1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationAutomatic electrical controls for household and similar usePart 2-7: Particular requirements for timers and time switchesBS EN 60730-2-7:2010Incorporating corrigendum December 20
2、11National forewordThis British Standard is the UK implementation of EN 60730-2-7:2010,IEC 60730-2-7:2008. It supersedes BS EN 60730-2-7:1992, which will be withdrawn on 1 October 2013.The CENELEC common modifications have been implemented at the appropriate places in the text and are indicated by t
3、ags (e.g. ).The UK participation in its preparation was entrusted to Technical CommitteeCPL/72, Electrical control devices for household equipment and appliances. A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to in
4、clude all the necessary provisions of a contract. Users are responsible for its correct application.ISBN 978 0 580 77552 9 ICS 39.040.99; 97.120Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard was published under the authority of the Standards Po
5、licy and Strategy Committee on 30 April 2011.Date Text affectedBRITISH STANDARDBS EN 60730-2-7:201029 February 2012 Implementation of CENELEC corrigendum December 2011incorprating corrigendum December 2011. It was derived from The start and finish of text introduced or altered by corrigendum is indi
6、cated in the text by tags. Text altered by CENELEC corrigendum December 2011 is indicated in the text by . Amendments/corrigenda issued since publication The British Standards Institution 2012EUROPEAN STANDARD EN 60730-2-7 NORME EUROPENNE EUROPISCHE NORM October 2010 CENELEC European Committee for E
7、lectrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref.
8、No. EN 60730-2-7:2010 E ICS 97.120Supersedes EN 60730-2-7:1991 + corr. Mar.2001 + A1:1997 + corr. Mar.2001 + A11:1994 + corr. Mar.2001 + A12:1993 + corr. Mar.2001 + A13:2003 + A14:2003English version Automatic electrical controls for household and similar use - Part 2-7: Particular requirements for
9、timers and time switches (IEC 60730-2-7:2008, modified) Dispositifs de commande lectrique automatiques usage domestique et analogue - Partie 2-7: Rgles particulires pour les minuteries et les minuteries cycliques (CEI 60730-2-7:2008, modifie) Automatische elektrische Regel- und Steuergerte fr den Ha
10、usgebrauch und hnliche Anwendungen - Teil 2-7: Besondere Anforderungen an Zeitsteuergerte und Schaltuhren (IEC 60730-2-7:2008, modifiziert) This European Standard was approved by CENELEC on 2010-10-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the
11、conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists
12、in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrot
13、echnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, S
14、witzerland and the United Kingdom. Incorporating corrigendum December 2011Foreword The text of the International Standard IEC 60730-2-7:2008, prepared by IEC TC 72, Automatic controls for household use, together with the common modifications prepared by the Technical Committee CENELEC TC 72, Automat
15、ic controls for household use, was submitted to the CENELEC Unique Acceptance Procedure and was approved as EN 60730-2-7 on 2010-10-01. This document supersedes EN 60730-2-7:1991 + A1:1997 + A11:1994 + A12:1993 + A13:2003 + A14:2003. Attention is drawn to the possibility that some of the elements of
16、 this document may be the subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent rights. The following dates are fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by e
17、ndorsement (dop) 2011-10-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2013-10-01 This Part 2-7 is to be used in conjunction with EN 60730-1:2000, Automatic electrical controls for household and similar use Part 1: General requirements, and any sub
18、sequent amendments. This European Standard has been prepared under a mandate given to CENELEC by the European Commission and the European Free Trade Association and covers essential requirements of EC Directive 2004/108/EC. See Annex ZZ. Annexes ZA and ZZ have been added by CENELEC. _ Endorsement no
19、tice The text of the International Standard IEC 60730-2-7:2008 was approved by CENELEC as a European Standard with agreed common modifications. BS EN 60730-2-7:2010EN 60730-2-7:2010 (E) 2 CONTENTS 1 Scope and normative references 4 2 Definitions 5 3 General requirements.6 4 General notes on tests .6
20、 5 Rating 6 6 Classification7 7 Information . 88 Protection against electric shock 99 Provision for protective earthing . 910 Terminals and terminations 911 Constructional requirements. 912 Moisture and dust resistance10 13 Electric strength and insulation resistance10 14 Heating 10 15 Manufacturing
