1、BSI Standards PublicationBS EN 50288-3-1:2013Multi-element metallic cables used in analogue and digital communication and controlPart 3-1: Sectional specification for unscreened cables characterised up to 100 MHz Horizontal and building backbone cablesBS EN 50288-3-1:2013 BRITISH STANDARDNational fo
2、rewordThis British Standard is the UK implementation of EN 50288-3-1:2013. It supersedes BS EN 50288-3-1:2003 which is withdrawn.The UK participation in its preparation was entrusted to Technical Committee EPL/46, Cables, wires and waveguides, radio frequency connectors and accessories for communica
3、tion and signalling.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2013.Pub
4、lished by BSI Standards Limited 2013ISBN 978 0 580 77096 8 ICS 33.120.20Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 September 2013.Amendments/corrigenda i
5、ssued since publicationDate T e x t a f f e c t e dBS EN 50288-3-1:2013EUROPEAN STANDARD EN 50288-3-1 NORME EUROPENNE EUROPISCHE NORM May 2013 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Norm
6、ung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50288-3-1:2013 E ICS 33.120.20 Supersedes EN 50288-3-1:2003 English version Multi-element metallic cables used in anal
7、ogue and digital communication and control - Part 3-1: Sectional specification for unscreened cables characterised up to 100 MHz - Horizontal and building backbone cables Cbles mtalliques lments multiples utiliss pour les transmissions et les commandes analogiques et numriques - Partie 3-1: Spcifica
8、tion intermdiaire pour les cbles non blinds pour applications jusqu 100 MHz - Cbles horizontaux et verticaux de btiment Mehradrige metallische Daten- und Kontrollkabel fr analoge und digitale bertragung - Teil 3-1: Rahmenspezifikation fr ungeschirmte Kabel bis 100 MHz - Kabel fr den Horizontal- und
9、Steigbereich This European Standard was approved by CENELEC on 2013-03-18. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bib
10、liographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the r
11、esponsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, F
12、inland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 50288-3-1:2013EN 50
13、288-3-1:2013 - 2 - Contents Page Foreword 3 1 Scope 4 2 Normative references . 4 3 Terms, definitions, symbols and abbreviations 4 4 Cable construction . 4 4.1 Conductor . 4 4.2 Insulation 5 4.3 Cabling elements 5 4.4 Identification of cabling elements 5 4.5 Screening of cabling elements . 5 4.6 Cab
14、le make-up . 5 4.7 Filling compound . 5 4.8 Interstitial fillers 5 4.9 Screening of the cable core . 5 4.10 Moisture barriers . 5 4.11 Wrapping layers 5 4.12 Sheath 5 5 Tests and requirements for completed cables . 6 5.1 Electrical tests 6 5.2 Mechanical test requirements 8 5.3 Environmental tests 9
15、 5.4 Fire performance tests 9 Annex A (informative) Maximum voltage, current and temperature rating for cables used for POE applications 10 Annex B (Informative) Blank Detail Specification 11 BS EN 50288-3-1:2013- 3 - EN 50288-3-1:2013 Foreword This document EN 50288-3-1:2013 has been prepared by CL
16、C/SC 46XC “Multicore, Multipair and Quad Data communication cables“, of CLC/TC 46X, “Communication cables“. The following dates are fixed: latest date by which this document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2014-03-18 la
17、test date by which the national standards conflicting with this document have to be withdrawn (dow) 2016-03-18 This document supersedes EN 50288-3-1:2003. EN 50288-3-1:2013 includes the following significant technical changes with respect to EN 50288-3-1:2003: the addition of the Blank Detail Specif
18、ication Annex; a number minor corrections and updating of references; the re-classification of ELFEXT to ACR-F. This Part 3-1 is to be read in conjunction to EN 50288-1. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELEC and/
19、or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC). BS EN 50288-3-1:2013EN 50288-3-1:2013 - 4 - 1 Scope EN
20、50288-3-1 is a sectional specification for unscreened cables, characterised from 1 MHz up to 100 MHz, to be used in horizontal and building backbone wiring as defined in EN 50173. This sectional specification contains the electrical, mechanical, transmission and environmental performance characteris
