1、11-11 13 17 23 - 1 SECTION 13 17 23 THERAPEUTIC POOLS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION Therapeutic pool equipment, including filtering

2、, heating, circulating, and sterilizing components as designated in this section. 1.2 RELATED WORK A. Section 01 00 00, GENERAL REQUIREMENTS: Requirements for pre-test of equipment. B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Seismic requirements for non-struct

3、ural equipment. C. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING: General mechanical requirements and items, which are common to more than one section of Division 22. D. Section 22 11 23, DOMESTIC WATER PUMPS and Section 22 14 29, SUMP PUMPS: Requirements for circulating pumps, sump pumps. E. S

4、ection 23 07 11, HVAC, PLUMBING, AND BOILER PLANT INSULATION: Requirements for pipe insulation. F. Section 22 05 19, METERS AND GAGES FOR PLUMBING PIPING and Section 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING: For copper tubing valves and gages. G. Section 22 33 00, ELECTRIC DOMESTIC WATER HE

5、ATERS: For semi instantaneous water heaters. 1.3 QUALITY ASSURANCE Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING, which includes welding qualifications. 1.4 SUBMITTALS A. Submit in accordance with specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literat

6、ure and Data: 1. Pool Inlets 2. Pool Drain 3. Filter System 4. Sight Glasses 5. Float Tank 6. Float Control and Valve Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 2 7. Rate of Flow Indicator 8. Hypochlorinator 9. Ozone Generator 1

7、0. Hair and Lint Interceptor 11. Vacuum Cleaning Tool 12. Vacuum Cleaning Fittings 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are listed in the text by the basic designation only. B. American Society of Me

8、chanical Engineers (ASME): B1.20.1-83(R2006) Pipe Threads, General Purpose B16.5-09 . Pipe Flanges and Flanged Fittings B16.9-07 . Factory-Made Wrought Steel Butt welding Fittings B16.11-09 Forged Fittings, Socket-Welding and Threaded B16.23-06 Cast Copper Alloy Solder Joint Drainage Fittings B16.24

9、-01(R2006) . Cast Copper Alloy Pipe Flanges and Flanged Fittings C. American Society for Testing and Materials (ASTM): A47/A47M-99(R2009) . Ferritic Malleable Iron Castings B32-08 Solder Metal B61-08 Steam or Valve Bronze Castings B62-09 Composition Bronze or Ounce Metal Castings F439-09 . Socket-Ty

10、pe Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 F441/F441M-09 . Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe, Schedules 40 and 80 D. American Welding Society (AWS): A5.1/A5.1M-04 Filler Metals for Brazing E. Manufacturers Standardization Society (MSS) of the V

11、alve and Fitting Industry, Inc.: SP-80-08 . Bronze Gate, Globe, Angle and Check Valves PART 2 - PRODUCTS 2.1 POOL INLETS Nozzle-type with adjustable plastic jet head and regulating shutter in strainer plate to control flow. Shall have cast brass body, with anchor flange and all exposed parts nickel

12、bronze. 2.2 POOL DRAINS A. Gutter Drains: Cast brass body with chromium plated polished brass strainer or PVC approximately 64 by 95 mm (2-1/2 by 3-3/4 inches). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 3 B. Outlet Drains: Cast

13、 Iron body or PVC with adjustable anti-vortex cover of chromium plated brass or stainless steel or PVC not less than 300 mm (12 inches) in diameter. SPEC WRITER NOTE: No cartridge filters should be utilized only when State Department of Health Codes require, otherwise, should sand filters be utilize

14、d. 2.3 FILTER AND JET SYSTEM A. Vertical pressure type or vacuum type utilizing diatomaceous earth as filtering medium, equipped with pre-coat tank, continuous body feed tank, and all necessary valves, gages, piping and accessories. Filters plant, when handling water from the pool at the rate of _m/

15、L (_gpm) shall deliver filtrate, free from color, turbidity, or matter in suspension. B. Filter Elements: Shall consist of a battery of elements having a total free unobstructed filter area of not less than _ square meters (_square feet). Filtering medium shall be deposited on elements constructed o

