1、BRITISH STANDARD BS EN 60570:2003 Electrical supply track systems for luminaires The European Standard EN 60570:2003 has the status of a British Standard ICS 29.120.20; 29.140.40 BS EN 60570:2003 This British Standard was published under the authority of the Standards Policy and Strategy Committee o
2、n 24 September 2003 BSI 24 September 2003 ISBN 0 580 42639 4 National foreword This British Standard is the official English language version of EN 60570:2003. It was derived by CENELEC from IEC 60570:2003. It supersedes BS EN 60570:1997 and BS EN 60570-2-1:1995 which will be withdrawn on 2010-03-01
3、. The CENELEC common modifications have been implemented at the appropriate places in the text and are indicated by tags (e.g.) The UK participation in its preparation was entrusted to Technical Committee CPL/34/4, Luminaires, which has the responsibility to: A list of organizations represented on t
4、his committee can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by usi
5、ng the “Search” facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity f
6、rom legal obligations. aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in th
7、e UK. Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 21 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No. Date CommentsEUROPEAN
8、STANDARD EN 60570 NORME EUROPENNE EUROPISCHE NORM July 2003 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2003 CENELEC - All r
9、ights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 60570:2003 E ICS 29.120.20; 29.140.40 Supersedes EN 60570:1996 + A1:1998 + A2:2000 b) 1 track supply connector; c) 1 end cover (if required); d) 1 coupler per length of track supplied (if applicabl
10、e) (minimum of 3); e) 1 adaptor per length of track supplied (minimum of 3); f) 1 luminaire supply connector per length of track supplied (if applicable) (minimum of 3); g) the necessary suspension devices and any other components as specified by the manufacturer in his installation instructions; h)
11、 a typical luminaire representing the most unfavourable combination from a testing point of view for the purpose of the test of clause 11; i) additionally with a class III test sample, one selection of track of each type of class I track made by the same manufacturer. NOTE Item i) is required for th
12、e tests of 8.1.1 when testing a class III track. 5.4 Unless otherwise specified, the tests are carried out in the order of the clauses. 6 Marking The provisions of section three of IEC 60598-1 apply together with the requirements in 6.1 to 6.7. 6.1 The track shall be marked with rated current (A), r
13、ated voltage (V) and the graphical symbol IEC 60417-5180 for class III equipment if appropriate. A mixed supply system shall be marked with rated current (A), rated voltage (V) on the mains voltage sector and on the SELV sector respectively. The SELV sector shall also be marked with the symbol for c
14、lass III. 6.2 Adaptors need only be marked with their rated current, rated voltage, manufacturers name or trade mark and type reference and the graphical symbol IEC 60417-5180 for class III equipment if appropriate. Adaptors and luminaire supply connectors incorporated in luminaires do not require m
15、arking additional to that of the luminaire. If the adaptor has a fuse incorporated, the rated current and type of fuse shall be marked on the body of the adaptor. 6.3 Couplers and connectors need only be marked with the manufacturers name or trade mark and type reference and the graphical symbol IEC 60417-5180 for class III equipment if appropriate. Page7 EN60570:2003