ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf

上传人:visitstep340 文档编号:460531 上传时间:2018-11-25 格式:PDF 页数:5 大小:90.83KB
下载 相关 举报
ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf_第1页
第1页 / 共5页
ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf_第2页
第2页 / 共5页
ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf_第3页
第3页 / 共5页
ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf_第4页
第4页 / 共5页
ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: B174 10Standard Specification forBunch-Stranded Copper Conductors for ElectricalConductors1This standard is issued under the fixed designation B174; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revi

2、sion. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers bare bunch-stranded

3、conduc-tors made from round copper wires, either uncoated or coatedwith tin, lead, or lead-alloy for use as electrical conductors(Explanatory Note 1 and Explanatory Note 2).1.2 Coated wires shall include only those wires with fin-ished diameters and densities substantially equal to the respec-tive d

4、iameters and densities of uncoated wires.1.3 The values stated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two s

5、ystems may result in non-conformancewith the standard.1.3.1 For conductor sizes designated by AWG or kcmil, therequirements in SI units have been numerically converted fromcorresponding values, stated or derived, in inch-pound units.For conductor sizes designated by SI units only, the require-ments

6、are stated or derived in SI units.2. Referenced Documents2.1 The following documents of the issue in effect at thetime of reference form a part of this specification to the extentreferenced herein:2.2 ASTM Standards:2B3 Specification for Soft or Annealed Copper WireB33 Specification for Tin-Coated S

7、oft or Annealed CopperWire for Electrical PurposesB172 Specification for Rope-Lay-Stranded Copper Con-ductors Having Bunch-Stranded Members, for ElectricalConductorsB189 Specification for Lead-Coated and Lead-Alloy-Coated Soft Copper Wire for Electrical PurposesB193 Test Method for Resistivity of El

8、ectrical ConductorMaterialsB263 Test Method for Determination of Cross-SectionalArea of Stranded ConductorsB354 Terminology Relating to Uninsulated Metallic Elec-trical Conductors2.3 American National Standard:ANSI C42.35 Definitions of Electrical Terms33. Classification3.1 For the purpose of this s

9、pecification bunch-strandedconductors are classified as shown in Tables 1 and 2.4. Ordering Information4.1 Orders for material under this specification shall includethe following information:4.1.1 Quantity of each size and class,4.1.2 Conductor size: circular-mil area or AWG (see 7.1),4.1.3 Class (S

10、ection 3 and Table 3),4.1.4 Whether coated or uncoated; if coated, designate typeof coating (see 11.1),4.1.5 Maximum length of lay (see 6.3),4.1.6 Whether separator is required (see 7.2),4.1.7 Package size (see section 15.1),4.1.8 Special package marking, if required (Section 14), and4.1.9 Place of

11、inspection (Section 13).5. Joints5.1 Necessary joints in wires shall be made in accordancewith accepted commercial practice.5.2 Joints shall be so constructed and so disposed through-out the conductor that the diameter or configuration of thecompleted conductor is not substantially affected, and so

12、thatthe flexibility of the completed conductor is not adverselyaffected.1This specification is under the jurisdiction of ASTM Committee B01 onElectrical Conductors and is the direct responsibility of Subcommittee B01.04 onConductors of Copper and Copper Alloys.Current edition approved April 1, 2010.

13、 Published May 2010. Originallyapproved in 1941. Last previous edition approved in 2002 as B174 02 (2007)1.DOI: 10.1520/B0174-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume informati

14、on, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, Unit

15、ed States.6. Lay6.1 Conductors of the same size and description furnishedon one order shall have the same lay.6.2 The direction of lay shall be at the option of themanufacturer unless otherwise specified.TABLE 1 A Classification and Construction Requirements of Bunch-Stranded ConductorsAClass I Bunc

16、h Stranded ConductorsArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass INominalWire Diameter0.0201 In.(0.511 mm)Nominal dcresistance20CMaximum dcresistance20CNominal dcresistance20CMaximum dcresistance20CNominal dcresistance20CMaximum dcresist

17、ance20CNominal dcresistance20CMaximum dcresistance20Ccmil mm 24 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km20820 10.5 7 52 0.508 0.518 1.67 1.70 0.528 0.539 1.73 1.7716510 8.37 8 41 0.641 0.654 2.10 2.14 0.666 0.679 2.19 2.2313090 6.63 9 33 0.808 0.824 2.65 2.70 0.840 0.857 2.76

18、2.8110380 5.26 10 26 1.02 1.04 3.34 3.41 1.06 1.08 3.48 3.55TABLE 1 B Classification and Construction Requirements of Bunch-Stranded ConductorsClass J Bunch Stranded ConductorsAArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass JNominalWireDiam

19、eter0.0126 In.(0.320 mm)Nominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20Ccmil mm 28 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km10380 5.26 10 65 1.02 1.04

20、 3.34 3.41 1.08 1.10 3.54 3.616530 3.31 12 41 1.62 1.65 5.31 5.42 1.72 1.75 5.64 5.764110 2.08 14 26 2.57 2.62 8.44 8.61 2.73 2.79 8.96 9.142580 1.31 16 16 4.10 4.18 13.5 13.7 4.35 4.44 14.3 14.61620 0.821 18 10 6.53 6.66 21.4 21.9 6.94 7.07 22.8 23.21020 0.517 20 7 10.4 10.6 34.0 34.7 11.0 11.2 36.