16、f stainless steel or stone. Elements shall be easily removable for cleaning when necessary. Head and tail-pieces shall be bronze. C. Pressure Type Filter: Filter elements shall be contained in filter shells fabricated of high grade tank steel with corrosion-resisting interior finish, riveted or weld

17、ed, designed for a working pressure of 410 kPa (60 psig). Shells shall be tested before shipment under a hydrostatic pressure of 690 kPa (100 psig) and shall show no sign of leakage. Top heads shall be easily removable to give access to elements. Shells shall be securely supported by legs and shall

18、have all necessary openings for pipes properly reinforced. D. Vacuum Type Filter: Tank shall be open type made completely of glass fiber reinforced plastic and externally braced with galvanized steel. Elements shall have suitable porosity and permeability so that after pre-coating initial pressure l

19、oss will be less than 3400 Pa (1 inch mercury). Filter elements shall be glass fiber reinforced plastic with mono-filament plastic sleeves, or corrosion-resisting metal, mounted vertically, and connected to a closed underdrain manifold leading to pump suction. Elements shall be easily and individual

20、ly removable and not require tie rods for assembly. Provide filter battery with a vacuum limit switch to stop circulating pump at a predetermined point before reaching maximum possible suction lift. E. Vacuum Type Filter Level Control Valve: Modulating type float valve installed in filter inlet line

21、 with float operator installed in filter Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 4 tank to insure no overflowing of filter tank. Valve shall be a butterfly type with diaphragm operator and be controlled by a pilot float valve

22、 in filter tank. Level control shall be fail-safe type. F. Pre-coat Tank: Steel, having a capacity of not less than 4.5 kg (10 pounds) of filtering medium. Assemble into inlet piping. G. Continuous Feed Tank (Slurry Tank): Continuous motor agitated feed tank of sufficient size for filter battery. H.

23、 Jets shall be adjustable / directional and multi-functional jets formed of thermoplastic co-extrusion of PVC so as not to cause corrosive action with pool shell. Jets shall be pumped and plumbed through manufacturers standard dual pump system. Jets for the therapy pool shall include (2) front resis

24、tance/therapy jets, (1) 5 attachable therapy hose for deep tissue massage. These jets are controlled with a variable frequency drive and cannot be driven with pneumatic controls appropriately. Laminar flow or paddle wheel systems are not to be accepted as adequate replacements for the adjustable mul

25、ti-directional jet system. 2.4 SIGHT GLASSES Shall be manufacturers standard. Vane shall extend into pipe to deflect a continuous stream of water into and through the glass. Sight glass shall have blow-off cock. 2.5 FLOAT TANK OR POOL VESSEL A. Constructed of steel or thermoplastic with reinforced f

26、iberglass backing. Steel is welded construction, open top, galvanized after fabrication. B. Openings: Sizes shown and properly reinforced with flanges welded to tank and threaded for screwed pipe connections, or may have extra heavy couplings welded to tank both inside and outside. C. Support: Iron

27、or steel stand or chair or other type suitable for tank furnished. D. Tank size: Tank size shall be 7-6” x 14 x 5 deep containing a volume of 2,250 total gallon capacity. 2.6 FLOW METER Meter shall be capable of operating at 52 degrees C (125 degrees F) and 410 kPa (60 psig). Scale shall be calibrat

28、ed in L/min (gpm) and shall be suitable for the flow delivery. 2.7 HYPOCHLORINATOR OR BROMINATOR A. Automatically controlled of sufficient capacity to produce residual chlorine or bromine content in pool water, at any point in pool, of between 0.40 and 0.60 mg/L (ppm). Hypochlorinator shall be insta

29、lled complete with suction hose, strainer assembly at end of suction hose, Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 5 sight feed indicator, two hypochlorite solution tanks of sufficient size, and all other necessary accessorie

30、s. B. Furnish one orthotolidin comparator having a standard color disc with a range from 0.05 to 1.00 mg/L (ppm), arranged in nine steps and equipped with a dust-proof eyepiece, fitted with a glass prism which will bring image of treated sample and color standard side by side to facilitate quick and

