ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf

上传人:explodesoak291 文档编号:462380 上传时间:2018-11-27 格式:PDF 页数:7 大小:119.39KB
下载 相关 举报
ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf_第1页
第1页 / 共7页
ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf_第2页
第2页 / 共7页
ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf_第3页
第3页 / 共7页
ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf_第4页
第4页 / 共7页
ASTM B819-2000(2011) Standard Specification for Seamless Copper Tube for Medical Gas Systems《医用天然气系统用无缝铜管的标准规格》.pdf_第5页
第5页 / 共7页
亲,该文档总共7页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation: B819 00 (Reapproved 2011)Standard Specification forSeamless Copper Tube for Medical Gas Systems1This standard is issued under the fixed designation B819; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last

2、 revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification establishes the requirements for twowall thickness schedules of specially cleaned, straight lengthsof

3、seamless copper tube, identified as Types K and L, suitablefor medical gas systems. The tube shall be installed inconformance with the requirements of the National FireProtection Association (NFPA) Standard 99, Gas and VacuumSystems (NFPA) Standard 99C, Standard for Hypobaric Facili-ties (NFPA) Stan

4、dard 99B, and Canadian Standards Associa-tion (CSA) Standard Z 305.1/Z 7396.1, Nonflammable Medi-cal Gas Piping Systems.NOTE 1Types K and L tube are defined in Specification B88.NOTE 2Drawn temper tube is suitable for use with capillary (solderjoint) fittings for brazing.1.2 The values stated in inc

5、h-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units, which are provided for informationonly and are not considered standard.1.3 The following safety hazard caveat pertains only to thetest method portion of Section 12 of this specificat

6、ion. Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.22. Referenced Do

7、cuments2.1 ASTM Standards:3B88 Specification for Seamless Copper Water TubeB251 Specification for General Requirements for WroughtSeamless Copper and Copper-Alloy TubeB280 Specification for Seamless Copper Tube for Air Con-ditioning and Refrigeration Field ServiceB601 Classification for Temper Desig

8、nations for Copperand Copper AlloysWrought and CastB846 Terminology for Copper and Copper AlloysE8 Test Methods for Tension Testing of Metallic MaterialsE18 Test Methods for Rockwell Hardness of Metallic Ma-terialsE29 Practice for Using Significant Digits in Test Data toDetermine Conformance with Sp

9、ecificationsE53 Test Method for Determination of Copper in UnalloyedCopper by GravimetryE62 Test Methods for Chemical Analysis of Copper andCopper Alloys (Photometric Methods)4E243 Practice for Electromagnetic (Eddy-Current) Exami-nation of Copper and Copper-Alloy TubesE255 Practice for Sampling Cop

10、per and Copper Alloys forthe Determination of Chemical CompositionE527 Practice for Numbering Metals and Alloys in theUnified Numbering System (UNS)2.2 Other Standards:National Fire Protection Association (NFPA) 99, Gas andVacuum Systems (NFPA) 99C and Standard for Hypo-baric Facilities (NFPA) 99B5C

11、ompressed Gas Association (CGA) G-4.1, CleaningEquipment for Oxygen Service6Canadian Standards Association (CSA) Z 305.1/Z 7396.1,Nonflammable Medical Gas Piping Systems73. Terminology3.1 For definitions of terms related to copper and copperalloys, refer to Terminology B846.3.2 Definitions of Terms

12、Specific to This Standard:1This specification is under the jurisdiction ofASTM Committee B05 on Copperand Copper Alloys and is the direct responsibility of Subcommittee B05.04 on Pipeand Tube.Current edition approved Oct. 1, 2011. Published February 2012. Originallyapproved in 1992. Last previous ed

13、ition approved in 2006 as B819 00 (2006).DOI: 10.1520/B0819-00R11.2The UNS system for copper and copper alloys (see Practice E527) is a simpleexpansion of the former standard system accomplished by the addition of a prefix“C” and a suffix “00”. The suffix can be used to accommodate composition varia

14、tionof the base alloy.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.4Withdrawn. The last approved version o

