1、*USACE / NAVFAC / AFCESA / NASA UFGS-23 81 00.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-23 81 00.00 20 (July 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION TABLE OF CONTENTSDIVISION 23 - HEATING, VENTILATING, AND AI
2、R CONDITIONINGSECTION 23 81 00.00 20UNITARY AIR CONDITIONING EQUIPMENT11/09PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 SUBMITTALS1.4 QUALITY ASSURANCE1.4.1 Modification of References1.4.2 Detail Drawing1.4.3 Safety1.4.4 Posted Operating Instructions1.4.5 Sizing1.5 REFRIGERANTS1.6 ENVIRON
3、MENTAL REQUIREMENTS1.7 SUSTAINABLE DESIGN REQUIREMENTS1.7.1 Local/Regional Materials1.7.2 Environmental DataPART 2 PRODUCTS2.1 ROOM AIR CONDITIONERS2.1.1 Units for Operation on 115 Volts2.1.2 Units for Operation on 208 or 230 Volts2.1.3 Controls2.2 PACKAGED TERMINAL UNITS2.2.1 Heat Pumps2.2.2 Air Co
4、nditioners2.2.3 Indoor Noise Rating2.2.4 Room Cabinets2.2.5 Grilles2.2.6 Wall Sleeves and Mounts2.2.7 Heating Section for Air Conditioners2.2.8 Refrigeration Sections2.2.9 Ventilation Damper Assembly2.2.10 Air Filters2.2.11 ControlsSECTION 23 81 00.00 20 Page 1Provided by IHSNot for ResaleNo reprodu
5、ction or networking permitted without license from IHS-,-,-2.3 HEAT PUMPS, AIR TO AIR2.3.1 Energy Performance2.3.2 Air Coils2.3.3 Supplemental Electric Heaters2.3.4 Compressors2.3.5 Mounting Provisions2.3.6 Temperature Controls2.3.7 Accessories2.4 AIR CONDITIONERS2.4.1 Single Package Type2.4.2 Split
6、-System Type2.4.3 Single Zone Units2.4.4 Multizone Units2.4.5 Heaters2.4.6 Compressors2.4.7 Coils2.4.8 Condenser Controls2.4.9 Fans2.4.10 Filters2.4.11 Filter Boxes2.4.12 Mixing Boxes2.4.13 Thermostats2.4.13.1 Cooling2.4.13.2 Heating2.4.13.3 Supply Air Fan2.5 FILTERS2.5.1 Replaceable Type Filters2.5
7、.2 High Efficiency Filters2.5.3 Cleanable Type Filters2.5.4 Manometers2.6 COATINGS FOR FINNED TUBE COILS2.6.1 Phenolic Coating2.6.2 Chemical Conversion Coating with Polyelastomer Finish Coat2.6.3 Vinyl Coating2.7 MOTORS AND STARTERS2.8 REFRIGERANT PIPING AND ACCESSORIES2.8.1 Factory Charged Tubing2.
