1、December 2016 English price group 16No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 01.040.91; 91.140.10; 91.140.30
2、!%n7“2597520www.din.deDIN EN 14037-1Free hanging heating and cooling surfaces for water with a temperature below 120 C Part 1: Prefabricated ceiling mounted radiant panels for space heating Technical specifications and requirements;English version EN 140371:2016,English translation of DIN EN 14037-1
3、:2016-12An der Decke frei abgehngte Heiz und Khlflchen fr Wasser mit einer Temperatur unter 120 C Teil 1: Vorgefertigte Deckenstrahlplatten zur Raumheizung Technische Spezifikationen und Anforderungen;Englische Fassung EN 140371:2016,Englische bersetzung von DIN EN 14037-1:2016-12Panneaux rayonnants
4、 de chauffage et de rafrachissement aliments avec une eau une temprature infrieure 120 C Partie 1: Panneaux rayonnants de plafond prfabriqus destins au chauffage des locaux Spcifications techniques et exigences;Version anglaise EN 140371:2016,Traduction anglaise de DIN EN 14037-1:2016-12SupersedesDI
5、N EN 140371:200308See start of applicationwww.beuth.deDocument comprises 34 pagesDTranslation by DIN-Sprachendienst.In case of doubt, the German-language original shall be considered authoritative.12.16 DIN EN 14037-1:2016-12 2 A comma is used as the decimal marker. Start of application The start of
6、 application of this standard is 2016-12-01. It should be noted that, in Germany, CE conformity marking of construction products will be permitted once this standard has been listed in the Official Journal of the European Union and/or the Bundesanzeiger (German Federal Gazette) and from the date giv
7、en therein. For further information, users of this standard should refer to the websites of the European Commission or of the relevant building authority. The standard which this document replaces, DIN EN 14037-1:2003-08, may be used in parallel with this standard during a specified transition perio
8、d where such has been laid down in the Official Journal of the European Union and/or the Bundesanzeiger (German Federal Gazette). National foreword This document (EN 14037-1:2016) has been prepared by Technical Committee CEN/TC 130 “Space heating appliances without integral heat sources” (Secretaria
9、t: UNI, Italy). The responsible German body involved in its preparation was DIN-Normenausschuss Heiz- und Raumlufttechnik (DIN Standards Committee Heating and Ventilation Technology), Working Committee NA 041-01-69-52 AK Deckenstrahlplatten (SpA CEN/TC 130/WG 7). Amendments This standard differs fro
10、m DIN EN 14037-1:2003-08 as follows: a) the title of the standard has been modified; b) the Introduction has been modified; c) the scope has been changed; d) new terms and definitions have been included; e) Annex ZA has been revised. Previous editions DIN V 4706-1: 1993-06 DIN EN 14037-1: 2003-08 EU
11、ROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 14037-1 September 2016 ICS 91.140.10; 91.140.30 Supersedes EN 14037-1:2003English Version Free hanging heating and cooling surfaces for water with a temperature below 120C - Part 1: Pre-fabricated ceiling mounted radiant panels for space heating - T
12、echnical specifications and requirements Panneaux rayonnants de chauffage et de rafrachissement aliments avec une eau une temprature infrieure 120 C - Partie 1 : Panneaux rayonnants de plafond prfabriqus destins au chauffage des locaux - Spcifications techniques et exigences An der Decke frei abgehn
13、gte Heiz- und Khlflchen fr Wasser mit einer Temperatur unter 120 C - Teil 1: Vorgefertigte Deckenstrahlplatten zur Raumheizung - Technische Spezifikationen und Anforderungen This European Standard was approved by CEN on 19 March 2016. CEN members are bound to comply with the CEN/CENELEC Internal Reg
14、ulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN mem
15、ber. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
16、CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland
17、, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey andUnited Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2016 CEN All rights of exploitation in
18、any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14037-1:2016 EEN 14037-1:2016 (E) 2 Contents European foreword 4 Introduction . 5 1 Scope . 6 2 Normative references . 6 3 Terms and definitions 6 4 Symbols and units . 11 5 Requirements . 13 5.1 General manufacturing
