1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences ForUL 60079-7Explosive atmospheres Part 7: Equipment protection by increased safety eUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PE
2、RMISSION FROM ULNational Differences ForUL 60079-7Explosive atmospheres Part 7: Equipment protection by increased safety eFifth EditionEdition Date: FEBRUARY 24, 2017Adoption of IEC 60079-7, Explosive Atmospheres - Part 7: Equipment Protection by IncreasedSafety e (fifth edition, issued by IEC June
3、2015) as a new IEC-based UL standard, UL 60079-7with US Differences.This document provides a single listing of the National Differences included in the UL adoption ofthe corresponding IEC standard.All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, ortra
4、nsmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwisewithout prior permission of UL.UL provides this standards document as is without warranty of any kind, either expressed or implied,including but not limited to, the implied warranties of merchantability or
5、 fitness for any purpose.In no event will UL be liable for any special, incidental, consequential, indirect or similar damages,including loss of profits, lost savings, loss of data, or any other damages arising out of the use of or theinability to use this standards document, even if UL or an author
6、ized UL representative has been advisedof the possibility of such damage. In no event shall ULs liability for any damage ever exceed the pricepaid for this standards document, regardless of the form of the claim.Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify,
7、 and hold ULharmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonableattorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronicStandard on the purchasers computer system.Copyright 2017 Underwriters Laborato
8、ries Inc.FEBRUARY 24, 2017NATIONAL DIFFERENCES FOR UL 60079-72UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPrefaceThis document provides a single listing of the technical National Differences included in the UL adoptionof the corresponding
9、IEC standard.In its IEC-based standards, UL uses the notations indicated below to identify national difference type, andthese types are additionally noted in this document. The standard may not use all types of thesedeviations.D1 - These are deviations which are based on basic safety principles and
10、requirements, elimination ofwhich would compromise safety for U.S. consumers and users of products.D2 - These are deviations based on safety practices. These are deviations for IEC requirements that maybe acceptable, but adopting the IEC requirements would require considerable retesting or redesign
11、on themanufacturers part.DC - These are deviations based on the component standards and will not be deleted until a particularcomponent standard is harmonized with the IEC component standard.DE - These are deviations based on editorial comments or corrections.DR - These are deviations based on the n
12、ational regulatory requirements.Each national difference contains a description of what the national difference entails. Typically one of thefollowing words is used to explain how the text of the national difference is to be applied to the base IECtext:Addition / Add - An addition entails adding a c
13、omplete new numbered clause, subclause, table, figure,or annex. Addition is not meant to include adding select words to the base IEC text.Deletion / Delete - A deletion entails complete deletion of an entire numbered clause, subclause, table,figure, or annex without any replacement text.Modification
14、 / Modify - A modification is an altering of the existing base IEC text such as the addition,replacement or deletion of certain words or the replacement of an entire clause, subclause, table, figure,or annex of the base IEC text.FEBRUARY 24, 2017 NATIONAL DIFFERENCES FOR UL 60079-7 3UL COPYRIGHTED M
15、ATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences1DV.1 DR Modification of Clause 1, first paragraph to replace with the following:1DV.1.1 This part of IEC 60079 standard specifies the requirements for the design,construction, testing and ma
16、rking of electrical equipment and Ex Components with type ofprotection increased safety “e” intended for use in explosive gas atmospheres.1DV.2 DR Modification of Clause 1, eighth paragraph to replace with the following:1DV.2.1 This standard supplements and modifies the general requirements of IEC 6
17、0079-0UL 60079-0. Where a requirement of this standard conflicts with a requirement of IEC60079-0 UL 60079-0, the requirement of this standard takes precedence.1DV.3 DR Addition of 1DV.3.1Where references are made to other IEC 60079 standards, the referenced requirementsfound in these standards appl
