DLA MIL-DTL-49285 18 A-2010 CABLE SPECIAL PURPOSE ELECTRICAL SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE.pdf

上传人:boatfragile160 文档编号:690836 上传时间:2018-12-30 格式:PDF 页数:4 大小:74.48KB
下载 相关 举报
DLA MIL-DTL-49285 18 A-2010 CABLE SPECIAL PURPOSE ELECTRICAL SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE.pdf_第1页
第1页 / 共4页
DLA MIL-DTL-49285 18 A-2010 CABLE SPECIAL PURPOSE ELECTRICAL SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE.pdf_第2页
第2页 / 共4页
DLA MIL-DTL-49285 18 A-2010 CABLE SPECIAL PURPOSE ELECTRICAL SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE.pdf_第3页
第3页 / 共4页
DLA MIL-DTL-49285 18 A-2010 CABLE SPECIAL PURPOSE ELECTRICAL SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE.pdf_第4页
第4页 / 共4页
亲,该文档总共4页,全部预览完了,如果喜欢就下载吧!
资源描述

1、 MIL-DTL-49285/18A 31 March 2010 SUPERSEDING MIL-C-49285/18 19 October 1989 DETAIL SPECIFICATION SHEET CABLE, SPECIAL PURPOSE, ELECTRICAL, SIX INDIVIDUALLY SHIELDED PAIRS OF 22 AWG SOLID WIRE This specification is approved for use by all Departments and Agencies of the Department of Defense. The req

2、uirements for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-49285. FIGURE 1. Cable illustration. AMSC N/A FSC 6145 INCH-POUND Inactive for new design after 16 June 1997. Provided by IHSNot for ResaleNo reproduction or networking permitted without licens

3、e from IHS-,-,-MIL-DTL-49285/18A 2 Engineering information: See table I. Note: Not for aerospace use. TABLE I. Description, electrical. Electrical characteristics Requirements Nominal capacitance between conductors Nominal capacitance between the conductor and the shield with one conductor tied to t

4、he shield Continuous working voltage Nominal capacitance between adjacent shields Continuous working voltage between adjacent shields Shield dc resistance 40 pF/ft (picofarads/foot) 77 pF/ft 300 V rms maximum between conductors 150 pF/ft 50 volts maximum 14 ohms/1,000 feet maximum TABLE II. Descript

5、ion, physical. Components Construction details Number of pairs Conductor type and wire size Conductor insulation Conductor insulation thickness Drain wire type and size Jacket material Jacket thickness Finished cable diameter Cable style (UL) Tensile strength (jacket) Elongation (jacket) Overall cab

6、ling lay length Six individually shielded Solid tinned copper 22 AWG Polyvinyl chloride 0.013 inch nominal thickness Solid tinned copper 22 AWG Polyvinyl chloride 0.035 inch 0.398 inch maximum outside diameter 2464 2,000 pounds per square inch minimum 150 percent minimum 1.3 twists per foot 10 perce

7、nt Cabled pair orientation: The position of the red and green pair shield shall determine the rotation direction for pair location (see figure 1). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-49285/18A 3 TABLE III. Shield color code. Pair

8、numbers Shield color Center core 1stpair 2ndpair 3rdpair 4thpair 5thpair 6thpair Red Green Blue 1 Blue 2 Blue 3 Blue 4 REQUIREMENTS: Design and construction: (see table II and table III): Shield location and orientation. The polyester aluminum shield is to be located on the outer circumference of th

9、e pair, with the aluminum foil side outward. Insulation on the interior of the shield is to be complete with no aluminum available for contact. Drain wire location. The drain wire is to be spirally located between the noise reducing tape and the aluminum foil shield, and is to be in continuous conta

10、ct with the aluminum surface of the foil shield and the noise reducing tape throughout the cable. Cable temperature rating. The cable temperature rating shall be -20C to +80C. Flammability. The cable shall pass UL 2556 flame test requirements. Shield integrity test.* Frequency Response * 100 kHz 114

11、 dB below reference 500 kHz 105 dB below reference 1 MHz 99 dB below reference 5 MHz 85 dB below reference 10 MHz 79 dB below reference 15 MHz 74 dB below reference 20 MHz 70 dB below reference 25 MHz 65 dB below reference 30 MHz 61 dB below reference 100 MHz 42 dB below reference * Any two readings

12、 may deviate to a value of 0.9 times the stated limits. * All values are a minimum numerical value. Fixture resonance will occur between 40 and 70 MHz. Crosstalk test limits. All values are minimums. Frequency (kHz) Near end crosstalk (dB) Far end crosstalk (dB) 40 58 58 70 56 55 100 54 53 1,000 55

13、52 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-49285/18A 4 Insulation resistance between shields: 100 megohms/1,000 feet minimum. Durometer hardness. The cable jacket shall have a “Shore A” hardness of 82 5. Part or Identifying Number (PI

14、N): The PIN shall be M49285/18. Changes from previous issue. The margins of this specification are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in th

15、ese notations. Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue. Referenced documents. This document references MIL-DTL-49285 and UL 2556. CONCLUDING MATE

16、RIAL Custodians: Preparing activity: Army CR DLA - CC Navy SH Air Force 85 DLA - CC Review activities: (Project 6145-2009-022) Army MI Air Force 99 DLA IS NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change. You should verify the currency of the information above using the ASSIST Online database at https:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1