19、 requirements 13 5.2 Surface protection. 13 5.3 Materials . 14 5.4 Surface emissivity . 14 5.5 Mechanical resistance . 14 5.5.1 Horizontal curvature of radiant ceiling panels 14 5.5.2 Vertical deflection of radiant ceiling panels . 15 5.6 Resistance to fixings . 15 5.7 Pressure tightness 15 5.8 Resi
20、stance to pressure 15 5.9 Dimensional tolerances 15 5.10 Upper Insulation 16 5.11 Water flow resistance 16 5.12 Release of dangerous substances 16 5.13 Reaction to fire . 16 5.13.1 General 16 5.13.2 Free hanging heating and cooling surfaces classified as Class A1 without the need for testing 16 5.13
21、.3 Free hanging heating and cooling surfaces classified according to the test results . 17 5.14 Rated thermal output and characteristic equation 17 5.15 Surface temperature 17 6 Assessment and verification of constancy of performance - AVCP . 17 6.1 General 17 6.2 Type testing . 17 6.2.1 General 17
22、6.2.2 Test samples, testing and compliance criteria . 18 6.2.3 Test reports . 19 6.2.4 Shared other party results . 19 6.3 Factory production control (FPC) . 20 6.3.1 General 20 6.3.2 Requirements . 20 6.3.3 Product specific requirements . 24 6.3.4 Initial inspection of factory and of FPC . 24 6.3.5
23、 Continuous surveillance of FPC 25 6.3.6 Procedure for modifications . 25 6.3.7 One-off products, pre-production products (e.g. prototypes) and products produced in very low quantity 26 7 Technical documentation . 27 7.1 General 27 7.2 Designation of the ceiling mounted radiant panels 27 7.3 Maximum
24、 operating pressure 27 7.4 Maximum operating temperature 27 DIN EN 14037-1:2016-12 EN 14037-1:2016 (E) 3 7.5 Thermal output respectively cooling capacity 27 7.6 Dimensions and technical data . 27 7.7 Reference data 28 7.8 Installation manual . 28 Annex ZA (informative) Relationship of this European
25、Standard with Regulation (EU) No. 305/2011 29 ZA.1 Scope and relevant characteristics . 29 ZA.2 System of Assessment and Verification of Constancy of Performance (AVCP) . 30 ZA.3 Assignment of AVCP tasks 30 Bibliography 32 DIN EN 14037-1:2016-12 EN 14037-1:2016 (E) 4 European foreword This document
26、(EN 14037-1:2016) has been prepared by Technical Committee CEN/TC 130 “Space heating appliances without integral heat sources”, the secretariat of which is held by UNI. This document supersedes EN 14037-1:2003. This European Standard shall be given the status of a national standard, either by public
27、ation of an identical text or by endorsement, at the latest by March 2017, and conflicting national standards shall be withdrawn at the latest by June 2018. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall
28、not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the Eu-ropean Free Trade Association, and supports basic work requirements of Regulation (EU) No. 305/2011. For relationship with Regulat
29、ion (EU) No. 305/2011, see informative Annex ZA, which is an integral part of this document. The main changes are: the title has been changed, the introduction has been changed, the scope has been changed, new definitions have been added, the Annex ZA has been adapted. According to the CEN/CENELEC I
30、nternal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland
31、, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portu-gal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 14037-1:2016-12 EN 14037-1:2016 (E) 5 Introduction This European Standard results from the recognition, that
32、heated and chilled ceiling radiant panels falling into the field of application hereinafter stated are traded on the basis of their thermal output. For evaluating and comparing different heated and chilled ceiling surfaces it is therefore necessary to refer to a heating stipulated value. As installa
33、tions with ceiling mounted radiant panels can also be used in practice for space cooling, it is nec-essary to have a test method for evaluating the cooling capacity. Installations with different free hanging heating and cooling surfaces need, for the use of space heating a test method for evaluating
34、 the heating out-put. The test method differs from the method for ceiling mounted radiant panels. The European Standard EN 14037, Free hanging heating and cooling surfaces for water with a temperature below 120C, consists of the following parts: Part 1: Pre-fabricated ceiling mounted radiant panels
35、for space heating - Technical specifications and re-quirements; Part 2: Pre-fabricated ceiling mounted radiant panels for space heating - Test method for thermal output; Part 3: Pre-fabricated ceiling mounted radiant panels for space heating - Rating method and evaluation of radiant thermal output;
