1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences ForUL 60335-1Safety of Household and Similar Appliances, Part 1: General RequirementsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PE
2、RMISSION FROM ULNational Differences ForUL 60335-1Safety of Household and Similar Appliances, Part 1: General RequirementsEdition: 5Edition Date: October 31, 2011UL 60335-1 is an adoption of IEC 60335-1, Safety Standard for of Household and SimilarElectrical Appliances, Part 1: General Requirements,
3、 (Edition 4.2, Issued by the IEC September2006). Please note that the national difference document incorporates all of the U.S. nationaldifferences for UL 60335-1.This document provides a single listing of the National Differences included in the UL adoption ofthe corresponding IEC standard.All righ
4、ts reserved. No part of this publication may be reproduced, stored in a retrieval system, ortransmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwisewithout prior permission of UL.UL provides this standards document as is without warranty of any kind, either
5、expressed or implied,including but not limited to, the implied warranties of merchantability or fitness for any purpose.In no event will UL be liable for any special, incidental, consequential, indirect or similar damages,including loss of profits, lost savings, loss of data, or any other damages ar
6、ising out of the use of or theinability to use this standards document, even if UL or an authorized UL representative has been advisedof the possibility of such damage. In no event shall ULs liability for any damage ever exceed the pricepaid for this standards document, regardless of the form of the
7、 claim.Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold ULharmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonableattorneys fees) resulting from any error or deviation introduced while purchaser is stori
8、ng an electronicStandard on the purchasers computer system.Copyright Underwriters Laboratories Inc.OCTOBER 31, 2011NATIONAL DIFFERENCES FOR UL UL 60335-12UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPrefaceThis document provides a single li
9、sting of the technical National Differences included in the UL adoptionof the corresponding IEC standard.In its IEC-based standards, UL uses the notations indicated below to identify national difference type, andthese types are additionally noted in this document. The standard may not use all types
10、of thesedeviations.D1 - These are deviations which are based on basic safety principles and requirements, elimination ofwhich would compromise safety for U.S. consumers and users of products.D2 - These are deviations based on safety practices. These are deviations for IEC requirements that maybe acc
11、eptable, but adopting the IEC requirements would require considerable retesting or redesign on themanufacturers part.DC - These are deviations based on the component standards and will not be deleted until a particularcomponent standard is harmonized with the IEC component standard.DE - These are de
12、viations based on editorial comments or corrections.DR - These are deviations based on the national regulatory requirements.Each national difference contains a description of what the national difference entails. Typically one of thefollowing words is used to explain how the text of the national dif
13、ference is to be applied to the base IECtext:Addition / Add - An addition entails adding a complete new numbered clause, subclause, table,figure, or annex. Addition is not meant to include adding select words to the base IEC text.Deletion / Delete - A deletion entails complete deletion of an entire
14、numbered clause, subclause,table, figure, or annex without any replacement text.Modification / Modify - A modification is an altering of the existing base IEC text such as theaddition, replacement or deletion of certain words or the replacement of an entire clause,subclause, table, figure, or annex
15、of the base IEC text.OCTOBER 31, 2011 NATIONAL DIFFERENCES FOR UL UL 60335-1 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences2DV.1 DR Addition:This standard is applicable to household and similar electrical appliances and
16、equipmentwhich are designed to be installed in accordance with relevant installation codes: NationalElectrical Code (NEC) ANSI/NFPA 70; or CSA C22.1 Canadian Electrical Code (CEC) Part I;or Mexican Electrical Installations NOM-001-SEDE.2DV.2 DC Addition:Certain IEC component standard requirements ar
17、e replaced by the relevant requirementsof component standards, examples of which are listed in Annex DVA.2DV.3 DR Addition:In Mexico, international standards are informative. For the relevant applicable standard ineach clause, see annex DVB.2DV.4 DE Addition:Add the following normative reference:ISO
18、 9773,Plastics Determination of burning behaviour of thin flexible vertical specimens in contactwith a small-flame ignition source3.4.1DV DR Modification to replace the definition with the following:EXTRA-LOW VOLTAGE: Voltage that does not exceed 30 V rms or 42,4 V peak ac or dc.3.4.2DV DR Modificat
19、ion to replace the first paragraph with the following:SAFETY EXTRA-LOW VOLTAGE: Voltage not exceeding 30 V rms or 42,4 V peak or 30 V dcbetween conductors and between conductors and earth. Where an appliance is intendedfor use immersed in water, SAFETY EXTRA-LOW VOLTAGE is 15 V rms or 21,2 V peak or
20、 15 V dc.3.6.4DV DE Modification to add the following note:NOTE 3 A LIMITED POWER SOURCE is not considered to be LIVE PARTS.3.10DV D2 Addition:LIMITED POWER SOURCE: A power source whose output voltage is SELV and the maximumoutput current and other parameters are limited in accordance with Table 3.1
21、0DV.1.OCTOBER 31, 2011NATIONAL DIFFERENCES FOR UL UL 60335-14UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 3.10DV.1 Limits for inherently LIMITED POWER SOURCESOutput voltage1)Output current2)Apparent power3)(UOC)(ISC) (S)V a.c. V d.c.
