1、Alarm systems Combinedand integrated systems General requirementsDD CLC/TS 50398:2009raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI British StandardsNational forewordThis Draft for Development is the UK implementation of CLC/TS 50398:2009.It supe
2、rsedes DD CLC/TS 50398:2002 which is withdrawn.This publication is not to be regarded as a British Standard.It is being issued in the Draft for Development series of publications and is ofa provisional nature. It should be applied on this provisional basis, so thatinformation and experience of its p
3、ractical application can be obtained.Comments arising from the use of this Draft for Development are requestedso that UK experience can be reported to the European organization respon-sible for its conversion to a European standard. A review of this publicationwill be initiated not later than three
4、years after its publication by theEuropean organization so that a decision can be taken on its status.Notification of the start of the review period will be made in an announce-ment in the appropriate issue of Update Standards.According to the replies received by the end of the review period, the re
5、spon-sible BSI Committee will decide whether to support the conversion into aEuropean Standard, to extend the life of the Technical Specification or towithdraw it. Comments should be sent to the Secretary of the responsible BSITechnical Committee at British Standards House, 389 Chiswick High Road,Lo
6、ndon W4 4AL.The UK participation in its preparation was entrusted to Technical CommitteeGW/1, Electronic security systems.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acon
7、tract. Users are responsible for its correct application. BSI 2009ISBN 978 0 580 57203 6ICS 13.320BRITISH STANDARDDD CLC/TS 50398:2009Amendments issued since publicationDate Text affectedThis Draft for Development was published under the authority of the Standards Policy and Strategy Committee on 31
8、 March 2009TECHNICAL SPECIFICATION CLC/TS 50398 SPCIFICATION TECHNIQUE TECHNISCHE SPEZIFIKATION February 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: avenue M
9、arnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. CLC/TS 50398:2009 E ICS 13.320 Supersedes CLC/TS 50398:2002English version Alarm systems - Combined and integrated alarm systems - General requirements
10、Systmes dalarme - Systmes dalarme combins et intgrs - Rgles gnrales Alarmanlagen - Kombinierte und integrierte Alarmanlagen - Allgemeine Anforderungen This Technical Specification was approved by CENELEC on 2008-11-14. CENELEC members are required to announce the existence of this TS in the same way
11、 as for an EN and to make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting national standards in force. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, F
12、inland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. DD CLC/TS 50398:2009CLC/TS 50398:2009 - 2 - Foreword This Technical Spec
13、ification was prepared by the Technical Committee CENELEC TC 79, Alarm systems. The text of the draft was circulated for voting in accordance with the CEN/CENELEC Internal Regulations, Part 2, Subclause 11.3.3.3 and was approved by CENELEC as CLC/TS 50398 on 2008-11-14. This Technical Specification
14、supersedes CLC/TS 50398:2002. The following date was fixed: latest date by which the existence of the CLC/TS has to be announced at national level (doa) 2009-05-14 _ DD CLC/TS 50398:2009- 3 - CLC/TS 50398:2009 Contents Introduction . 4 1 Scope . 5 2 Normative references . 5 3 Definitions . 5 4 Gener
15、al description and fundamental principles 8 4.1 General . 8 4.2 Standards . 8 4.3 Configuration types of integrated alarm systems . 8 5 System requirements and compatibility assessment .13 5.1 General design .13 5.2 Common facility for control .14 5.3 Common facility for indication 14 5.4 Processing
16、 in alarm standard-required processing elements 15 5.5 Connection to alarm transmission system 15 5.6 Interconnection .15 5.7 Power supplies .16 5.8 Timing requirements .16 5.9 Simultaneous occurrence of events .16 5.10 Verification of performance.16 5.11 Central control facilities for type 1 integr
17、ated alarm systems .17 6 Documentation and training 18 Annex A (informative) Application and installation guidelines and responsibilities .19 Figures Figure 1 First example of type 1 configuration 9 Figure 2 Second example of type 1 configuration Class 1 CCF . 9 Figure 3 Third example of type 1 conf
18、iguration Class 2 CCF .10 Figure 4 First example of type 2 configuration 10 Figure 5 Second example of type 2 configuration .11 Figure 6 Third example of type 2 configuration .11 Figure 7 Fourth example of type 2 configuration .12 Figure 8 Fifth example of type 2 configuration 12 DD CLC/TS 50398:200
19、9CLC/TS 50398:2009 - 4 - Introduction This Technical Specification describes the general requirements and configuration types for combined and integrated alarm systems which shall apply when one or more of the applications being integrated is an alarm application. In this document, the wording combi
20、ned and integrated alarm system is synonymous with integrated alarm system, which will mostly be used in the document. The prime considerations of this Technical Specification are to ensure that the individual alarm standards, requirements or guidelines are applied when they form a part of an integr
21、ated system solution with each other or with other (specified or unspecified) applications. This document provides additional information relating to initial system design, planning, installation, commissioning, operation and maintenance for such combined and integrated alarm systems. DD CLC/TS 5039
22、8:2009- 5 - CLC/TS 50398:2009 1 Scope This Technical Specification specifies the requirements for alarm systems combined and integrated with other systems which may or may not be alarm systems. This Technical Specification defines requirements, related to integration, in order to complement the indi
23、vidual alarm application standards and to provide clarification where there is conflict. Alarm transmission systems are excluded from the scope of this Technical Specification. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated
24、 references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 54 series, Fire detection and fire alarm systems EN 50130 series, Alarm systems EN 50131 series, Alarm systems Intrusion and hold-up systems EN 50
25、132 series, Alarm systems CCTV surveillance systems for use in security applications EN 50133 series, Alarm systems Access control systems for use in security applications EN 50134 series, Alarm systems Social alarm systems EN 50136 series, Alarm systems Alarm transmission systems and equipment EN 6
26、0073:2002, Basic and safety principles for man-machine interface, marking and identification Coding principles for indicators and actuators (IEC 60073:2002) 3 Definitions For the purposes of this document, the following terms and definitions apply. 3.1 additional facility facility which is not stand