36、Part 4: Pre-fabricated ceiling mounted radiant panels for space heating - Test method for cooling capacity; Part 5: Open or closed heated ceiling surfaces - Test method for thermal output. DIN EN 14037-1:2016-12 EN 14037-1:2016 (E) 6 1 Scope This European Standard defines technical specifications an
37、d requirements of free hanging pre-fabricated ceiling mounted radiant panels with an air gap between construction and the emitter (not embedded) fed with water at temperatures below 120 C connected with a centralized heating supply source intended to be installed in buildings. The panels should be i
38、nstalled with an upper insulation. The European Standard does not apply to independent heating devices. The European Standard also defines the additional common data that the manufacturer has to provide to the trade in order to ensure the correct application of the products. This European standard d
39、oes not cover the performance of hanging accessories. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indis-pensable for its application. For dated references, only the edition cited applies. For undated references, the latest
40、edition of the referenced document (including any amendments) applies. EN 13501-1, Fire classification of construction products and building elements - Part 1: Classification using da-ta from reaction to fire tests EN 14037-2:2016, Free hanging heating and cooling surfaces for water with a temperatu
41、re below 120C Part 2: Pre-fabricated ceiling mounted radiant panels for space heating - Test method for thermal output EN 14037-3:2016, Free hanging heating and cooling surfaces for water with a temperature below 120C - Part 3: Pre-fabricated ceiling mounted radiant panels for space heating - Rating
42、 method and evaluation of radiant thermal output EN ISO 2409, Paints and varnishes - Cross-cut test (ISO 2409) 3 Terms and definitions For the purposes of this document, the terms and definitions given below apply. 3.1 heating appliance device having the purpose of transferring heat in order to prov
43、ide specific temperature conditions inside buildings 3.2 independent heating appliance self-contained heating appliance which does not need to be connected to a remote heat source (e. g. a boiler) as it contains its own heat source (e. g. gas fired appliances, electric appliances, heat pump applianc
44、es) 3.3 pre-fabricated ceiling mounted radiant panel pre-fabricated heat-transmitting device in the form of a heating or cooling element with width of 0,3 m up to 1,5 m fitted with connection components or open pipes for in-side-assembling and designed to operate on water flow heating and/or cooling
45、 facilities DIN EN 14037-1:2016-12 EN 14037-1:2016 (E) 7 3.4 model ceiling mounted radiant panel or heated ceiling surface of defined construction, e.g. width, height, number and diameter of the tubes 3.5 type group of models with identical modular cross section 3.6 sample ceiling mounted radiant pa
46、nel or heated ceiling surface, used for testing 3.7 inlet water temperature bulk temperature of the water entering the ceiling mounted radiant panel 3.8 outlet water temperature bulk temperature of the water leaving the ceiling mounted radiant panel 3.9 mean water temperature arithmetical mean of in
47、let and outlet water temperature 3.10 water temperature drop temperature difference between the inlet and outlet water temperature of the pre-fabricated ceiling mount-ed radiant panel 3.11 mean radiant temperature temperature in a defined point of the room resulting from the radiation of all surroun
48、ding surfaces and of the pre-fabricated ceiling mounted radiant panel respectively heated ceiling surface 3.12 reference room temperature temperature measured with a globe thermometer 3.13 temperature difference temperature difference between mean water temperature and reference room temperature 3.1
49、4 standard temperature difference of ceiling mounted radiant panels (EN 14037-2) mean water temperature 75C and reference room temperature 20C, determined temperature difference 55 K 3.15 surface temperatures of the inside surfaces of the test room mean temperatures of the inside surfaces of the test room 3.16 mean surface temperature of the pre-fabricated ceiling mounted radiant panel mean temperature on the heating or coo