21、tics of the cables, when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application. The cables covered in this sectional specification are intended to operate with volt
22、ages and currents normally encountered in communication systems. These cables are not intended to be used in conjunction with low impedance sources, for example, the electric power supplies of public utility mains. 2 Normative references The following documents, in whole or in part, are normatively
23、referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 50173 Series Information technology - Generic cabling systems EN 5
24、0288-1 Multi-element metallic cables used in analogue and digital communication and control - Part 1: Generic specification EN 50289 Series Communication cables - Specifications for test methods EN 50290 Series Communication cables EN 60811 Series Electric and optical fibre cables - Test methods for
25、 non-metallic materials (IEC 60811 series) IEC 60189-2 Low-frequency cables and wires with PVC insulation and PVC sheath - Part 2: Cables in pairs, triples, quads and quintuples for inside installations 3 Terms, definitions, symbols and abbreviations 3.1 Terms and definitions For the purposes of thi
26、s document the terms and definitions of EN 50288-1 apply. 3.2 Symbols and abbreviations For the purposes of this document, the following abbreviations apply. EX Exogenous (derived or originating externally) POE Power Over Ethernet 4 Cable construction 4.1 Conductor The conductor shall be solid coppe
27、r and meet the requirements of EN 50288-1, 4.1. BS EN 50288-3-1:2013- 5 - EN 50288-3-1:2013 The conductor shall be plain or metal coated. The nominal conductor diameter shall be 0,5 mm and 0,8 mm. NOTE Constructions with copper clad conductors do not meet the requirements. 4.2 Insulation The insulat
28、ion shall be of a suitable material according to the relevant part of EN 50290-2. 4.3 Cabling elements The cable element shall be a pair or a quad. 4.4 Identification of cabling elements Unless otherwise specified, the colour coding for identification is given in IEC 60189-2. The colours shall meet
29、the requirements of EN 50288-1, 4.4. 4.5 Screening of cabling elements Not applicable. 4.6 Cable make-up The cable elements shall be laid up in concentric layer(s) or units to form the cable core. 4.7 Filling compound Not applicable. 4.8 Interstitial fillers Where fillers are used they shall meet th
30、e requirements of EN 50288-1, 4.8. 4.9 Screening of the cable core Not applicable. 4.10 Moisture barriers Not applicable. 4.11 Wrapping layers Where wrapping layers are used they shall be in accordance with EN 50288-1, 4.11. 4.12 Sheath The sheath shall be of a suitable material according to the rel
31、evant part of EN 50290-2. BS EN 50288-3-1:2013EN 50288-3-1:2013 - 6 - 5 Tests and requirements for completed cables The following tables give the tests to be applied, together with the respective limits, in order to demonstrate compliance with this specification. 5.1 Electrical tests 5.1.1 Low-frequ
32、ency and d.c. electrical measurements Table 1 - Low-frequency and d.c. electrical measurements EN 50288-1 sub-clause Parameter Requirement 5.1.1.1 Conductor loop resistance 19,0 /100 m 5.1.1.2 Conductor resistance unbalance 2,0 % 5.1.1.3 Dielectric strength conductor/conductor 1,0 kV d.c. or 0,7 kV
33、a.c. for 1 min or 2,5 kV d.c. or 1,7 kV a.c. for 2 s 5.1.1.4 Insulation resistance 5 000 M.km when tested in accordance with EN 50289-1-4 5.1.1.5 Mutual capacitance No requirement specified 5.1.1.6 Capacitance unbalance to earth 1 200 pF/km 5.1.2 High-frequency electrical and transmission measuremen
34、ts Table 2 - High-frequency electrical and transmission requirements EN 50288-1 sub-clause Parameter Requirement 5.1.2.1 Velocity of propagation Phase delay 534+36/f ns/100 m, 1 MHz f 100 MHz 5.1.2.2 Propagation delay difference (skew) 45 ns/100 m at 100 MHz 5.1.2.3 Longitudinal attenuation2) 3) 4)5
35、.1.2.4 Near-end unbalance attenuation 40-10log(f) dB, 1 MHz f 100 MHz, 1 4 10 16 20 31,25 62,5 100 MHz 2,1 4,0 6,3 8,0 9,0 11,4 16,5 21,3 dB/100 m 1,9108f+0,0222f+0,2/f, 1 MHz f 100 MHz BS EN 50288-3-1:2013- 7 - EN 50288-3-1:2013 5.1.2.5 Near-end crosstalk (NEXT)1) 2) 5.1.2.6 Attenuation to crosstal
