1、BRITISH STANDARDBS EN 61557-5:2007Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. Equipment for testing, measuring or monitoring of protective measures Part 5: Resistance to earth The European Standard EN 61557-5:2007 has the status of a British StandardICS
2、17.220.20; 29.080.01; 29.240.01g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58BS EN 61557-5:2007This British Standard was published under the autho
3、rity of the Standards Policy and Strategy Committee on 29 June 2007 BSI 2007ISBN 978 0 580 50858 5National forewordThis British Standard was published by BSI. It is the UK implementation of EN 61557-5:2007. It is identical with IEC 61557-5:2007. It supersedes BS EN 61557-5:1997, which will be withdr
4、awn on 1 March 2010.The UK participation in its preparation was entrusted to Technical Committee PEL/85, Measuring equipment for electrical and electromagnetic quantities.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purpo
5、rt to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations.Amendments issued since publicationAmd. No. Date CommentsEUROPEAN STANDARD EN 61557-5 NORME EUROPENNE EUROPISCH
6、E NORM March 2007 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2007 CENELEC - All rights of exploitation in any form and by a
7、ny means reserved worldwide for CENELEC members. Ref. No. EN 61557-5:2007 E ICS 17.220.20; 29.080.01; 29.240.01 Supersedes EN 61557-5:1997English version Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. - Equipment for testing, measuring or monitoring of prot
8、ective measures - Part 5: Resistance to earth (IEC 61557-5:2007) Scurit lectrique dans les rseaux de distribution basse tension de 1 000 V c.a. et 1 500 V c.c. - Dispositifs de contrle, de mesure ou de surveillance de mesures de protection - Partie 5: Rsistance la terre (CEI 61557-5:2007) Elektrisch
9、e Sicherheit in Niederspannungsnetzen bis AC 1 000 V und DC 1 500 V - Gerte zum Prfen, Messen oder berwachen von Schutzmanahmen - Teil 5: Erdungwiderstand (IEC 61557-5:2007) This European Standard was approved by CENELEC on 2007-03-01. CENELEC members are bound to comply with the CEN/CENELEC Interna
10、l Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC memb
11、er. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC
12、 members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, S
13、lovenia, Spain, Sweden, Switzerland and the United Kingdom. EN 61557-5:2007 2 Foreword The text of document 85/294/FDIS, future edition 2 of IEC 61557-5, prepared by IEC TC 85, Measuring equipment for electrical and electromagnetic quantities, was submitted to the IEC-CENELEC parallel vote and was a
14、pproved by CENELEC as EN 61557-5 on 2007-03-01. This European Standard supersedes EN 61557-5:1997. The following changes were made with respect to EN 61557-5:1997: complete revision of the definitions; revision of some requirements. This standard is to be used in conjunction with EN 61557-1. The fol
15、lowing dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2007-12-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2010-03-01 Annex ZA has been
16、 added by CENELEC. _ Endorsement notice The text of the International Standard IEC 61557-5:2007 was approved by CENELEC as a European Standard without any modification. _ 3 EN 61557-5:2007 CONTENTS 1 Scope 4 2 Normative references .4 3 Terms and definitions .4 4 Requirements.5 5 Marking and operatin
17、g instructions .6 5.1 Marking.6 5.2 Operating instructions .7 6 Tests7 Annex ZA (normative) Normative references to international publications with their corresponding European publications .8 Table 1 Calculation of operating uncertainty.5 EN 61557-5:2007 4 ELECTRICAL SAFETY IN LOW VOLTAGE DISTRIBUT
18、ION SYSTEMS UP TO 1 000 V a.c. AND 1 500 V d.c. EQUIPMENT FOR TESTING, MEASURING OR MONITORING OF PROTECTIVE MEASURES Part 5: Resistance to earth 1 Scope This part of IEC 61557 specifies the requirements for equipment for measuring earth resistance using an a.c. voltage. 2 Normative references The f
19、ollowing referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 61010-1:2001, Safety requirements for electrical e
20、quipment for measurement, control, and laboratory use Part 1: General requirements IEC 61557-1, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. Equipment for testing, measuring or monitoring of protective measures Part 1: General requirements 3 Terms and def
21、initions For the purposes of this document, the definitions given in IEC 61557-1 and the following definitions apply. 3.1 series interference voltage extraneous voltage superimposed on the measuring voltage 3.2 auxiliary earth electrode additional earth electrode for a current required for the purpo
22、se of measurements 3.3 auxiliary earth electrode resistance RHresistance of an additional earth electrode through which current flows that is required for the purpose of measurements 3.4 probe additional earth electrode used as a probe for sampling potentials during measurements 5 EN 61557-5:2007 3.
