:29 BST 2006, Uncontrolled Copy, (c) BSIEN 54-17:2005 (E) 7 NOTE A short circuit isolating device may be a physically separate device or it may be incorporated into another device apart from the control an
43、d indicating equipment (e.g. integrated into a smoke detector or detector base). 3.2 closed condition condition of the short-circuit isolator which allows the normal signals and supply currents to pass through the short-circuit isolator (i.e. the correct condition for the short-circuit isolator when
44、 there is no short circuit) 3.3 open condition condition of the short-circuit isolator which prevents the passage of short circuit currents through the short-circuit isolator. (i.e. the correct condition for the short-circuit isolator when it is protecting part of a circuit from the effects of a sho
45、rt circuit) 4 Requirements 4.1 Compliance In order to comply with this European Standard the short-circuit isolator shall meet the requirements of this clause, which shall be verified by visual inspection or engineering assessment, shall be tested as described in Clause 5 and shall meet the requirem
46、ents of the tests. However, for short circuit isolating devices which are integrated into other devices already covered by an existing European Standard (EN), the environmental conditioning shall be performed in accordance with that EN. 4.2 Integral status indication If the short-circuit isolator in
47、corporates an integral visual indication of its status, then this indication shall not be red. 4.3 Connection of ancillary devices Where the short-circuit isolator provides for connections to ancillary devices (e.g. remote indicators), open- or short-circuit failures of these connections shall not p
48、revent the correct operation of the short-circuit isolator. 4.4 Monitoring of detachable short-circuit isolators If a short circuit isolating device is detachable (i.e. it is attached to a mounting base), then a means shall be provided for a remote monitoring system (e.g. the control and indicating
49、equipment) to detect the removal of the device from the base, in order to give a fault signal. 4.5 Manufacturers adjustments It shall not be possible to change the manufacturers settings except by special means (e.g. the use of a special code or tool) or by breaking or removing a seal. 4.6 On-site adjustments If there is provision for on-site adjustment of the short-circuit isolator, then for each setting the short-circuit isolator shall comply with the requirements of this European Standard. Access to the means of adjustm