8、8.2 Field-Assembled Refrigerant Piping2.8.3 Fittings2.8.4 Brazing Filler Material2.8.5 Pipe Hangers and Supports2.8.6 Pipe Sleeves2.8.6.1 Sleeves in Masonry and Concrete Walls, Floors, and Roofs2.8.6.2 Sleeves in Partitions and Non-Masonry Structures2.9 FINISHES2.10 SOURCE QUALITY CONTROL2.10.1 Salt
9、-Spray TestsPART 3 EXECUTION3.1 EQUIPMENT INSTALLATION3.1.1 Packaged Terminal Air Conditioners and Heat Pumps3.1.2 Unitary Air Conditioning System3.1.3 Room Air Conditioners3.2 PIPING3.2.1 Pipe Hangers and Supports3.2.2 Refrigerant Piping3.2.3 Returning Oil From Refrigerant System3.2.4 Refrigerant D
10、riers, Sight Glass Indicators, and StrainersSECTION 23 81 00.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3.2.5 Strainer Locations and Installation3.2.6 Solenoid Valve Installation3.3 AUXILIARY DRAIN PANS, DRAIN CONNECTIONS, AND DRAIN
11、LINES3.4 ACCESS PANELS3.5 AIR FILTERS3.6 FLASHING AND PITCH POCKETS3.7 IDENTIFICATION TAGS AND PLATES3.8 FIELD QUALITY CONTROL3.8.1 Leak Testing3.8.2 Evacuation, Dehydration, and Charging3.8.3 Start-Up and Initial Operational Tests3.8.4 Performance Tests3.9 WASTE MANAGEMENT3.10 SCHEDULE- End of Sect
12、ion Table of Contents -SECTION 23 81 00.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-23 81 00.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-23 81 00.00 20 (July 2006)UNIFIED FACIL
13、ITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION 23 81 00.00 20UNITARY AIR CONDITIONING EQUIPMENT11/09*NOTE: This guide specification covers the requirements for room air conditioners, packaged terminal units, heat pumps, and air conditioners of the single p
14、ackage or split system type.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not
15、brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a
16、UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organiz
17、ation, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the SECTION 23 81 00.00 20 Page 4Provided by IHSNot for ResaleNo reproduction or
18、networking permitted without license from IHS-,-,-Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The
19、 publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.AIR-CONDITIONING, HEATING AND REFRIGERATION INSTITUTE (AHRI)AHRI 210/240 (2008) Performance Rating of Unitary Air-Conditioning and Air
20、-Source Heat Pump EquipmentAHRI 310/380 (2004) Standard for Packaged Terminal Air-Conditioners and Heat PumpsAHRI 340/360 (2004) Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump EquipmentAHRI 350 (2000) Sound Rating of Non-Ducted Indoor Air-Conditioning Equipmen
21、tAHRI DCAACP (Online) Directory of Certified Applied Air-Conditioning ProductsAHRI DCUP (Online) Directory of Certified Unitary ProductsAMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS (ASHRAE)ASHRAE 15 Std 15 Errata 2007, 2009, Std 34 Errata 2007, 2008, Addenda a-y, aa-ae)
22、ANSI/ASHRAE Standard 15-Safety Standard for Refrigeration Systems and ANSI/ASHRAE Standard 34-Designation and Safety Classification of RefrigerantsASHRAE 52.2 (2007; Addenda B 2008; Errata 2009) Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle SizeASHRAE
23、55 (2004; Int 1:2005; Errata:2006; Int 2:2007; Errata:2007; Addendas A, B:2008; Addendas D - G:2009) Thermal Environmental Conditions for Human OccupancyASHRAE 62.1 (2007; INT 2007; INT 2-15 2008; Errata 2008; Addenda a, b, e, f and h 2008) Ventilation for Acceptable Indoor Air QualitySECTION 23 81
24、00.00 20 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ASHRAE 90.1 - IP (2007; Supplement 2008; Errata 2009; Errata 2009) Energy Standard for Buildings Except Low-Rise Residential Buildings, I-P EditionASHRAE 90.1 - SI (2007; Supplement 2008;
25、 Errata 2009; Errata 2009) Energy Standard for Buildings Except Low-Rise Residential Buildings, SI EditionAMERICAN WELDING SOCIETY (AWS)AWS A5.8/A5.8M (2004; Errata 2004) Specification for Filler Metals for Brazing and Braze WeldingASME INTERNATIONAL (ASME)ASME B16.22 (2001; R 2005) Standard for Wro
26、ught Copper and Copper Alloy Solder Joint Pressure FittingsASME B31.5 (2006) Refrigeration Piping and Heat Transfer ComponentsASSOCIATION OF HOME APPLIANCE MANUFACTURERS (AHAM)AHAM RAC-1 (2005) Directory of Certified Room Air ConditionersASTM INTERNATIONAL (ASTM)ASTM A 123/A 123M (2009) Standard Spe
27、cification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel ProductsASTM A 653/A 653M (2009) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip ProcessASTM B 117 (2009) Standing Practice for Operating Salt Spray (Fog) Appa
