1、AMSC N/A FSC 5950 INCH-POUND MIL-PRF-27/344C 13 July 2012 SUPERSEDING MIL-PRF-27/344B 17 January 1986 PERFORMANCE SPECIFICATION SHEET TRANSFORMERS, POWER, 90 VOLTAMPERES, 3-PHASE This specification is approved for use by all Departments and agencies of the Department of Defense. The complete require

2、ments for procuring the transformer described herein shall consist of this document and the latest issue of specification MIL-PRF-27. (For dash numbers 01 through 07) Primary (For dash nos. 01 thru 07) WYE, 115 V to Com 1,2,3 line 4 Com WYE, 200 V L-L 1,2,3 (For dash numbers 08 through 21) SECONDARY

3、 WYE, L Com Connect 6-8-10, Load 5-6, 7-6, 9-6 DELTA, L-L Connect 6-7, 8-9 5-10, Load 5,7,9 WYE, L-L Connect 6-10, 8-10, Load 5,7,9 PRIMARY (For dash nos. 08 thru 14) Delta, 115 V L-L 1,2,3 PRIMARY (For dash nos. 15 thru 21) Delta, 200 V L-L 1,2,3 CIRCUIT DIAGRAMS FIGURE 1. Dimensions and configurat

4、ions. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-27/344C 2 NOTES: 1. Dimensions are in inches. 2. Metric equivalents are given for general information only. 3. Unless otherwise specified, tolerance is .04 (1.0 mm). 4. Marking shall be on

5、 top and side of case. 5. Terminal 4 is missing for dash nos. 08 thru 21. FIGURE 1. Dimensions and configurations - Continued. Inches mm .010 0.25 .02 0.5 .090 2.29 .1380 3.505 .20 5.1 .28 7.1 .40 10.2 .45 11.4 .85 21.8 1.49 37.8 2.00 50.8 2.44 62.0 2.50 63.5 2.94 74.7 Provided by IHSNot for ResaleN

6、o reproduction or networking permitted without license from IHS-,-,-MIL-PRF-27/344C 3 REQUIREMENTS: (When numbers in parentheses, i.e., (1-2) are used, they indicate the winding and the extreme terminals of the winding.) Electrical ratings: Primary voltage at 400 20 Hz Wye connected (dash numbers 01

7、 through 07). (1-4): 115 V ac. (2-4): 115 V ac. (3-4): 115 V ac. (1-2): 200 V ac. (1-3): 200 V ac. (2-3): 200 V ac. Delta connected (dash numbers 08 through 14) (1-2): 115 V ac. (1-3): 115 V ac. (2-3): 115 V ac. Delta connected (dash numbers 15 through 21) (1-2): 200 V ac. (1-3): 200 V ac. (2-3): 20

8、0 V ac. Secondary voltage: See table I. Secondary current: See table I. Working voltage: 535 volts peak, maximum. Design and construction: Dimensions and configuration: See figure 1. Duty cycle. Continuous. Case: Epoxy fiberglass. Terminals: Solderable turret type. Height: 0.28 .040 inch (7.11 1.02m

9、m). Diameter: 0.090 .010 inch (2.29 0.25mm). Weight: 1.3 pounds, maximum. Operating temperature range. -55 to +130C. Altitude: 70,000 feet. Terminal strength: MIL-STD-202, method 211, test condition A, 5 pounds. Dielectric withstanding voltage (Secondary connected wye): At atmospheric pressure (each

10、 winding): 1500 volts rms. At barometric pressure (each winding): 670 volts rms Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-27/344C 4 Electrical characteristics: Rated load: With rated voltage across the primary at 400 Hz, the voltage acr

11、oss each winding of the secondary, wye connected, shall be as specified in Table I within 5 percent at the current specified in TableI Regulation: 100)()()(xloadratedVoltageloadratedVoltageloadnoVoltage TABLE I. Electrical ratings - secondary. Dash numbers M27/344- Wye (L-Com) 4 wire 1/ Delta (L-L)

12、3 wire 2/ (each winding) Wye (L-Com) 4 wire 3/ (each winding) DC resistance 1/ Wye (L-Com) (each winding) Load current Load current 01, 08, 15 02, 09, 16 03, 10, 17 04, 11, 18 05, 12, 19 06, 13, 20 07, 14, 21 Volts rms 5 12 15 20 28 48 115 Amperes rms 6.00 2.50 2.00 1.50 1.08 0.63 0.26 Volts rms 8.6

13、6 20.8 26.0 34.6 48.5 83.1 200 Amperes rms 3.47 1.45 1.16 0.87 0.62 0.36 0.15 Ohms 25% .0147 .086 .135 .238 .510 1.39 8.37 1/ Wye, line to common, connect (6-8-10), load (5-6), (7-6), and (9-6). 2/ Delta, line to line, connect (6-7), (8-9), and (5-10), load (5-7-9). 3/ Wye, line to line, connect (6-

14、10), (8-10), load (5-7-9). Efficiency (at rated load): Shall be a minimum of 90 percent when computed as follows with Secondary connected wye, L-Com (Secondary voltage) (Secondary current) X 100 (Primary phase voltage)(Primary phase current) DC resistance (dash numbers 01 through 07): Primary: (1-4)

15、: 6.8 ohms 25 percent. (2-4): 6.8 ohms 25 percent. (3-4): 6.8 ohms 25 percent. DC resistance (dash numbers 08 through 14): Primary: (1-2): 4.53 ohms 25 percent. (2-3): 4.53 ohms 25 percent. (3-1): 4.53 ohms 25 percent. Provided by IHSNot for ResaleNo reproduction or networking permitted without lice

16、nse from IHS-,-,-MIL-PRF-27/344C 5 DC resistance (dash numbers 15 through 21): Primary: (1-2): 12.5 ohms 25 percent. (2-3): 12.5 ohms 25 percent. (3-1): 12.5 ohms 25 percent. Secondary: See table I. Temperature rise: 50C with rated voltage and current at 400 Hz, the secondary shall be wye connected

17、at an ambient temperature of 80C. Shock (specified pulse): MIL-STD-202, method 213. Marking location: See figure 1. Part or Identifying Number (PIN): M27/344-(dash number from table I). VERIFICATION: Extent of qualification: Qualification testing and approval to M27/344-07 and M27/349-18 shall be su

18、fficient to grant qualification approval to MIL-PRF-27/344 through MIL-PRF-27/349 inclusive, all parts. Qualification testing and approval to M27/344-21 shall be sufficient to grant qualification approval to M27/344-01 through M27/344-21. Changes from previous issue. The margins of this specificatio

19、n are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in these notations. Bidders and contractors are cautioned to evaluate the requirements of this doc

20、ument based on the entire content irrespective of the marginal notations and relationship to the last previous issue. Referenced documents. In addition to MIL-PRF-27, this document references the following: MIL-PRF-27/349 MIL-STD-202 Custodians: Preparing activity: Army - CR DLA - CC Navy - EC Air f

21、orce 85 DLA - CC Review activities: (Project 5950-2009-094) Army CR4, MI Navy - AS, MC, OS Air Force - 19, 99 NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https:/assist.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-