DLA W-F-1814 6 D-2013 FUSE CARTRIDGE HIGH INTERRUPTING CAPACITY CLASS J (CURRENT-LIMITING) 600 VOLTS 31-60 AMPERES.pdf

上传人:Iclinic170 文档编号:701583 上传时间:2019-01-01 格式:PDF 页数:3 大小:38.53KB
下载 相关 举报
DLA W-F-1814 6 D-2013 FUSE CARTRIDGE HIGH INTERRUPTING CAPACITY CLASS J (CURRENT-LIMITING) 600 VOLTS 31-60 AMPERES.pdf_第1页
第1页 / 共3页
DLA W-F-1814 6 D-2013 FUSE CARTRIDGE HIGH INTERRUPTING CAPACITY CLASS J (CURRENT-LIMITING) 600 VOLTS 31-60 AMPERES.pdf_第2页
第2页 / 共3页
DLA W-F-1814 6 D-2013 FUSE CARTRIDGE HIGH INTERRUPTING CAPACITY CLASS J (CURRENT-LIMITING) 600 VOLTS 31-60 AMPERES.pdf_第3页
第3页 / 共3页
亲,该文档总共3页,全部预览完了,如果喜欢就下载吧!
资源描述

1、 AMSC N/A FSC 5920 INCH-POUND W-F-1814/6D 15 November 2013 SUPERSEDING W-F-1814/6C 27 July 2009 FEDERAL SPECIFICATION SHEET FUSE, CARTRIDGE, HIGH INTERRUPTING CAPACITY, CLASS J (CURRENT-LIMITING) 600 VOLTS, 31-60 AMPERES The General Services Administration has authorized the use of this federal spec

2、ification, by all federal agencies. The complete requirements for procuring the fuses described herein shall consist of this document and the latest issue in effect of W-F-1814. Ltr Inches mm Min Max Min Max A 2.350 2.410 59.69 61.21 B .980 1.020 24.89 25.91 C .620 - 15.75 - D 1.054 1.070 26.77 27.1

3、8 NOTES: 1. Dimensions are in inches. 2. Metric equivalents are given for general information only. 3. Unless otherwise specified, tolerances are .02 (0.51 mm) for two-place decimals and .005 (0.13 mm) for three-place decimals. FIGURE 1. Configuration and dimensions. Provided by IHSNot for ResaleNo

4、reproduction or networking permitted without license from IHS-,-,-W-F-1814/6D 2 REQUIREMENTS: Interface and physical dimensions: See figure 1. Physical: Nonrenewable. Terminals: Ferrule type: Material: Brass, copper or copper alloy. Strength: 5 pound-inches torque between body and ferrules. Body: In

5、sulating material: Ceramic, melamine-impregnated glass fiber, or the equivalent. Electrical: Voltage: 600 volts or less. Frequency: 48 Hz to 60 Hz . Current: See table I. Current carrying capacity: 100 percent indefinitely with temperature rise not to exceed 55C above ambient on the ferrules. Overlo

6、ad interrupt: Shall interrupt within 1 hour at 135 percent of rated current and within 6 minutes at 200 percent of rated current. Interrupting capacity rating: 200,000 amperes rms symmetrical at 600 volts, 60 Hz and a power factor of 20 percent or less. Closing angle shall be essentially at the zero

7、 of the voltage wave (maximum offset) or later, to produce start of arcing within 30 electrical degrees prior to system peak voltage. Threshold ratio: 30 maximum. Maximum peak let-thru current: See table I. Maximum clearing I2T: See table I. Applicable fuseholders: Class J for ferrule type fuses in

8、accordance with UL 4248-8. Part or Identifying Number (PIN): See table I. TABLE I. Electrical characteristics. 1/ Government PIN Current rating (amperes) Maximum peak let-thru current amperes Maximum clearing I2T x 103WF1814/06-001 35 7,500 12 WF1814/06-002 40 8,000 17 WF1814/06-003 45 8,500 18 WF18

9、14/06-004 50 9,000 22 WF1814/06-005 60 10,000 30 1/ For silver plated terminals, the designator “S“ is added after the dash number. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-F-1814/6D 3 Referenced documents. In addition to W-F-1814, this docu

10、ment references the following: UL 4248-8 The margins of this specification sheet are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in these notations.

11、 Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue. MILITARY INTEREST: CIVIL AGENCY COORDINATING ACTIVITIES: Custodians: GSA - FAS Army - CR Navy - EC Prep

12、aring activity: Air Force - 85 DLA - CC DLA - CC Review activities: (Project 5920-2013-009) Army - AT, CR4 Navy - OS NSA - NS NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https:/assist.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1