21、 deviation and drift11 16 Environmental stress 11 17 Endurance11 18 Mechanical strength .1 19 Threaded parts and connections.1 20 Creepage distances, clearances and distances through solid insulation .1 21 Fire hazard testing .122 Resistance to corrosion 1 23 Electromagnetic compatibility (EMC) requ
22、irements emission .1 24 Components .1 25 Normal operation1 26 Electromagnetic compatibility (EMC) requirements immunity .1 27 Abnormal operation 1 28 Guidance on the use of electronic disconnection 1 Annex H (normative) Requirements for electronic controls .16 Annex AA (normative) Number of cycles,
23、automatic and manual action Table AA.1 Values for free standing, independently mounted and in-line cord timers and time switches .aAnnex ZA (normative) Normative references to international publications with their corresponding European publications Annex ZZ (informative) Coverage of Essential Requi
24、rements of EC Directives. 2BS EN 60730-2-7:2010EN 60730-2-7:2010 (E) 3 555555555551819018 AUTOMATIC ELECTRICAL CONTROLS FOR HOUSEHOLD AND SIMILAR USE Part 2-7: Particular requirements for timers and time switches 1 Scope and normative references This clause of Part 1 is applicable except as follows:
25、 1.1 Replacement: In general, this part of IEC 60730 applies to timers and time switches for household and similar use that may use electricity, gas, oil, solid fuel, solar thermal energy, etc. or a combination thereof, including heating, air conditioning and similar applications. This standard is a
26、lso applicable to individual timers utilized as part of a control system or timers which are mechanically integral with multifunctional controls having non-electrical outlets. This standard does not apply to time-delay switches (TDS) within the scope of IEC 60669-2-31). Throughout this standard, the
27、 word “timers” means timers and time switches, unless the type is specifically mentioned. Devices which only indicate time or passage of time are not included. This standard does not apply to multi-functional controls having an integrated timing function which is not capable of being tested as a sep
28、arate timing device. 1.1.1 This standard applies to the inherent safety, to the operating characteristics where such are associated with equipment protection and to the testing of automatic electrical control devices used in appliances and other apparatus, electrical and non-electrical, for househol
29、d and similar purposes, but also extended to industrial purposes when no dedicated product standards exist, such as that for central heating, air conditioning, process heating, etc. Timers for equipment not intended for normal household use, but which nevertheless may be used by the public, such as
30、equipment intended to be used by laymen in shops, in light industry and on farms, are within the scope of this standard. This standard is also applicable to timers for appliances within the scope of IEC 60335-1. This standard does not apply to timers designed exclusively for industrial applications.
31、 Throughout this standard, the word “equipment“ means “appliance and equipment“. 1.1.2 This standard applies to automatic electrical control devices, mechanically, electromechanically, electrically or electronically operated, responsive to or controlling parameters such as temperature, pressure, pas
32、sage or time, humidity, light, electrostatic effect, flow or liquid level. _ 1)IEC 60669-2-3:2006, Switches for household and similar fixed electrical installations Part 2-3: Particular requirements Time-delay switches (TDS) BS EN 60730-2-7:2010EN 60730-2-7:2010 (E) 4 1.1.3 This standard applies to
33、automatic electrical control devices serving the starting of small motors that are used principally in appliances and apparatus for household and similar purposes. Such control devices may be built into or be separate from the motor. 1.1.4 This standard applies to non-automatic control devices when
34、such are associated with automatic control devices. 1.2 Replacement: This standard applies to controls with a rated voltage not exceeding 690 V and a rated current not exceeding 63 A. 1.3 Replacement: This standard does not take into account the response value of an automatic action of a control, if
35、 such a response value is dependent upon the method of mounting the control in the equipment. If a response value is of significant purpose for the safety of the user or surroundings, the value defined in the appropriate household equipment standard or as determined by the manufacturer shall apply.