28、ratusASTM B 280 (2008) Standard Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field ServiceASTM B 88 (2003) Standard Specification for Seamless Copper Water TubeASTM B 88M (2005) Standard Specification for Seamless Copper Water Tube (Metric)ASTM C 534/C 534M (2008) St
29、andard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular FormSECTION 23 81 00.00 20 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ASTM D 1654 (2008) Evaluation of Painted or Coated Specimens Sub
30、jected to Corrosive EnvironmentsASTM E 2129 (2005) Standard Practice for Data Collection for Sustainability Assessment of Building ProductsASTM E 84 (2009c) Standard Test Method for Surface Burning Characteristics of Building MaterialsASTM F 1040 (1987; R 2007) Standard Specification for Filter Unit
31、s, Air Conditioning, Viscous - Impingement and Dry Types, ReplaceableASTM F 872 (1984; R 1990) Filter Units, Air Conditioning: Viscous-Impingement Type, CleanableMANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)MSS SP-58 (2002) Standard for Pipe Hangers and Supports - Ma
32、terials, Design and ManufactureMSS SP-69 (2003; R 2004) Standard for Pipe Hangers and Supports - Selection and ApplicationNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)NEMA ICS 1 (2000; R 2005; R 2008) Standard for Industrial Control and Systems General RequirementsNEMA ICS 2 (2000; Errata 200
33、2; R 2005; Errata 2006) Standard for Industrial Control and Systems: Controllers, Contactors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control EquipmentNEMA ICS 6 (1993; R 2006) Standard for Industrial Controls and Syste
34、ms EnclosuresNEMA MG 1 (2007; Errata 2008) Standard for Motors and GeneratorsU.S. DEPARTMENT OF DEFENSE (DOD)MIL-DTL-5541 (Rev F) Chemical Conversion Coatings on Aluminum and Aluminum AlloysU.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling Sy
35、stemSECTION 23 81 00.00 20 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-U.S. GENERAL SERVICES ADMINISTRATION (GSA)FS A-A-50502 (Basic) Air Conditioners, (Unitary Heat Pump), Air to Air (3,000 to 300,000 BTU)FS OO-A-373 (Rev D) Air Conditione
36、rs, Single Package TypeFS OO-A-374 (Rev C) Air Conditioners with Remote Condensing Units or Remote Air-Cooled, and Water-Cooled Condenser Units, UnitaryU.S. GREEN BUILDING COUNCIL (USGBC)LEED (2002; R 2005) Leadership in Energy and Environmental Design(tm) Green Building Rating System for New Constr
37、uction (LEED-NC)UNDERWRITERS LABORATORIES (UL)UL 109 (1997; Rev May 2009) Tube Fittings for Flammable and Combustible Fluids, Refrigeration Service, and Marine UseUL 484 (2007; Rev thru Mar 2009) Room Air ConditionersUL 873 (2007; Rev thru Oct 2009)Temperature-Indicating and -Regulating EquipmentUL
38、900 (2004; Rev thru Nov 2007) Standard for Air Filter Units1.2 RELATED REQUIREMENTSSection 23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS, applies to this section with the additions and modifications specified herein.1.3 SUBMITTALS*NOTE: Submittals must be limited to those necessary for adequ
39、ate quality control. The importance of an item in the project should be one of the primary factors in determining if a submittal for the item should be required.A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”.
40、Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.SECTION 23 81 00.00 20 Page 8Provided by IHSNot for ResaleNo reproductio
41、n or networking permitted without license from IHS-,-,-For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident M
42、anagement System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy projects.Submitt
43、al items not designated with a “G“ are considered as being for information only for Army projects and for Contractor Quality Control approval for Navy projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality C
44、ontrol approval.for information only. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsField-assembled refrigera
45、nt pipingControl system wiring diagramsSD-03 Product DataRoom air conditionersPackaged terminal unitsHeat pumps, air to airAir conditionersSubmit documentation for Energy Star qualifications or meeting FEMP requirements. Indicate Energy Efficiency Rating.Filters; (LEED) Submit documentation indicati
46、ng type of biobased material in product and biobased content. Indicate relative dollar value of biobased content products to total dollar value of products included in project. Submit documentation indicating relative dollar value of rapidly renewable materials to total dollar value of products included in project.ThermostatsRefri