18、y as modified by any applicable U.S. National Differences.2DV DR Modification of Clause 2 references to replace with the following:ANSI C78.1, Fluorescent Lamps Rapid Start Types Dimensional and Electrical CharacteristicsANSI C81.61, Electric Lamp BasesANSI C81.62, Lampholders for BasesANSI /NFPA 70
19、, National Electrical Code (NEC)IEC 60034-1, Rotating electrical machines Part 1: Rating and performanceIEC 60034-29, Rotating electrical machines Part 29: Equivalent loading and superpositiontechniques indirect loading to determine temperature riseIEC 60044-6, Instrument transformers Part 6: Requir
20、ements for protective current transformersfor transient performanceIEC 60061-1, Lamp caps and holders together with gauges for the control of interchangeabilityand safety. Part 1: Lamp capsIEC 60061-2, Lamp caps and holders together with gauges for the control of interchangeabilityand safety Part 2:
21、 LampholdersIEC 60064, Tungsten filament lamps for domestic and similar general lighting purposes Performance requirementsIEC 60068-2-6, Environmental testing Part 2-6: Tests Test Fc: Vibration (sinusoidal)IEC 60068-2-27:2008, Environmental testing Part 2-27: Tests Test Ea and guidance: ShockFEBRUAR
22、Y 24, 2017NATIONAL DIFFERENCES FOR UL 60079-74UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULIEC 60068-2-42, Environmental testing Part 2-42: Tests Test Kc: Sulphur dioxide test forcontacts and connectionsIEC 60079-0, Explosive atmospheres Pa
23、rt 0: Equipment General requirementsIEC 60079-1, Explosive atmospheres Part 1: Equipment protection by flameproof enclosures dIEC 60079-11, Explosive atmospheres Part 11: Equipment protection by intrinsic safety iIEC 60079-30-1, Explosive atmospheres Part 30-1: Electrical resistance trace heating Ge
24、neraland testing requirementsIEC/IEEE 60079-30-1, Explosive atmospheres Part 30-1: Electrical resistance trace heating General and testing requirementsIEC 60081, Double-Capped Fluorescent Lamps Performance SpecificationIEC 60085, Electrical insulation Thermal evaluation and designationIEC 60112, Met
25、hod for the determination of the proof and the comparative tracking indices of solidinsulating materialsIEC 60216-1, Electrical insulating materials Thermal endurance properties Part 1: Ageingprocedures and evaluation of test resultsIEC 60216-2, Electrical insulating materials Thermal endurance prop
26、erties Part 2:Determination of thermal endurance properties of electrical insulating materials Choice of testcriteriaIEC 60228, Conductors of insulated cablesIEC 60238, Edison screw lampholdersIEC 60317-3:2004, Specifications for particular types of winding wires Part 3: Polyesterenamelled round cop
27、per wire, class 155IEC 60317-3:2004/AMD1:2010IEC 60317-8, Specifications for particular types of winding wires Part 8: Polyesterimideenamelled round copper wire, class 180IEC 60317-13, Specifications for particular types of winding wires Part 13: Polyester orpolyesterimide overcoated with polyamide-
28、imide enamelled round copper wire, class 200IEC 60317-46, Specifications for particular types of winding wires Part 46: Aromatic polyimideenamelled round copper wire, class 240IEC 60400, Lampholders for tubular fluorescent lamps and starterholdersIEC 60432-1, Incandescent lamps Safety specifications
29、 Part 1: Tungsten filament lamps fordomestic and similar general lighting purposesFEBRUARY 24, 2017 NATIONAL DIFFERENCES FOR UL 60079-7 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULIEC 60432-2, Incandescent lamps Safety specifications Part
30、 2: Tungsten halogen lamps fordomestic and similar general lighting purposesIEC 60432-3, Incandescent lamps Safety specifications Part 3: Tungsten halogen lamps(non-vehicle)IEC 60529, Degrees of protection provided by enclosures (IP Code)IEC 60598-1, Luminaires Part 1: General requirements and tests
31、IEC 60664-1, Insulation coordination for equipment within low-voltage systems Part 1:Principles, requirements and testsIEC 60947-1, Low-voltage switchgear and controlgear Part 1: General rulesIEC 60947-7-1, Low-voltage switchgear and controlgear Part 7-1: Ancillary equipment Terminal blocks for copp
32、er conductorsIEC 60947-7-2, Low-voltage switchgear and controlgear Part 7-2: Ancillary equipment Protective conductor terminal blocks for copper conductorsIEC 60947-7-4, Low-voltage switchgear and controlgear Part 7-4: Ancillary equipment PCBterminal blocks for copper conductorsIEC 60998-2-4, Connec
33、ting devices for low-voltage circuits for household and similar purposes Part 2-4: Particular requirements for twist-on connecting devicesIEC 60999-1, Connecting devices Electrical copper conductors Safety requirements forscrew-type and screwless-type clamping units Part 1: General requirements and