23、5 probe resistance RSearth electrode resistance of an additional earth electrode used as a probe for sampling potentials during measurements 4 Requirements The following requirements as well as those given in IEC 61557-1 shall apply. 4.1 The output voltage present across the terminals E and H shall
24、be an a.c. voltage without a d.c. component. The frequency and the waveform shall be chosen so that electrical interference, particularly from installations operating with system frequency, will not adversely influence the measurement result to an excessive degree. 4.2 If the influence of interferen
25、ce voltages from distribution systems as a.c. currents or as d.c. currents exceeds the requirements of 4.3, this shall be stated by the manufacturer in the operating instructions. 4.3 The maximum percentage operating uncertainty within the measurement range to be marked or stated shall not exceed 30
26、 % with the measured value as fiducial value, as determined in accordance with Table 1. Table 1 Calculation of operating uncertainty Intrinsic uncertainty or influence quantity Reference conditions or specified operating range Designationcode Requirements or test in accordance with the relevant part
27、s of IEC 61557 Type of test Intrinsic uncertainty Reference conditions A Part 5, subclause 6.1 R Position Reference position 90 E1Part 1, subclause 4.2 R Supply voltage At the limits stated by the manufacturer E2Part 1, subclauses 4.2, 4.3 R Temperature 0 C and 35 C E3Part 1, subclause 4.2 T Series
28、interference voltage See 4.2 and 4.3 E4Part 5, subclauses 4.2, 4.3 T Resistance of the probes and auxiliary earth eletrodes 0 to 100 RAbut 50 k E5Part 5, subclause 4.3 T System frequency 99 % and 101 % of the nominal frequency E7Part 5, subclause 4.3 T System voltage 85 % and 110 % of the nominal vo
29、ltage E8Part 5, subclause 4.3 T Operating uncertainty )1,15(28272524232221EEEEEEEAB +=Part 5, subclause 4.3 R A = intrinsic uncertainty En= variations R = routine test T = type test B % = Bfiducial value100 % EN 61557-5:2007 6 The operating uncertainty shall apply under the rated operating condition
30、s given in IEC 61557-1 and the following: injection of series interference voltages with system frequencies of 400 Hz, 60 Hz, 50 Hz, 162/3Hz or with d.c. voltage respectively across the terminals E (ES) and S or to the earth resistance loop. The r.m.s. value of the series interference voltage for eq
31、uipment with auxiliary probes shall be 3 V. For equipment using current clamps, the presence of interfering disturbances shall be clearly indicated, if the influence quantity will exceed the specified value of the variation E4and of operating uncertainty; resistance of the auxiliary earth electrode
32、and of the probes: 0 to 100 RAbut 50 k; system voltages between 85 % and 110 % of the nominal voltage and between 99 % and 101 % of the nominal system frequency for measuring equipment with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system. 4
33、.4 The measuring equipment shall be capable of determining whether the maximum permissible resistances of the probes and auxiliary earth electrodes are exceeded. 4.5 No hazardous touch voltages shall appear during the measurements. This can be achieved by a suitable design of the source for the outp
34、ut voltage by: limiting the open-circuit value of the output voltage to an r.m.s. value of 50 V or a peak value of 70 V; NOTE The open-circuit voltage during measurements in agricultural plants should not exceed an r.m.s. value of 25 V or a peak value of 35 V. limiting the r.m.s. (peak) value of the
35、 short-circuit current to 3,5 mA (5 mA) when the value of the voltage exceeds 50 V (70 V) or 25 V (35 V). When no compliance with the above condition exists, then an automatic disconnection of the measurement process shall operate within a time period permissible according to Figure 1 of IEC 61010-1