21、1 36.8TABLE 1 C Classification and Construction Requirements of Bunch-Stranded ConductorsClass K Bunch Stranded ConductorsAArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass KNominalWireDiameter0.0100 In.(0.254 mm)Nominaldcresistance20CMaximumd

22、cresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20Ccmil mm 30 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km10380 5.26 10 104 1.02 1.04 3.35 3.41 1.09 1.12 3.58 3.656530 3.31 12 65 1.62 1.

23、65 5.31 5.42 1.74 1.77 5.71 5.824110 2.08 14 41 2.57 2.62 8.43 8.60 2.76 2.82 9.06 9.242580 1.31 16 26 4.10 4.18 13.5 13.7 4.40 4.49 14.4 14.71620 0.821 18 16 6.53 6.66 21.4 21.9 7.01 7.15 23.0 23.51020 0.517 20 10B10.4 10.6 34.1 34.8 11.1 11.4 36.4 37.1640 0.324 22 7 16.5 16.9 54.1 55.2 17.7 18.1 5

24、8.1 59.2AThe constructions shown in these tables are typical of those used in the industry. It is intended that these tables preclude other constructions which may be desirablefor specific applications. The constructions shown provide for a finished stranded conductor approximately of the area indic

25、ated. When specified by the purchaser, thenumber or sizes of wire may be increased to provide additional area to compensate for draw-down during subsequent processing.BAs an alternate to the construction shown for 20 AWG, Class K; for hook-up wire construction may consist of 8 wires 0.0100 in. (0.25

26、4 mm) diameter around wire of0.0142 in. (0.361 mm) diameter.B174 1026.3 Unless otherwise specified by the purchaser, the lengthof lay of bare or coated bunch-stranded conductors shallconform to the requirements of Column B of Table 3.6.4 When specified, for constructions other than those listedin Fo

27、otnote A of Tables 1 and 2, the length of lay shall conformto the requirements of Column A of Table 3.6.5 Conductors of an intermediate nominal area in circularmils shall conform to the requirements for length of lay of thenext smaller conductor.7. Construction7.1 The area of cross section, and the

28、number and diameterof wires for a variety of strand constructions in general use areshown in Tables 1 and 2.7.2 If a separator is required to be furnished with theconductor, it shall be at the option of the manufacturer unlessotherwise specified by the purchaser as to requirements for thekind and th

29、ickness of material and its application details.8. Physical and Electrical Tests8.1 Tests for the electrical properties of wires composingconductors made from soft or annealed copper wire, bare orcoated, shall be made before stranding.8.2 Tests for the physical properties of soft or annealedcopper w

30、ire, bare or coated, may be made upon the wiresbefore stranding or upon wires removed from the completedstranded conductors, but need not be made upon both. Careshall be taken to avoid mechanical injury and stretching whenremoving wires from the conductor for the purpose of testing.8.3 The physical

31、properties of wire when tested beforestranding shall conform to the applicable requirements of 11.1.8.4 The physical properties of wires removed from thecompleted stranded conductor shall be permitted to vary fromthe applicable requirements of 11.1 by the following amounts(Explanatory Note 3):8.4.1

32、Average of Results Obtained on All Wires TestedThepercent minimum elongation may be reduced by the value of5 % from the values required for unstranded wires as specifiedby Specifications B3, B33,orB189, as applicable. For ex-ample, where the unstranded wire specification requires mini-mum elongation

33、 of 30 %, wire of that material removed fromSpecification B174 stranded conductor shall meet a minimumelongation value of 25 %, a value 5 % reduction.8.4.2 Results Obtained on Individual WiresThe percentminimum elongation may be reduced by the value of 15 %from the values required for unstranded wir

34、es as specified bySpecifications B3, B33,orB189, as applicable. For example,where the unstranded wire specification requires minimumelongation of 30 %, wire of that material removed fromSpecification B174 stranded conductor shall meet a minimumTABLE 2 Classification and Construction Requirements of

35、Bunch-Stranded ConductorsClass L, M, O, P and Q Bunch StrandedConductorsAArea ofCross SectionClassification,Size, andMinimum Numberof WiresUncoated Copper Coated CopperSize,AWGClass L Class M Class O Class P Class Q Nominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistanc

36、e20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominalWireDiameter0.0080 In.(0.511 mm)NominalWireDiameter0.0063 In.(0.320 mm)NominalWireDiameter0.0050 In.(0.254 mm)NominalWireDiameter0.0040 In.(0.320 mm)NominalWireDiameter0.0031 In.(0.254 mm)cmil mm 32 AW