34、particularrequirements for clamping units for conductors from 0,2 mm2up to 35 mm2(included)IEC 60999-2, Connecting devices Electrical copper conductors Safety requirements forscrew-type and screwless-type clamping units Part 2: Particular requirements for clamping unitsfor conductors above 35 mm2up
35、to 300 mm2(included)IEC 61184, Bayonet lampholdersIEC 61195, Double-capped fluorescent lamps Safety specificationsIEC 61347-1, Lamp controlgear Part 1: General and safety requirementsIEC 61347-2-3, Lamp control gear Part 2-3: Particular requirements for a.c. and/or d.c. suppliedelectronic control ge
36、ar for fluorescent lampsIEC 62035, Discharge lamps (excluding fluorescent lamps) Safety specificationsISO 2859-1, Sampling procedures for inspection by attributes Part 1: Sampling schemesindexed by acceptance quality limit (AQL) for lot-by-lot inspectionISO 527-2, Plastics Determination of tensile p
37、roperties Part 2: Test conditions for mouldingand extrusion plasticsISO 178, Plastics Determination of flexural propertiesFEBRUARY 24, 2017NATIONAL DIFFERENCES FOR UL 60079-76UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL 486E Equipment Wi
38、ring Terminal for Use with Aluminum and/or Copper ConductorsUL 508 Industrial Control EquipmentUL 746A Polymeric Materials Short Term Property EvaluationsUL 746B Polymeric Materials Long Term Property EvaluationsUL 840 Insulation Coordination Including Clearances and Creepage Distances for Electrica
39、lEquipmentUL 844 Luminaires for Use in Hazardous (Classified) LocationsUL 1059 Terminal BlocksUL 1598 LuminairesUL 2238 Cable Assemblies and Fittings for Industrial Control and Signal DistributionUL 2237 Multi-Point Interconnection Power Cable Assemblies for Industrial MachineryUL 8750 Light Emittin
40、g Diode (LED) Equipment for Use in Lighting ProductsUL 60079-0 Explosive Atmospheres Part 0: Equipment General RequirementsUL 60079-1 Explosive Atmospheres Part 1: Equipment Protection by Flameproof EnclosuresdUL 60079-11 Explosive Atmospheres Part 11: Equipment Protection by Intrinsic Safety iUL 60
41、079-15 Explosive Atmospheres Part 15: Construction, Test and Marking of Type ofProtection n Electrical ApparatusUL 60947-1 Low Voltage Switchgear and Controlgear Part 1: General RulesUL 60947-7-1 Low Voltage Switchgear and Controlgear Part 7-1: Ancillary Equipment Terminal Blocks for Copper Conducto
42、rsUL 60947-7-2 Low Voltage Switchgear and Controlgear Part 7-2: Ancillary Equipment Protective Conductors Terminal Blocks for Copper ConductorsUL 60947-7-4 Low Voltage Switchgear and Controlgear Part 7-4: Ancillary Equipment PCBTerminal Blocks for Copper Conductors3DV DR Modification of Clause 3 to
43、replace with the following:For the purposes of this document standard, the terms and definitions given in IEC 60079-0UL 60079-0, as well as the following apply.NOTE For the definitions of any other terms, particularly those of a more general nature, please refer to IEC60050-426 or other appropriate
44、parts of IEC 60050, International Electrotechnical Vocabulary.FEBRUARY 24, 2017 NATIONAL DIFFERENCES FOR UL 60079-7 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3.13.1DV DR Modification of Clause 3.13.1, Note 1 to replace with the followin
45、g:Note 1 to entry: Electric trace heating systems are addressed by IEC/IEEE 60079-30-1 or IEC/IEEE 60079-30-1 orIEEE 515.3.13.2DV DR Modification of Clause 3.13.2, to Add Note 2 as follows:Note 2 to entry: Where references are made to a resistance heating device, the reference is intended to be read
46、as resistance heating equipment to align with the NEC definitions of device and equipment.3.19DV DR Modification of Clause 3.19, Note 1 to replace with the following:Note 1 to entry: For additional information on trace heaters, see IEC/IEEE 60079-30-1.4.1DV DR Modification of Clause 4.1 to replace w
47、ith the following:Electrical equipment with Type of Protection increased safety “e” shall be one of thefollowing: Level of Protection “eb” (EPL “Mb” or “Gb”); or Level of Protection “ec” (EPL “Gc”).The requirements of this clause apply, unless otherwise stated in Clause 5, to all electricalequipment
48、 and Ex Components with Type of Protection “e”.Equipment evaluated as Level of Protection “ec” may include manually operated arcing orsparking components located within an enclosure that have been considered to be notaccessible in normal operation without the use of a tool (see fastener general requ
49、irementsof UL 60079-0. The function of these components and their location in an enclosure asnoted above shall be specifically identified in the schedule documents prepared inaccordance with the documentation requirements of UL 60079-0.FEBRUARY 24, 2017NATIONAL DIFFERENCES FOR UL 60079-78UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4.2.1DV.1