1、 *USACE / NAVFAC / AFCESA / NASA UFGS-28 31 33.13 20 (April 2006)-Preparing Activity: NAVFAC Replacing without change UFGS-13853N (August 2003)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION TABLE OF CONTENTSDIVISION 28 - ELECTRONIC SAFETY AND SEC

2、URITYSECTION 28 31 33.13 20EXTERIOR FIRE REPORTING SYSTEM, RADIO TYPE04/06PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.2.1 Continuity of Protection1.3 SYSTEM DESIGN1.4 SUBMITTALS1.5 DRAWINGS1.5.1 System Layout Drawings1.5.2 Wiring Diagrams1.5.3 Mounting Details1.6 ALARM SYSTEM POWER CALCULA

3、TIONS1.7 FIRE ALARM SYSTEM UL OR FM LISTING1.8 QUALIFICATIONS1.8.1 List of Prior Installations1.8.2 Manufacturers Technical Representative1.9 SYSTEM AS-BUILT DRAWINGS1.10 QUALITY ASSURANCE1.10.1 Qualifications of Installer1.10.2 Manufacturers Technical Representative1.10.3 Qualification of System Te

4、chnicianPART 2 PRODUCTS2.1 RADIO ALARM TRANSMITTERS2.1.1 Transmitter Identity Code2.1.2 Environmental Operating Requirements2.1.3 RF Power Output2.1.4 Memory2.1.5 Transmission Confirmation2.1.6 Automatic Test2.1.7 Battery Monitoring2.1.8 Inputs/Zone Connections2.1.8.1 Zone Annunciation2.1.8.2 Zone D

5、isconnecting MeansSECTION 28 31 33.13 20 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.1.8.3 Monitoring for Integrity2.1.9 Trouble Annunciator2.1.10 Transmitter Power Source2.1.11 Transmitter Enclosure2.1.11.1 Security2.1.12 Antennas and Ca

6、bles2.1.13 Lightning Protection2.1.14 Moisture Protection2.2 RADIO MASTER BOXES2.2.1 Signal Designations2.2.1.1 Tamper2.2.1.2 Fire2.2.1.3 Master2.2.1.4 Medical Emergency2.2.1.5 Police Emergency2.2.2 Housing (Enclosure)2.2.2.1 Operating Panel2.2.2.2 Interface Device for Master Box Radio Transmitters2

7、.3 RADIO STREET BOXES2.3.1 Signal Designations2.3.1.1 Tamper2.3.1.2 Fire2.3.1.3 Medical Emergency2.3.1.4 Police Emergency2.3.2 Power Source2.3.2.1 Photovoltaic Power System2.3.3 Housing (Enclosure)2.3.3.1 Operating Panel2.4 MANUAL FIRE ALARM BOXES2.5 BOX LOCATION LIGHT2.5.1 Box Location Marker (Non-

8、Electric)2.6 BASE STATION RECEIVING OR CONTROL EQUIPMENT2.6.1 Display2.6.2 Memory2.6.2.1 Memory Readout2.6.3 Digital Clock2.6.4 Printer2.6.5 Audible Annunciation2.6.6 Receivers2.6.7 Decoders2.6.8 Primary Power Source2.6.9 Emergency Power Source2.6.9.1 Emergency Power Switchover2.6.10 Network Battery

9、 Charger2.6.11 Monitoring for Network Integrity2.6.11.1 Receiver Monitoring for Integrity2.6.11.2 Power Monitoring for Integrity2.6.11.3 Meters2.6.12 Component Connections2.6.13 Protective Finish2.6.14 Base Station Receiving or Control Network Antennas2.6.15 Lightning Protection2.6.16 Field Programm

10、ing Capability2.7 COMPUTER-AIDED DISPATCH (CAD) SYSTEM2.7.1 Interconnection to Alarm System2.7.2 Monitor and Keyboard2.7.3 Printer2.7.4 Automatic Display2.7.5 Manual Alarm Entry CapabilitySECTION 28 31 33.13 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without licens

11、e from IHS-,-,-2.7.6 Unit Status Tracking Capability2.7.7 Pre-Incident Plan Retrieval2.7.8 Hazardous Materials Data Retrieval2.7.9 Power Source2.7.9.1 Uninterruptible Power Supply (UPS)2.8 INTERCONNECTION WITH EXISTING COMPUTER-AIDED DISPATCH (CAD) SYSTEM2.8.1 Interconnection to Alarm Reporting Syst