36、k ratio at the far end 2) 6) ACR-F 1 4 10 16 20 31,25 62,5 100 MHz 64 52 44 40 38 34 28 24 dB 64-20log(f), 1 MHz f 100 MHz, values referenced to 100 m 5.1.2.7.1 Power sum near-end crosstalk 2) (PSNEXT) 1 4 10 16 20 31,25 62,5 100 MHz 62,3 53,3 47,3 44,2 42,8 39,9 35,4 32,3 dB 62,3-15log(f), 1 MHz f
37、100 MHz 5.1.2.7.2 Power Sum Attenuation to crosstalk ratio at the far end 2) 6) (PSACR-F) 1 4 10 16 20 31,25 62,5 100 MHz 61 49 41 37 35 31 25 21 dB 61-20log(f), 1 MHz f 100 MHz, values referenced to 100 m 5.1.2.8 Mean characteristic impedance 100 5 , 120 5 , at 100 MHz 5.1.2.9 Return loss 2) 5)4 8
38、10 16 20 31,25 62,5 100 MHz 23,1 24,5 25,0 25,0 25,0 23,6 21,5 20,1 dB 20+5log(f), 4 MHz f 10 MHz; 25dB, 10 MHz f 20 MHz; 25-7log(f/20), 20 MHz f 100 MHz, 5.1.2.10 Coupling attenuation 40 dB, 30 MHz f 100 MHz; 40-20log(f/100) dB, 100 MHz f 1 000 MHz; 1)For hybrid cables and multi-unit cables, PSNEXT
39、 between all non fibre recognised cable units shall be 3 dB better than the specified pair to pair NEXT at all specified frequencies. 2) The values in the table are for information only. The formula given shall be used to determine compliance, rounded to one decimal place. 3) The attenuation shall m
40、eet values adjusted for temperature up to 40 C with a temperature coefficient of 0,4 % per degree rise and for temperatures from 40 C to 60 C with a temperature coefficient of 0,6 %, above 20 C. 4) Values between 1 MHz and 4 MHz are for information only. 5) For the measurement of return loss a test
41、sample having a round trip loss 40 dB at any measured frequency should be used. 6)ELFEXT is now re-classified as ACR-F, PSELFEXT is now re-classified PSACR-F, see Annex A of EN 50288-1 for an explanation 1 4 10 16 20 31,25 62,5 100 MHz 65,3 56,3 50,3 47,3 45,8 42,9 38,4 35,3 dB 65,3-15log(f), 1 MHz
42、f 100 MHz BS EN 50288-3-1:2013EN 50288-3-1:2013 - 8 - 5.2 Mechanical test requirements Table 3 - Mechanical test requirements EN 50288-1 sub-clause Parameter Requirement 5.2.1 Conductor elongation at break EN 50289-3-2 10 % 5.2.2 Shrinkage of insulation EN 50289-3-4 5 % 5.2.3 Crush resistance of the
43、 cable EN 50289-3-5 1 000 N / 1 min / 100 mm Near-end crosstalk, return loss and characteristic impedance shall remain within the specified limits 5.2.4 Impact resistance of the cable EN 50289-3-6 12,5 mm radius / 1 J / 3 impacts at 1 m from the measured end Near-end crosstalk, return loss and chara
44、cteristic impedance shall remain within the specified limits 5.2.5 Abrasion resistance of the sheath markings EN 50289-3-8 Marking shall remain legible after 10 strokes Force 4 N 5.2.6 Simulated installation testing of the cable 5.2.6.1 Simulated installation testing of the cable Single bend EN 5028
45、9-3-9:2001, Clause 4, procedure 2 Single bend 4 dia / 4 cycles Near-end crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits 5.2.6.2 Simulated installation testing of the cable “S” bend EN 50289-3-9:2001, Clause 8 “S” bend 8 dia / 1
46、00 m / 1 cycle / 120 deg / 1 m/s Near-end crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits 5.2.7 Tensile performance EN 50289-3-16 combined with 5.2.6 of this standard Load shall be 25 N per pair (i.e.100 N for 4 pairs) Near-end
47、 crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits BS EN 50288-3-1:2013- 9 - EN 50288-3-1:2013 5.3 Environmental tests Table 4 - Environmental test requirements EN 50288-1 sub-clause Parameter Requirement 5.3.1 Cold bend performa
48、nce of the cable EN 50289-3-9 Mandrel diameter 8 OD, No. of turns 4, temp -20 C 2 C No cracks when examined visually without magnification 5.3.5 Temperature cycling EN 50289-4-6 The attenuation shall meet the adjusted values according to footnote 3 in Table 2 when subjected to 2 temperature cycles b
49、etween 20 C and 60 C 5.3.6 Hot shock performance (test) As specified in EN 60811-509 5.4 Fire performance tests Fire performance tests shall be in accordance with EN 50288-1, 5.4 BS EN 50288-3-1:2013EN 50288-3-1:2013 - 10 - Annex A (informative) Maximum voltage, current and temperature rating for cables used for POE applications Table A.1 specifies the maximum recommended voltage, current, current density and conduc