36、1.4 Replacement: This standard applies also to timers incorporating electronic devices, requirements for which are contained in Annex H. 1.5 Normative references This subclause of Part 1 applies except as follows: Addition: IEC 60669-1:1998, Switches for household and similar fixed-electrical instal
37、lations Part 1: General requirements 2)Amendment 1 (1999) Amendment 2 (2006) IEC 61010-1, Safety requirements for electrical equipment for measurement, control, and laboratory use Part 1: General requirements 2 Definitions This clause of Part 1 is applicable except as follows: 2.3 Definitions relati
38、ng to the function of controls Additional definition: 2.3.101 timing cycle program including all the switching activities involved in a start-to-finish operation of a controlled appliance _ 2)There exists a consolidated edition 3.2 (2007) that includes edition 3 and its Amendments 1 and 2. BS EN 607
39、30-2-7:2010EN 60730-2-7:2010 (E) 5 2.5 Definitions of types of control according to construction Additional definitions: 2.5.101 plug-in timer timer or time switch designed for direct plug-in to a socket-outlet NOTE The plug-in timer is equipped with conductor blades, pins or other means, protruding
40、 from the enclosure of the control or the control body itself, to match the dimensional parameters of the socket-outlet to which the control will be connected. 2.5.102 TV timer control for television equipment that can be set by the user, switching very high inrush currents of a very short duration
41、generated by electrical power supply components and associated electronic component parts with various electrical characteristics NOTE Examples are power transformers, electronic tube filaments, large electric capacitors and others in television receivers, radio and video products. 2.5.103 synchrono
42、us timer timer or a time switch in which the transmission is effected by a device that is time-based on the frequency of the power supply for the prime mover or the load 2.5.104 hand-wound timer timer or time switch in which the transmission is provided by actuation 3 General requirements This claus
43、e of Part 1 is applicable. 4 General notes on tests This clause of Part 1 is applicable except as follows: 4.1.4 Addition: 4.3.2.1 Addition: 5 Rating This clause of Part 1 is applicable. Text deleted Text deletedBS EN 60730-2-7:2010EN 60730-2-7:2010 (E) 6 6 Classification This clause of Part 1 is ap
44、plicable except as follows: 6.3 According to their purpose 6.3.6 Additional subclause: 6.3.6.101 TV timer; 6.4 According to features of automatic action 6.4.3 Additional subclauses: 6.4.3.101 a timing action which automatically resets upon loss of the electrical supply (Type 1.Q or 2.Q); 6.4.3.102 a
45、 timing action which is interrupted upon loss of the electrical supply and resumes at the point of interruption upon restoration of the electrical supply (Type 1.R or 2.R); 6.4.3.103 a timing action of a time switch which, after interruption of the electrical supply for any interval up to the declar
46、ed period of power reserve, resumes its intended operating sequence as if no interruption of the supply has occurred (Type 1.S or 2.S); 6.4.3.104 a timing action with a declared running accuracy in an ambient temperature of 20 C to 25 C (Type 1.T or 2.T); 6.4.3.105 a timing action in which the diffe
47、rence between set time and actual switching time does not exceed the declared amount (Type 1.U or 2.U). 6.5 According to the degree of protection and control pollution degree Additional subclause: 6.5.101 According to declared industrial environmental conditions (see IEC 61010-1): 6.10 According to
48、number of cycles of actuation (M) for each manual actuation Additional subclauses: 6.10.101 500 cycles; 6.10.102 2 500 cycles; 6.10.103 5 000 cycles. 6.15 According to construction Additional subclause: 6.15.101 plug-in timer. Text deletedBS EN 60730-2-7:2010EN 60730-2-7:2010 (E) 7 7 Information Thi
49、s clause of Part 1 is applicable except as follows: 7.2 Methods of providing information 7.2.9 Addition: Where symbols are used , for Type 1.S or 2.S actions, the power reserve is to be marked on the timer by the letter “R“, followed by the duration of the power reserve, followed by the symbol indicating the time unit as follows: minutes min hours h days d years a Table 7.2 Modification: Replace the lines corresponding to items 7, 26, 27 an