1、Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardwarePart 3: Fire resistance of hinged and pivoted timber doorsets and openabletimber framed windows BS EN 15269-3:2012Incorporating
2、 corrigendum August 2016BSI Standards PublicationBS EN 15269-3:2012 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 15269-3:2012.The UK participation in its preparation was entrusted CZ Technical Committee FSH/22, Fire resistance tests UP4VCDPNNJUUFF4) JSFSFTJTU
3、BODFUFTUTfor doors.A list of organizations represented on this TVCcommittee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2016.
4、Published by BSI Standards Limited 2016ISBN 978 0 580 95419 1ICS 13.220.50; 91.060.50Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 August 2012.Amendments/co
5、rrigenda issued since publicationDate Text affected31 August 2016 Standard title correctedBS EN 15269-3:2012EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15269-3 August 2012 ICS 13.220.50; 91.060.50 English Version Extended application of test results for fire resistance and/or smoke control
6、for door, shutter and openable window assemblies, including their elements of building hardware - Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows Application tendue des rsultats dessais de rsistance au feu et/ou dtanchit la fume des blocs-portes, bloc
7、s-fermetures et fentres, y compris leurs lments de quincaillerie - Partie 3 : Rsistance au feu des blocs-portes battants et pivotants en bois et des fentres ossature bois Erweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeit und/oder Rauchdichtigkeit von Tren, Toren und Fenst
8、ern einschlielich ihrer Baubeschlge - Teil 3: Feuerwiderstandsfhigkeit von Drehflgeltren und Fenstern aus Holz This European Standard was approved by CEN on 16 June 2012. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
9、 Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (E
10、nglish, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgiu
11、m, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerl
12、and, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref.
13、 No. EN 15269-3:2012: EBS EN 15269-3:2012EN 15269-3:2012 (E) 2 Contents Page Foreword 3g31 Scope 4g32 Normative references 4g33 Terms and definitions .5g34 Determination of the field of extended application 6g34.1 General 6g34.2 How to use the extended application rules in Annex A .6g34.3 Procedure
14、for maximum field of extended application .6g34.4 Analysis of test results .7g35 Extended application report .7g36 Classification report 7g3Annex A (normative) Construction parameter variations 9g3Annex B (normative) Arrangements for doorsets incorporating side and/or overpanels . 70g3BS EN 15269-3:
15、2012EN 15269-3:2012 (E) 3 Foreword This document (EN 15269-3:2012) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical t
16、ext or by endorsement, at the latest by February 2013, and conflicting national standards shall be withdrawn at the latest by February 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held resp
17、onsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. This document is one of a series entitled “EN 15269, Extended application of test results for fire resistance and/or
18、 smoke control for door, shutter and openable window assemblies, including their elements of building hardware” which consists of the following parts: Part 1: General requirements; Part 2: Fire resistance of hinged and pivoted steel doorsets; Part 3: Fire resistance of hinged and pivoted timber door
19、sets and openable timber framed windows; Part 4: Fire resistance of hinged and pivoted glass doorsets; Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable windows; Part 6: Fire resistance of sliding timber doorsets; Part 7: Fire resistance of sliding steel doors
20、ets; Part 8: Fire resistance of horizontally folding timber doorsets; Part 9: Fire resistance of horizontally folding steel doorsets; Part 10: Fire resistance of steel rolling shutter assemblies; Part 11: Fire resistance of operable fabric curtains; Part 20: Smoke control for hinged and pivoted stee
21、l, timber and metal framed glazed doorsets. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former
22、 Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 15269-3:2012EN 15269-3:2012 (E) 4 1 S
23、cope This European Standard covers hinged or pivoted doorsets with timber based leaves, timber framed glazed doors and openable timber framed windows. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 163
24、4-1. This standard covers doorsets with internal structural elements which are comprised of timber. Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples: integrity (E), integrity/radiation (EW) or integrity/insulation (E
25、I1or EI2) classification; glazed elements including vision panels and framed glazed doorsets, louvres and/or vents; side, transom or overpanels; items of building hardware; decorative finishes; intumescent, smoke, draught or acoustic seals; alternative supporting construction(s). The effect on the C
26、lassification C for the doorsets following an extended application process is not addressed in this European Standard. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, onl
27、y the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 179, Building hardware Emergency exit devices operated by a lever handle or push pad, for use on escape routes Requirements and test methods EN 844 (all parts), R
28、ound and sawn timber Terminology EN 1125, Building hardware Panic exit devices operated by a horizontal bar, for use on escape routes Requirements and test methods EN 1363-1, Fire resistance tests Part 1: General requirements EN 1634-1, Fire resistance and smoke control tests for door, shutter and o