31、 accurate reading. 2.8 OZONE GENERATOR Automatically controlled non-arc, conforming to OSHA Standards and shall be suitable for wall mounting. Components shall be Underwriters Laboratories labeled. Replacement ozone cartridge cells shall have a minimum life of 6,000 hours. 2.9 HAIR AND LINT INTERCEP

32、TOR Install in suction line of circulating pump, a duplex strainer with heavy cast iron body or PVC body, flanged inlet and outlet with IPS standard interceptors, removable brass or stainless steel or PVC perforated basket strainers, gasketed water-tight covers secured with bolted yoke arrangement,

33、install valves to allow off-stream basket to be removed for cleaning with continuous flow through the other strainer. Strainer size shall be based on a flow rate of 125 percent of circulating pump L/min (gpm), with maximum pressure drop of 45 kPa (15 feet). Floating weir systems made of PVC material

34、 and telescoping skimmer body are also acceptable alternatives. 2.10 VACUUM CLEANING TOOL “Tow Type“ vacuum cleaning tool complete with 375 mm (15 inch sweep), renewable bristle brush, with handle and swivel tee connection and solid rubber or rubber-tired wheels, extension handles and 15 m (50 feet)

35、 of vacuum hose with couplings at each end and any other accessories necessary for cleaning pool. Provide six copper floats, with clamps, for hose. Handheld vacuum model with manual suction stimulation is acceptable alternative. 2.11 VACUUM CLEANING FITTING If “tow type” vacuum, Shall have cast iron

36、 body, with polished brass, chromium plated, adjustable vacuum connection with approved type cover. 2.12 POOL HEATRES Refer to specification Section 22 33 00, ELECTRIC DOMESTIC WATER HEATERS, for semi instantaneous water heaters. 2.13 COMPUTER DOCUMENTATION SYSTEM AND REMOTE CONTROL OPERATIONS A. Co

37、ntrol system, which was custom designed, utilizes a fully integrated control system. This system is based around an industry standard PLC Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 6 (Programmable Logic Controller) which monitor

38、s pool conditions through various sensors. The PLC also communicates with the Operator/Trainer via the infrared remote control, the maintenance pendant, and Windows-based software running on a personal computer. The software monitors the pool functions, treadmill speed, and jet power via RS-232 comm

39、unications with the PLC, and then uses this information to display current session information, and store the information in a patient database for future reference, and progress reports. B. Control system shall include water-resistant remote control unit, which can control jet action, treadmill flo

40、or action. Additional controls shall include manual controls for the previously listed items, thermostatic control of water temperature, filtration system controls, and all other pertinent controls for a complete working system. C. Pool electronic patient monitoring systems shall include Pentium PC

41、complete with monitor, tower, mouse, surge protector, and keyboard, two fixed underwater cameras, camera switching device, 25 viewing monitor, VCR, and appropriate software and licensing agreements. 2.14 PIPING AND DRAINS A. Piping shall be PVC schedule 40 piping from each drain with shutoff valve a

42、s required and down turn to existing adjacent sump pit drain. Water supply piping shall not be ferrous metals to prevent corrosion and water chemistry issues. B. Pool drain: Install and connect pool drain from the pool to the designated location in the sump pit. Refer to Section 22 14 29, SUMP PUMPS

43、. PART 3 - EXECUTION 3.1 INSTALLATION A. Install therapeutic pool equipment as per manufacturers instruction and under the supervision of manufacturers qualified representative and as shown on drawings. B. Caulk watertight pool inlets. C. Install flow meter on filtered water supply pipe to pool. D.