15、f this historical standard is referencedon www.astm.org.5Available from National Fire Protection Association (NFPA), 1 BatterymarchPark Quincy, Massachusetts USA 02169-7471, http:/www.nfpa.org.(NFPA), 1 Batterymarch Park, Quincy, MA 02269-9101.6Available from Compressed Gas Association, 14501 George

16、 Carter Way, Suite103, Chantilly VA 20151-2923Compressed Gas Association (CGA), 1725 Jefferson Davis Hwy., Suite 1004,Arlington, VA 22202-4102.7Available from Canadian Standards Association (CSA), 5060 Spectrum Way,Suite 100 Mississauga, Ontario Canada, L4W 5N6Available from Canadian Standards Assoc

17、iation (CSA), 178 Rexdale Blvd.,Toronto, ON M9W1R3, Canada.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.1 lengthsstraight pieces of the product.3.2.2 standardun

18、iform lengths established as commercialstandards.3.2.3 tube, copper watera seamless copper tube conform-ing to the particular dimensions commercially known asCopperWaterTube and designated asTypes K and L(seeTable1).3.2.4 tube, seamlessa tube produced with a continuousperiphery in all stages of the

19、operations.4. Ordering Information4.1 Orders for material under this specification shall includethe following information:4.1.1 Specification B81900.4.1.2 Nominal or standard size (Column 1 of Table 1) andwhether Type K or L (Sections 3 and 10),4.1.3 Temper (Sections 7 and 8),4.1.4 Length (see 10.5)

20、,4.1.5 Quantity (pieces) of each size and type,4.2 The following options are available and should bespecified at the time of placing the order when required.4.2.1 Whether tension test determinations are required (Sec-tion 8),4.2.2 Whether the tube shall be charged with dry, oil-freenitrogen during c

21、apping, closing, or plugging (see 11.8),4.2.3 Certification, if required (see Section 20), and4.2.4 Mill Test Report, if required, (see Section 21).4.2.5 In addition, when material is purchased for agencies ofthe U.S. government, it shall conform to the SupplementaryRequirements as defined herein wh

22、en specified in the contractor purchase order.5. Materials and Manufacture5.1 MaterialThe materials of manufacture shall be a castbillet of Copper Alloy UNS C12200 of such purity andsoundness as to be suitable for processing into the productsprescribed herein.5.2 ManufactureThe product shall be manu

23、factured bysuch hot working necessary to convert the billet to a tubularshape and cold worked to the finished size.6. Chemical Composition6.1 The material shall conform to the following chemicalrequirements of Copper UNS No. C12200:Copper (incl silver), % 99.9 minimumPhosphorous, % 0.015 to 0.0406.2

24、 These specification limits do not preclude the presenceof other elements. Limits for unnamed elements may beestablished by agreement between the manufacturer or supplierand the purchaser.7. Temper7.1 Seamless copper tube for medical gas systems shall befurnished in the H58 (Drawn General Purpose) t

25、emper, asdefined in Practice B601.8. Mechanical Properties8.1 The tube shall conform to the mechanical propertyrequirements specified in Table 2 when tested in accordancewith Test Methods E18 and E8, respectively. Tension testdeterminations need not be made except when indicated by thepurchaser at t

26、he time of placing the order.Aconvenient methodTABLE 1 Dimensions, Mass, and Tolerances in Diameter and Wall Thickness for Nominal or Standard Copper Water Tube Sizes.(All tolerances are plus and minus except as otherwise indicated)NominalorStandardSize.in.OutsideDiameter,in. (mm)AverageOutsideDiame

27、terATolerances,in. (mm)Wall Thickness and Tolerances, in.Type K Type L Theoretical Mass, lb/ft (kg/m)Wall Thickness Wall Tolerance Thickness Tolerance Type K Type L14 0.375 (9.52) 0.001 (0.025) 0.035 (0.889) 0.0035 (0.089) 0.030 (0.762) 0.003 (0.076) 0.145 (0.216) 0.126 (0.187)38 0.500 (12.7) 0.001