12、em2.9 SURGE SUPPRESSION2.10 RADIO ALARM TRANSMITTER BATTERY CONDITIONER2.10.1 Capacity2.10.2 Meter2.11 RADIO ALARM TRANSMITTER BATTERY LOAD TESTER2.12 SAFETY DISCONNECT SWITCH2.13 PROTECTED PREMISES CONTROL UNITS2.13.1 Fire Alarm Control Units2.13.2 Fire Suppression/Extinguishing System Control Unit

13、s2.13.3 Fire Pump Control Units2.14 DRY CONTACT INITIATING DEVICES2.14.1 Sprinkler Waterflow Alarm Initiating Devices2.14.2 Fire Extinguishing System Discharge Alarm Initiating Devices2.14.3 Valve Position Supervisory Initiating Devices2.14.4 Pressure Supervisory Initiating Devices2.14.5 Temperature

14、 Supervisory Signal Initiating Devices2.14.6 Water Level Supervisory Signal Initiating Devices2.15 CONDUIT2.15.1 Rigid Steel Conduit2.15.2 Intermediate Metal Conduit (IMC)2.15.3 Electrical Metallic Tubing (EMT)2.15.4 Surface Metal Raceway and Fittings2.16 OUTLET BOXES2.17 FITTINGS FOR CONDUIT AND OU

15、TLET BOXES2.18 WIRING2.19 GROUND RODS2.20 SPARE PARTSPART 3 EXECUTION3.1 RADIO FREQUENCY ASSIGNMENT3.2 INSTALLATION3.2.1 Conductor Identification3.2.2 Conduit Installation3.2.3 Additional Installation Requirements3.3 PROGRAMMING3.3.1 Programming Revisions During Preliminary Testing3.3.2 Programming

16、Revisions During the Final Acceptance Stage3.4 FIELD TESTING3.4.1 Tests During Installation3.4.2 Final Acceptance Test3.5 ADDITIONAL TESTS3.6 INSTRUCTION OF GOVERNMENT PERSONNEL3.6.1 Instruction of Operating Personnel3.6.2 Instruction of Maintenance Personnel3.6.3 Advanced Maintenance Training- End

17、of Section Table of Contents -SECTION 28 31 33.13 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 33.13 20 (April 2006)-Preparing Activity: NAVFAC Replacing without change UFGS-13853N (August 2003)U

18、NIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION 28 31 33.13 20EXTERIOR FIRE REPORTING SYSTEM, RADIO TYPE04/06*NOTE: This guide specification covers the requirements for a complete base-wide radio fire reporting system which provides reporting of fi

19、re alarms to a central processing location through the use of radio transmitters connected to various building interior fire alarm systems and optional manual exterior alarm transmitters “street boxes“.Edit this guide specification for project specific requirements by adding, deleting, or revising t

20、ext. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical

21、proponent of the specification. A listing of Technical Proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE: Interior building fire alarm systems are covered by Section

22、 28 31 74.00 20 INTERIOR FIRE DETECTION AND ALARM SYSTEM and by Section 28 31 63.00 20, ANALOG ADDRESSABLE INTERIOR FIRE ALARM SYSTEM.*NOTE: Close coordination by the designer with the EFD/EFA Fire Protection Engineer, the Federal Fire Chief, and facility fire alarm maintenance personnel is absolute

23、ly essential to achieving the goal of an SECTION 28 31 33.13 20 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-alarm reporting system that meets the needs of the customer.*NOTE: The following information shall be included in the contract drawi

24、ngs:1. Complete scale map(s) of the Government facility (or portion thereof) where the system is to be installed, showing building locations and numbers, roads and streets by name and/or number, and significant landmarks such as airfield runways, navigable water, etc. Such map(s) shall show the loca

25、tion of each transmitter to be installed, and location of existing equipment to be reconnected or removed under this contract.2. Individual building plans of sufficient detail and scale to clearly indicate locations of transmitters and of local alarm systems (“protected premises control units“ per N

26、FPA 72), fire extinguishing system control units, and individual initiating devices to be connected to radio alarm transmitters. Show points of connection to AC power for transmitter (and location light for outdoor master boxes and/or manual fire alarm boxes).3. Table(s) showing: each transmitter lo

27、cation; transmitter code number; the number of zones to be connected and their descriptions; and the make and model of local control unit(s) to be tied into the transmitter. (e.g.: Bldg. 591; transmitter # 0591, Zone 1 - FACU common alarm contact, Zone 2 - carbon dioxide control unit common alarm co