44、Install sight glass as required per manufacturers instructions. E. Installation and activation of chlorinator shall be under direct supervision of a qualified representative of manufacturer of apparatus. 3.2 INSTRUCTION AND PERSONNEL TRAINING One 8 hour day of pool and water chemistry training shall

45、 be provided to the facility maintenance personnel to educate the user on how to maintain the pool and properly care for the pool water. Addition Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 17 23 - 7 training shall be provided for the ph

46、ysical therapists, doctors and athletic trainers on water therapy and conditioning techniques. 3.3 TEST Conduct performance test, in the presence of the Resident Engineer and a manufacturers field representative, to show that all therapeutic pool equipment and control devices operate properly and in accordance with design and specification requirements. - - - E N D - - - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
  • ETSI PRI-ETS 300 170-1992 Private Telecommunications Network (PTN) Inter-Exchange Signalling Data Link Layer Protocol《专用通信网(PTN) 内部交换信令的数据链接层协议》.pdf ETSI PRI-ETS 300 170-1992 Private Telecommunications Network (PTN) Inter-Exchange Signalling Data Link Layer Protocol《专用通信网(PTN) 内部交换信令的数据链接层协议》.pdf
  • ETSI PRI-ETS 300 176-1991 Radio Equipment and Systems Digital European Cordless Telecommunications Approval Test Specification (DI RES 3002)《无线电设备和系统的欧洲数字无绳通信设备的鉴定测试规范(DI RES 3002).pdf ETSI PRI-ETS 300 176-1991 Radio Equipment and Systems Digital European Cordless Telecommunications Approval Test Specification (DI RES 3002)《无线电设备和系统的欧洲数字无绳通信设备的鉴定测试规范(DI RES 3002).pdf
  • ETSI PRI-ETS 300 176-1992 Radio Equipment and Systems (RES) Digital European Cordless Telecommunications (DECT) Approval Test Specification《无线电设备和系统(RES) 欧洲数字增强无绳通信(DECT)的鉴定测试规范》.pdf ETSI PRI-ETS 300 176-1992 Radio Equipment and Systems (RES) Digital European Cordless Telecommunications (DECT) Approval Test Specification《无线电设备和系统(RES) 欧洲数字增强无绳通信(DECT)的鉴定测试规范》.pdf
  • ETSI PRI-ETS 300 220-1992 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to be Used in the 25 MHz to 1000 MHz .pdf ETSI PRI-ETS 300 220-1992 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to be Used in the 25 MHz to 1000 MHz .pdf
  • ETSI PRI-ETS 300 220-1992 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to be Used in the 25 MHz to 1000 MHz _1.pdf ETSI PRI-ETS 300 220-1992 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to be Used in the 25 MHz to 1000 MHz _1.pdf
  • ETSI PRI-ETS 300 220-1993 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to Be Used in the 25 MHz to 1 000 MHz to.pdf ETSI PRI-ETS 300 220-1993 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to Be Used in the 25 MHz to 1 000 MHz to.pdf
  • ETSI PRI-ETS 300 220-1993 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to Be Used in the 25 MHz to 1 000 MHz.pdf ETSI PRI-ETS 300 220-1993 Radio Equipment and Systems (RES) Short Range Devices Technical Characteristics and Test Methods for Radio Equipment to Be Used in the 25 MHz to 1 000 MHz.pdf
  • ETSI PRI-ETS 300 226-1992 Transmission and Multiplexing (TM) Single-Mode Optical Fibre Cables to Be Used in Ducts and for Directly Buried Application《传输和多路转换(TM) 用于管道内和直埋应用中的单模光缆》.pdf ETSI PRI-ETS 300 226-1992 Transmission and Multiplexing (TM) Single-Mode Optical Fibre Cables to Be Used in Ducts and for Directly Buried Application《传输和多路转换(TM) 用于管道内和直埋应用中的单模光缆》.pdf
  • ETSI PRI-ETS 300 226-1993 Transmission and Multiplexing (TM) Single-Mode Optical Fibre Cables to Be Used in Ducts and for Directly Buried Application《传输和多路转换(TM) 用于管道内和直埋应用中的单模光缆》.pdf ETSI PRI-ETS 300 226-1993 Transmission and Multiplexing (TM) Single-Mode Optical Fibre Cables to Be Used in Ducts and for Directly Buried Application《传输和多路转换(TM) 用于管道内和直埋应用中的单模光缆》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1