37、G 34 AWG 36 AWG 38 AWG 40 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km10380 5.26 10 165 . . . . 1.02 1.04 3.34 3.41 1.09 1.12 3.58 3.656530 3.31 12 104 . . . . 1.62 1.65 5.31 5.42 1.74 1.77 5.71 5.824110 2.08 14 65 104 . . . 2.57 2.62 8.43 8.60 2.76 2.82 9.06 9.242580 1.31 16 41 6

38、5 104 165 . 4.10 4.18 13.5 13.7 4.40 4.49 14.4 14.71620 0.821 18 26 41 65 104 165 6.53 6.66 21.4 21.9 7.00 7.15 23.0 23.41020 0.517 20 16 26 41 65 104 10.4 10.6 34.1 34.8 11.1 11.4 36.4 37.1640 0.324 22 . 19 . . . 16.5 16.9 54.1 55.2 17.7 18.1 58.1 59.2404 0.205 24 7 . 19 . . 26.2 26.7 86.0 87.7 28.

39、1 28.7 92.2 94.0253 0.128 26 . 7 . . . 41.8 42.6 137 140 44.9 45.8 147 150AThe constructions shown in this table are typical of those used in the industry. It is intended that this table preclude other constructions which may be desirable forspecific applications. The constructions shown provide for

40、 a finished stranded conductor approximately of the area indicated. When specified by the purchaser, the numberor sizes of wire may be increased to provide additional area to compensate for draw-down during subsequent processing.TABLE 3 Maximum Length of Lay for Bunch-StrandedConductorsArea ofCross

41、SectionSize,AWGMaximum Length of LayNominalDiameterColumnAColumnBcmil mm in. mm in. mm in. mm20 820 10.5 7 0.167 4.24 3.00 76.20 3.00 76.2016 510 8.37 8 0.149 3.78 2.75 69.85 2.75 69.8513 090 6.63 9 0.133 3.38 2.50 63.50 2.50 63.5010 380 5.26 10 0.118 3.00 2.50 63.50 2.50 63.506 530 3.31 12 0.093 2.

42、36 2.00 50.80 2.00 50.804 110 2.08 14 0.074 1.88 2.00 50.80 1.75 44.452 580 1.31 16 0.059 1.50 2.00 50.80 1.50 38.101 620 0.821 18 0.047 1.19 2.00 50.80 1.25 31.751 020 0.517 20 0.037 0.94 2.00 50.80 1.00 25.40640 0.324 22 0.030 0.76 1.30 33.02 0.80 20.32404 0.205 24 0.024 0.61 1.20 30.48 0.70 17.78

43、253 0.128 26 0.019 0.48 1.00 25.40 0.60 15.24159 0.0806 28 0.015 0.38 1.00 25.40 0.50 12.70B174 103elongation value of 15 %. If the reduction results in minimumelongation of less than 5 %, a minimum of 5 % shall apply.8.5 In the event that the requirements prescribed in 8.4.2 aremet, but those presc

44、ribed in 8.4.1 are not met, a retest shall bepermitted wherein all wires of a conductor of 100 wires or less,or 100 wires selected at random throughout a conductor ofmore than 100 wires shall be tested for the purpose of finaldetermination of conformance to 8.4.8.6 Elongation tests to determine comp

45、liance shall not bemade on the conductor as a unit.8.7 If a tinning, lead-coating, or lead-alloy-coating test isrequired, it shall be made on the wires prior to stranding.9. Density9.1 For the purpose of calculating mass, cross sections, etc.,the density of copper shall be taken as 8.89 g/cm3(0.3211

46、7lb/in.3) at 20C (Explanatory Note 4).10. Mass and Resistance10.1 The mass and electrical resistance of a unit length ofstranded conductor are a function of the length of lay (Explana-tory Note 6).10.2 The maximum electrical resistance of a unit length ofstranded conductor shall not exceed 2% over t

47、he nominal DCresistance shown in Tables 1 and 2 (Explanatory Note 5). Whenthe DC resistance is measured at other than 20C, it is to becorrected by using the multiplying factor given in Table 4.10.3 For conductors to be used in covered or insulated wiresor cables, direct current (DC) resistance measu

48、rements shall beused instead of the method outlined in Section 12, to determinecompliance with this specification.11. Requirements for Wires11.1 The purchaser shall designate the type of wire and typeof coating, if any, to be used in the conductor.11.1.1 Before stranding, uncoated wire shall meet th

49、e re-quirements of Specification B3.11.1.2 Before stranding, tinned wire shall meet the require-ments of Specification B33.11.1.3 Before stranding, lead-coated and lead-alloy coatedwire shall meet the requirements of Specification B189.11.2 These requirements shall not prohibit the manufactureof conductors from uncoated hard-drawn wires which areannealed after stranding.12. Variation in Area12.1 The calculated area of cross-section of a strandedconductor expressed in circular mils shall be the product of thesquare of the specified diameter