28、(0.025) 0.049 (1.24) 0.005 (0.13) 0.035 (0.889) 0.004 (0.10) 0.269 (0.400) 0.198 (0.295)12 0.625 (15.9) 0.001 (0.025) 0.049 (1.24) 0.005 (0.13) 0.040 (1.02) 0.004 (0.10) 0.344 (0.512) 0.285 (0.424)58 0.750 (19.1) 0.001 (0.025) 0.049 (1.24) 0.005 (0.13) 0.042 (1.07) 0.004 (0.10) 0.418 (0.622) 0.362 (

29、0.539)34 0.875 (22.3) 0.001 (0.025) 0.065 (1.65) 0.006 (0.15) 0.045 (1.14) 0.004 (0.10) 0.641 (0.954) 0.455 (0.677)1 1.125 (28.6) 0.0015 (0.038) 0.065 (1.65) 0.006 (0.15) 0.050 (1.27) 0.005 (0.13) 0.839 (1.25) 0.655 (0.975)114 1.375 (34.9) 0.0015 (0.038) 0.065 (1.65) 0.006 (0.15) 0.055 (1.40) 0.006

30、(0.15) 1.040 (1.55) 0.884 (1.32)112 1.625 (41.3) 0.002 (0.051) 0.072 (1.83) 0.007 (0.18) 0.060 (1.52) 0.006 (0.15) 1.360 (2.02) 1.140 (1.70)2 2.125 (54.0) 0.002 (0.051) 0.083 (2.11) 0.008 (0.20) 0.070 (1.78) 0.007 (0.18) 2.060 (3.07) 1.750 (2.60)212 2.625 (66.7) 0.002 (0.051) 0.095 (2.41) 0.010 (0.2

31、5) 0.080 (2.03) 0.008 (0.20) 2.930 (4.36) 2.480 (3.69)3 3.125 (79.4) 0.002 (0.510) 0.109 (2.77) 0.011 (0.28) 0.090 (2.29) 0.009 (0.23) 4.000 (5.95) 3.330 (4.96)312 3.625 (92.1) 0.002 (0.051) 0.120 (3.05) 0.012 (0.30) 0.100 (2.54) 0.010 (0.25) 5.120 (7.62) 4.290 (6.38)4 4.125 (105) 0.002 (0.051) 0.13

32、4 (3.40) 0.013 (0.33) 0.110 (2.79) 0.011 (0.28) 6.510 (9.69) 5.380 (8.01)5 5.125 (130) 0.002 (0.051) 0.160 (4.06) 0.016 (0.41) 0.125 (3.18) 0.012 (0.30) 9.670 (14.4) 7.610 (11.3)6 6.125 (156) 0.002 (0.051) 0.192 (4.88) 0.019 (0.48) 0.140 (3.56) 0.014 (0.36) 13.900 (20.7) 10.200 (15.2)8 8.125 (206)H+

33、0.0020.006(0.051)(0.150)0.271 (6.88) 0.027 (0.69) 0.200 (5.08) 0.020 (0.51) 25.900 (38.5) 19.300 (28.7)AThe average outside diameter of a tube is the average of the maximum and minimum outside diameter, as determined at any one cross section of the tube.TABLE 2 Mechanical PropertiesTemper Designatio

34、nFormRockwell HardnessATensile StrengthStandard Former Scale Value min, ksiB(MPa)CH58 drawn straight 30T 30 min 36 (250)general lengthspurposeARockwell hardness tests shall be made on the inside surfaces of the tube.When suitable equipment is not available for determining the specified Rockwellhardn

35、ess, other Rockwell scales and values may be specified subject to betweenthe purchaser and the supplier.Bksi = 1000 psi.CMPa = pascal 3 106.B819 00 (2011)2of indicating that these tests are to be made is to state that “TestProcedure T” is required (see 4.2.1). Where agreement on theRockwell hardness

36、 tests cannot be reached, the tensile strengthrequirements of Table 2 shall be the basis for acceptance orrejection.9. Nondestructive Testing9.1 Each tube up to and including 3-in. (76.2-mm) standardsize, 318-in. (79.4-mm) outside diameter, shall be subjected toan eddy-current test. Testing shall fo

