1、Page 1 of 1 2016 ASHRAE. All Rights reserved. Interpretation IC 170-2013-8 of ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of Health Care Facilities Date Approved: January 26, 2016 Request from: Mark Tome, CESI, 2209 Chestnut Road, York, PA 17408. Reference: This request for interpretation refers

2、to the requirements in ANSI/ASHRAE/ASHE Standard 170-2013, Section 7.4.1, regarding the location of return and exhaust grilles in Class B and C operating rooms. Background: The last two paragraphs of Section 7.4.1 describe the placement of return/exhaust grilles as follows: “The room shall be provid

3、ed with at least two low side-wall return or exhaust grilles spaced at opposite corners or as far apart as possible, with the bottom of these grilles installed approximately 8in. (203mm) above the floor. Exception: In addition to the required low return (or exhaust) air grilles, such grilles may be

4、placed high on the walls.” Interpretation: Since these two paragraphs do not mention locations other than walls, return or exhaust registers in the ceiling (or floor) are not permitted in Class B and C operating rooms. Question: Is this interpretation correct? Answer: No. Comments: The main return/exhaust grilles are intended to be located in the wall, not the ceiling. Other secondary exhaust grilles (e.g. smoke, anesthesia) could perhaps be located in the ceiling.