36、. 4.6 The user shall not be exposed to a voltage exceeding the permissible touch voltage and the measuring equipment shall recover within specification, when any plug or socket of the measuring equipment, intended for connection to the distribution systems power supply is connected to 120 % of its n
37、ominal voltage. Protective devices shall not be activated. 5 Marking and operating instructions 5.1 Marking In addition to the marking in accordance with IEC 61557-1, the following information shall be provided on the measuring equipment. 5.1.1 Measurement range within which the maximum operating un
38、certainty applies. 5.1.2 Frequency of the output voltage. 5.1.3 Designation of the terminals (as far as applicable): E: terminal for the earth electrode; ES: terminal for the probe placed nearest to the earth electrode; S: terminal for a probe; H: terminal for the auxiliary earth electrode. 7 EN 615
39、57-5:2007 5.2 Operating instructions The operating instructions shall state the following in addition to the statements in IEC 61557-1. 5.2.1 The range of applications (e.g. for agricultural plants or others) for the equipment for measuring earth resistance. 5.2.2 If applicable, the influence of ser
40、ies interference voltages that are larger than the values stated under 4.3. 5.2.3 A statement relating to the correct operation of the hand-driven generator (if provided). 5.2.4 The designations of terminals when different from 5.1.3. 6 Tests In addition to IEC 61557-1 the following tests shall be e
41、xecuted. 6.1 The operating uncertainty shall be determined in accordance with Table 1. In this process, the intrinsic uncertainty shall be determined under the following reference conditions: nominal value of the supply voltage; nominal r.p.m. of the hand-driven generator when used as a supply; nomi
42、nal frequency of the power supply in the case of mains-operated measuring equipment according to 4.3; reference temperature 23 C 2 C; reference position in accordance with the manufacturers statement; resistances of probes and auxiliary earth electrodes 100 ; interference voltage 0 V. The operating
43、uncertainty thus evaluated shall not exceed the limits specified in 4.3. 6.2 A check as to whether the conditions for the open-circuit voltage, short-circuit current and disconnect delay stated under 4.5 are met in each of the measurement ranges (routine test). 6.3 A check as to whether exceeding th
44、e permissible maximum resistances for probes and auxiliary earth electrodes is indicated (type test). 6.4 The overload protection in accordance with 4.6 shall be tested (type test), when any plug or socket of the measuring equipment, intended for conncetion to the distribution systems power supply i
45、s connected to 120 % of its nominal voltage. Protective devices shall not be activated. 6.5 Compliance with the tests in this clause shall be recorded. EN 61557-5:2007 8 Annex ZA (normative) Normative references to international publications with their corresponding European publications The followi
46、ng referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE When an international publication has been modified by
47、common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD YearIEC 61010-1 2001 Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements EN 61010-1 + corr. June 2001 2002 IEC 61557-1 -1)Electrical
48、 safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements EN 61557-1 20072)1)Undated reference. 2)Valid edition at date of issue. blankBS EN 61557-5:2007BSI389 Chiswick High R
49、oadLondonW4 4ALBSI British Standards InstitutionBSI is the independent national body responsible for preparing British Standards. It presents the UK view on standards in Europe and at the international level. It is incorporated by Royal Charter.RevisionsBritish Standards are updated by amendment or revision. Users of British Standards should make sure that they possess the latest amendments or editions.It is the constant