37、llow the procedures ofPractice E243, except for the determination of “end effect.”Tubes shall be passed through an eddy-current test unitadjusted to provide information on the suitability of the tubefor the intended application.9.1.1 Either notch depth or drilled hole standards shall beused.9.1.1.1

38、Notch-depth standards, rounded to the nearest 0.001in. (0.025 mm) shall be 22 % of the wall thickness. Thenotch-depth tolerance shall be plus and minus 0.0005 in. (0.013mm). Alternatively at the option of the manufacturer usingspeed-insensitive eddy-current units that are equipped so that afraction

39、of the maximum imbalance signal can be selected, thefollowing percent maximum imbalance signals may be used:Standard Tube Size, in.Maximum Percent ImbalanceSignal MagnitudeUp to38 , incl 0.212 to 2, incl 0.3Over 2 to 3, incl 0.49.1.1.2 Drilled holes shall be drilled radially through thewall using a

40、suitable drill jig that has a bushing to guide thedrill, care being taken to avoid distortion of the tube whiledrilling. The diameter of the drilled hole shall be in accordancewith the following and shall not vary by more than +0.001 in.(+0.026 mm), 0.000 in. (0.000 mm) of the hole diameterspecified

41、.Tube OutsideDiameter, in.Diameter of DrilledHoles, in. Drill Number14 to34 , incl 0.025 72Over34 to 1, incl 0.031 68Over 1 to 114 , incl 0.036 64Over 114 to 112 , incl 0.042 58Over 112 to 134 , incl 0.046 58Over 134 to 2, incl 0.052 559.1.2 Tubes that do not activate the signalling device of theedd

42、y-current testers shall be considered as conforming to therequirements of this test. Tubes with discontinuities indicatedby the testing unit may at the option of the manufacturer bereexamined or retested to determine whether the discontinuingis cause for rejection. Signals that are found to have bee

43、ncaused by minor mechanical damage, soil or moisture, shall notbe cause for rejection of the tubes provided the tube dimen-sions are still within prescribed limits and the tube is suitablefor its intended application.9.2 Tube made to this specification shall be capable ofwithstanding the pressure te

44、st of 9.2.1 or 9.2.2. Should subse-quent testing by the purchaser establish that the material doesnot meet these requirements, the material may be rejected.9.2.1 The tube shall stand without showing evidence ofleakage, and an internal hydrostatic pressure sufficient tosubject the material to a fiber

45、 stress of 6000 psi (41 MPa)calculated from the following equation for thin hollow cylin-ders under tension:P 52 StD 2 0.8t(1)where:P = hydrostatic pressure, psi (MPa);S = allowable stress of the material, psi (MPa);t = wall thickness, in. (mm); andD = outside diameter of the tube, in. (mm).9.2.2 Th

46、e tube shall stand an internal air pressure of 60 psig(415 kPa) for 5 s without showing evidence of leakage.The testmethod used shall permit easy visual detection of any leakage,such as by having the tube under water or by the pressuredifferential method.10. Dimensions, Mass and Permissible Variatio

47、ns10.1 For the purpose of determining conformance with thedimensional requirements specified in this specification, anymeasured value outside the specified limiting values for anydimensions may be cause for rejection.10.2 Standard Dimensions, Wall Thickness, and DiameterTolerances shall be in accord

48、ance with Table 1.10.3 Theoretical Weights for purposes of calculatingweights, cross sections, and so forth, the density of the coppershall be taken as 0.323 lb/in.3(8.94 g/cm3).10.4 Roundness Tolerance shall be as specified in Table 3.The deviation from roundness is measured as the differencebetwee

49、n major and minor diameters as determined at any onecross section of the tube.10.5 Standard Lengths and TolerancesThe standardlength and tolerances shall be as specified in Table 4.10.6 Squareness of CutThe departure from squareness ofthe end of any tube shall not exceed more than 0.010 in. (0.25mm) for tube up to and including12-in. (12.7-mm) standardsize; and not more than 0.016 in./in. (0.40 mm/mm) of outsidediameter for tube larger than12-in. (12.7-mm) standard size.11. Tube Cleaned for Medical Gas Systems11.1 Tube for medical gas systems s

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1