1、 AMSC N/A FSC 5935 INCH-POUND W-C-596/150B 10 October 2012 SUPERSEDING W-C-596/150A 3 May 1988 FEDERAL SPECIFICATION SHEET CONNECTOR, CABLE OUTLET, ELECTRICAL, SPECIFIC PURPOSE, SINGLE GROUNDING, LOCKING, 2 POLE, 3 WIRE, 30 AMPERES, 28 VOLTS, DIRECT CURRENT The General Services Administration has au

2、thorized the use of this federal specification, by all federal agencies. The complete requirements for procuring connector described herein shall consist of this document and the latest issue in effect of W-C-596. FIGURE 1. Configuration and dimensions. Inches mm 0.093 2.36 0.100 2.54 0.105 2.67 0.1

3、09 2.77 0.114 2.90 0.281 7.14 0.352 8.94 0.500 12.70 1.125 28.58 1.860 47.24 3.750 95.25 Inactive for new design after 10 October 2012. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C-596/150B 2 NOTES: 1. Dimensions are in inches. 2. Metric equiv

4、alents are given for information only. 3. Unless otherwise specified, tolerance is .005 (0.13 mm) on all decimals and 5 on angles. FIGURE 1. Configuration and dimensions - Continued. REQUIREMENTS: Design and configuration: See figure 1. Armored construction: Not acceptable. Ratings: Voltage: 28 volt

5、s. Current: 30 amperes. Frequency: Direct current Vibration: Method 204 of MIL-STD-202, test condition B (WC596/150-2 only). Shock: Method 213 of MIL-STD-202, test condition I (WC596/150-2 only). Mating connector: W-C-596/149. Strain relief: Accommodate cable diameter .296 - .625 inch (7.52 - 15.88

6、mm). Part or Identifying Number (PIN): The PIN consists of the prefix W-C, the basic specification number, the specification sheet number, and the style number. W-C- 596 /150 -1 Style number (see table I) Specification sheet number Specification number W-C Prefix TABLE I. Dash number. Dash no. Super

7、sedes style Description 1 2 ruggedizedChanges from previous issue. Marginal notations are not used in the revision to identify changes with respect to the previous issue due to the extensiveness of the changes. Referenced documents. In addition to W-C-596, this document references the following: W-C

8、-596/149 MIL-STD-202 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C-596/150B 3 CONCLUDING MATERIAL MILITARY INTERESTS: CIVIL AGENCY COORDINATING ACTIVITIES: Custodians: DCGOVT - DCG Army - CR DOT - ACO Navy - YD GSA - 7FXE Air Force - 85 HHS - F

9、EC DLA - CC USDA - AFS Review activities: Preparing activity: Army AR, AV, CR4, MI DLA - CC Navy - AS, EC, MC, SH Air Force 19, 99 (Project 5935-2012-089) NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https:/assist.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-