28、ntact, Zone 3 - fire pump running, Zone 4 - fire pump switch off normal, Zone 5 - fire pump trouble, Zone 6 - Spare; FACU is an XYZ Co. model ABC, carbon dioxide control unit is a UVW Co. model EFG, etc.).NOTE: WHEN INDICATING CONNECTIONS TO EXISTING CONTROL UNITS, DESIGNERS MUST DETERMINE THAT THER

29、E ARE DRY (Form A or Form C) CONTACTS AVAILABLE WITHIN THE CONTROL UNIT TO PERMIT THE CONNECTION. Designers must be aware that many older control units may lack the necessary contacts. If necessary to provide additional contacts, the designer must ascertain from the control unit manufacturer whether

30、 the necessary parts are available. In cases where the necessary contacts arent available, it will be necessary to indicate replacement of the control unit or other remedial action. 4. A complete layout of the fire/emergency communications center operations room or fire alarm watch office showing lo

31、cations of all new equipment, existing equipment that is to remain, and equipment to be removed. Show points of connection to power source(s).SECTION 28 31 33.13 20 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-5. Mounting details of the base

32、 station antennas, including structural design of antenna supporting towers if towers are required.*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only

33、and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feat

34、ure to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. T

35、he publications are referred to within the text by the basic designation only.FM GLOBAL (FM)FM APP GUIDE (updated on-line) Approval Guide http:/ OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)IEEE C62.11 (2005; Amd 1 2008) Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuit

36、s (1kV)IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power CircuitsIEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power CircuitsNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)ANSI C80

37、.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)SECTION 28 31 33.13 20 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)NEMA ICS 6 (19

38、93; R 2001; R 2006) EnclosuresNATIONAL FIRE PROTECTION ASSOCIATION (NFPA)NFPA 111 (2010) Standard on Stored Electrical Energy Emergency and Standby Power SystemsNFPA 12 (2008) Standard on Carbon Dioxide Extinguishing SystemsNFPA 1221 (2010) Standard for the Installation, Maintenance and Use of Emerg

39、ency Services Communications SystemsNFPA 12A (2009) Standard on Halon 1301 Fire Extinguishing SystemsNFPA 13 (2010; Errata 10-1) Standard for the Installation of Sprinkler SystemsNFPA 17 (2009) Standard for Dry Chemical Extinguishing SystemsNFPA 17A (2009; Errata 09-1) Standard for Wet Chemical Exti

40、nguishing SystemsNFPA 20 (2010; TIA 10-1) Standard for the Installation of Stationary Pumps for Fire ProtectionNFPA 2001 (2008) Standard on Clean Agent Fire Extinguishing SystemsNFPA 22 (2008) Standard for Water Tanks for Private Fire ProtectionNFPA 25 (2008) Standard for the Inspection, Testing, an

41、d Maintenance of Water-Based Fire Protection SystemsNFPA 70 (2008; TIA 08-1) National Electrical CodeNFPA 72 (2010; TIA 10-1; TIA 10-2; TIA 10-3; TIA 10-4) National Fire Alarm and Signaling CodeTELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)TIA-222-G (2005; Addenda 2007; Addenda 2009) Structural Stand

42、ards for Antenna Supporting Structures and AntennasU.S. FEDERAL HIGHWAY ADMINISTRATION (FHWA)MUTCD (2000) Manual of Uniform Traffic Control DevicesSECTION 28 31 33.13 20 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-U.S. GENERAL SERVICES ADMI

43、NISTRATION (GSA)FED-STD-595 (Rev C) Colors Used in Government ProcurementUNDERWRITERS LABORATORIES (UL)UL 1242 (2006; R 2001 thru 2007) Standard for Electrical Intermediate Metal Conduit - SteelUL 1449 (2006; R thru 2009) Surge Protective DevicesUL 346 (2005; R 2009) Waterflow Indicators for Fire Pr

44、otective Signaling SystemsUL 467 (2007) Grounding and Bonding EquipmentUL 497B (2004; R 2008) Protectors for Data Communication CircuitsUL 5 (2004; R thru 2009) Surface Metal Raceways and FittingsUL 514A (2004; R 2005 thru 2009) Metallic Outlet BoxesUL 514B (2004; R thru 2009) Conduit, Tubing and Ca

45、ble FittingsUL Fire Prot Dir (2010) Fire Protection Equipment Directory1.2 RELATED REQUIREMENTSMaterials and workmanship shall conform to Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, with the additions and modifications specified herein. Include provision of all labor, material, tools and