27、ard-required by any of the applications of the integrated alarm system 3.2 alarm warning of the presence of a hazard to life, property or the environment 3.3 alarm application application intended for the protection of life, property or the environment, such as intrusion and hold-up alarm system, so
28、cial alarm system, lift alarm system environmental alarm system, closed circuit television used for security and surveillance, access control system, fire detection, fire alarm and fire protection systems NOTE 1 This list may be extended, to follow the scope of CLC/TC 79 and CEN/TC 72. NOTE 2 Exampl
29、es of an environmental alarm may include a warning of toxic effluent leaking or a storage tank about to overflow. DD CLC/TS 50398:2009CLC/TS 50398:2009 - 6 - 3.4 alarm receiving centre continuously manned centre to which information concerning the status of one or more alarm systems is reported 3.5
30、alarm company organization which provides services for alarm systems 3.6 alarm condition condition of an alarm system, or part thereof, which results from the response of the system to the presence of a hazard 3.7 alarm system electrical installation which responds to the manual or automatic detecti
31、on of the presence of a hazard 3.8 alarm transmission equipment equipment which is used primarily for the transmission of alarms from the alarm system interface at the supervised premises to the annunciation equipment interface at the alarm receiving centre. It may also transmit information or comma
32、nds from the alarm receiving centre to one or more alarm systems NOTE This does not include equipment provided by a PTT (Public and Private Telephone Transmission) or other general telecommunications equipment (for example modems) where these are used primarily for alarm transmission. 3.9 alarm tran
33、smission system equipment and network used to transfer information concerned with the state of one or more alarm systems to one or more alarm receiving centres 3.10 application all related facilities used for a specific purpose NOTE Such as the detection and warning in the event of fire, lighting co
34、ntrol, etc. 3.11 application standard standard relevant to a specific application 3.12 central control facility CCF equipment used for control and/or indicating purposes in type 1 configuration, which is connected to one or more dedicated systems and which is normally manned by operating personnel N
35、OTE For example a computer at a supervised location. The CCF is an additional facility (and not the standard-required control and indicating equipment) for at least one of the applications. 3.13 command signal instruction or command that affects one or more systems 3.14 common device device which is
36、 shared by two or more applications 3.15 common facility facility which is shared by two or more applications NOTE A common facility may be additional for two or more applications, it may be standard-required for two or more applications or it may be additional for one or more applications and stand
37、ard-required for other applications. DD CLC/TS 50398:2009- 7 - CLC/TS 50398:2009 3.16 common transmission path transmission path used by two or more applications 3.17 dedicated device device used by a single application 3.18 dedicated system system used for a single application 3.19 dedicated transm
38、ission path transmission path used solely within one application 3.20 facility hardware or software which enable a system to fulfil one or more functions NOTE For example a transmission path, a processing element, displays. 3.21 fault condition condition of a system which prevents a system or part t
39、hereof from functioning as designed 3.22 fault signal message generated due to the presence of a fault condition 3.23 integrated alarm system system having one or more common facilities with at least one being an alarm application NOTE 1 The alarm transmission system is not considered as a part of a
40、n integrated alarm system. NOTE 2 Dedicated systems only connected via a unidirectional output device without any data communications, for example relay, are not considered as being part of integrated alarm systems. 3.24 integrity ability of an application to function as designed including the measu
41、re of immunity from influences which could affect correct operation 3.25 log book record book or its electronic equivalent into which all relevant details of the system, its performance and its maintenance can be entered in a relatively secure manner for later retrieval by authorised organizations 3
42、.26 non-alarm application application intended to provide control and not intended primarily for the protection of life, property or the environment NOTE For example: heating and ventilating; energy management; building management; lighting. 3.27 processing element facility to perform mathematical o
43、r logical operations on data according to programmed instructions in order to obtain the required functions DD CLC/TS 50398:2009CLC/TS 50398:2009 - 8 - 3.28 standard-required facility facility necessary to fulfil a requirement of an application standard NOTE A standard-required facility may be share
44、d by two or more applications. In this case this facility may be a standard-required facility for one application but additional for another application. 3.29 tamper condition condition of an alarm system in which tampering has been detected 3.30 transmission path communication route used to convey
45、information within the integrated alarm system 4 General description and fundamental principles 4.1 General Three configurations or types of integrated alarm systems are specified. Type 1 is applicable for the combination and integration of dedicated alarm systems and dedicated non-alarm systems. Ty
46、pe 2A is applicable for the combination and integration of alarm systems and non-alarm systems using common transmissions paths, common devices and common facilities. A single fault in any one application has no adverse affect on any another alarm application. To achieve this redundancy is needed. T
47、ype 2B is applicable for the combination and integration of alarm systems and non alarm systems using common transmissions paths, common devices and common facilities. A single fault in one application may have an adverse affect on other alarm applications. 4.2 Standards For integrated alarm systems
48、 the standards relevant to each application shall apply. Common facilities shall comply with all application standards for which they are standard-required. The most severe integrity requirement of each of the standards shall apply. The common facilities not covered by the application standards shal
49、l meet the requirements of this Technical Specification. Dedicated facilities shall comply with the relevant application standards. 4.3 Configuration types of integrated alarm systems 4.3.1 Type 1 A type 1 configuration is a combination of two or more dedicated systems. These dedicated systems are connected to common additional facilities, for example interconnected via additional transmission paths. In a type 1 configuration the standard-required facilities in an alarm application, in a