29、penable window assemblies and elements of building hardware Part 1: Fire resistance test for doors, shutters and openable windows EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 2: Fire resistance characterisa
30、tion test for elements of building hardware EN 12519, Windows and pedestrian doors Terminology BS EN 15269-3:2012EN 15269-3:2012 (E) 5 EN 13501-2, Fire classification of construction products and building elements Part 2: Classification using test data from fire resistance tests excluding ventilatio
31、n services EN 15254-4 Extended application of results from fire resistance tests Non-loadbearing walls Part 4: Glazed constructions EN 15269-1:2010, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their element
32、s of building hardware Part 1: General Requirements EN ISO 13943, Fire safety Vocabulary (ISO 13943) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1, EN 12519, EN ISO 13943, EN 1634-1, EN 1634-2 and EN 15269-1 and the following apply. 3.1 core
33、material fitted centrally within the thickness of a door leaf which may consist of a single sheet of material or a combination either of sheets of the same material or layers of different materials 3.2 effective rebate depth dimension of the door leaf thickness of overlapping adjacent edges of door
34、leaf relative to the door frame, transom or side panel or flush overpanel Note 1 to entry: At the meeting edges and for rebated leaves this dimension will be the rebate where the intumescent seal is fitted or, if no seal is fitted, the depth of the largest rebate (see Figure 1). 3.3 leaf symmetry co
35、nstruction of a door leaf, without consideration of any leaf edge rebates, viewed either side of an imaginary plane drawn centrally in the thickness of the leaf Note 1 to entry: A symmetrical door leaf will be identical either side of this imaginary plane, whilst an asymmetrical door leaf will diffe
36、r. 3.4 exposed intumescent seal intumescent seal which is fitted in the perimeter of the leaf or in the door frame rebate and is visible when the leaf is in the open position 3.5 concealed intumescent seal intumescent seal which is fitted in the perimeter of the leaf or in the door frame rebate and
37、is not visible when the leaf is in the open position, including seals behind veneers and laminates 3.6 facing (and decorative facing) outer layer of material on the leaf or panel normally only used for decorative, not for structural, purposes 3.7 subfacing layer (or layers) of material between the c
38、ore and the facing in the leaf or panel normally used for structural purposes BS EN 15269-3:2012EN 15269-3:2012 (E) 6 4 Determination of the field of extended application 4.1 General 4.1.1 Before there can be any consideration for extended application, a representative doorset shall have been tested
39、 in accordance with EN 1634-1 to achieve a test result which could generate a classification in accordance with EN 13501-2 at least equal to the classification subsequently required from extended application considerations. 4.1.2 A review of the doorset construction parameters can indicate that one
40、or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification f
41、or any specific parameter beyond that achieved during any one test, unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 If, when following the extended application procedure, any part of the classified product cannot be covered by the extended application ru
42、les then that part shall be omitted from the subsequent extended application report and classification report. 4.2 How to use the extended application rules in Annex A 4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an extended application report.
43、 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Annex A. 4.2.3 Review the type of classification to be retained from column (3) of Annex A and establish from the contents of column (4) of Annex A whether any extended application is available
44、 beyond the direct application rules in EN 1634-1 without the need for further testing. 4.2.4 Where this is deemed to be possible, it can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) of Annex A. 4.2.5 Where the variati
45、ons required can only be achieved from additional testing, the additional test can be made on a similar specimen type i.e. a doorset of the same or more onerous configuration where the leaf construction is fundamentally the same as that tested. Alternatively, column (5) of Annex A identifies an opti
46、on for alternative testing and relevant test parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide an extended field of application from a single test. However, where a manufacturer envisages to manufacture a range of doors incorporating single doors and
47、 also double doors with or without side, transom or over panels, with or without glazing, louvres or ventilation grilles, with alternative element of building hardware, etc., it is recommended that careful consideration is given to the complete range of doorset designs and options. This helps to min
48、imise the testing required before testing commences. 4.3.2 Establish all the parameter variations which are required to be part of the product range. 4.3.3 Determine which are the most important specification requirements and incorporate as many as possible into the specimen(s) for the first tests i
49、n the series. 4.3.4 Conduct the first fire resistance test or a series of tests and then establish which of the original desired parameter variations have not been covered by the fire resistance tests, including direct application possibilities. BS EN 15269-3:2012EN 15269-3:2012 (E) 7 4.3.5 Identify these parameter variations in Annex A and establish if any extended application is possible without further testing. 4.