1、 (Note: For further information on NFPA Codes and Standards, please see www.nfpa.org/codelist) Copyright 2014 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION Tentative Interim Amendment NFPA70 National Electrical Code2014 Edition Reference: 530.21(A) TIA 14-5 (SC 14-8-17 / TIA Log #1152) Pu
2、rsuant to Section 5 of the NFPA Regulations Governing the Development of NFPA Standards, the National Fire Protection Association has issued the following Tentative Interim Amendment to NFPA 70, National Electrical Code, 2014 edition. The TIA was processed by the NEC Code-Making Panel 15 and the Nat
3、ional Electrical CodeCorrelating Committee, and was issued by the Standards Council on August 14, 2014, with an effective date of September 3, 2014. A Tentative Interim Amendment is tentative because it has not been processed through the entire standards-making procedures. It is interim because it i
4、s effective only between editions of the standard. A TIA automatically becomes a public input of the proponent for the next edition of the standard; as such, it then is subject to all of the procedures of the standards-making process. 1. Revise 530.21(A) to read as follows: 530.21 Plugs and Receptac
5、les. (A) Rating. Plugs and receptacles, including cord connectors and flanged surface devices, shall be rated in amperes. The voltage rating of the plugs and receptacles shall be not less than the nominal circuit voltage. Plug and receptacle ampere ratings for ac circuits shall not be less than the feeder or branch-circuit overcurrent device ampere rating. Table 210.21(B)(2) shall not apply. Section 406.15 shall not apply. Issue Date: August 14, 2014 Effective Date: September 3, 2014