22、A VA 20 20 8,0 5 UOC200,2 and 3 0,5a3 and 6 0,756 and 10 10 0,82 (0,75)b10 and 13 15 1,30 (1,0)b13 and 16 17 1,5 (1,0)b16 and 25 30 2,525 and 32 432 and 40 640 and 63 10aThese cords may only be used if their length does not exceed 2 m between the point where the cord or cord guardenters the applianc
23、e and the entry to the plug.bCords having the cross-sectional areas indicated in the parentheses may be used for portable appliances if their lengthdoes not exceed 2 m.OCTOBER 31, 2011NATIONAL DIFFERENCES FOR UL UL 60335-112UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTI
24、ON WITHOUT PERMISSION FROM UL26.6DV.1 DR Modification:Replace the wording shown in Table 13 in the first paragraph by in accordance with thenational electrical codes.26.6DV.2 DR Deletion:Delete Table 13.27.2ADV D1 Addition:27.2ADV.1 If a fastener is intended to be used to secure a bonding conductor,
25、 it shall onlybe used for that purpose unless it is clear that it is unlikely to be removed or replacedduring servicing.27.2ADV.2 A single binding post may be used to secure both bonding conductors and theearthing conductor providing that the nut securing the earthing conductor is not relied onto se
26、cure the bonding conductors.27.5DV.1 D1 Modification to replace the 4th and 5th paragraph with 27.5DV.1.1 27.5DV.1.4 and Table 27.5DV:27.5DV.1.1 A current derived from a source having a no-load voltage not exceeding 12 V(a.c. or d.c.) and equal at least 2,0 times the rating of the earthed branch cir
27、cuit, is passedbetween the earthing terminal or earthing contact and each of the ACCESSIBLE METAL PARTS inturn.NOTE For the purpose of this requirement, the minimum rating of the branch circuit is 20Amps27.5DV.1.2 The voltage drop between the earthing terminal of the appliance or the earthingcontact
28、 of the appliance inlet and the ACCESSIBLE METAL PART is measured and shall not exceed4 volts.27.5DV.1.3 The resistance of the PROTECTIVE EARTHING CONDUCTOR is not included in themeasurement. However, if the PROTECTIVE EARTHING CONDUCTOR is supplied with the equipment,it may be included in the test
29、circuit, but the measurement of the voltage drop is made onlyfrom the main protective earthing terminal to the part required to be earthed.27.5DV.1.4 The resistance calculated from the current of this voltage drop shall not exceed0,1 ohm. The test duration is specified in Table 27.5DV.OCTOBER 31, 20
30、11 NATIONAL DIFFERENCES FOR UL UL 60335-1 13UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 27.5DV Earthing resistance test durationOver-current protection of branch circuit required forequipment (amps)Time (min)030 23160 461100 6101200
31、8201 and over 1027.5DV.2 D1 Modification:Delete Note 1.27.7DV D1 Addition of 27.7DV.1 27.7DV.1.8:27.7DV.1 Size of Protective Conductors27.7DV.1.1 PROTECTIVE EARTHING CONDUCTORS shall at least be of the same size as supplyconductors and shall comply with the minimum conductor sizes of column A of Tab
32、le27.7DV.1.2.1.27.7DV.1.2 Compliance is checked by inspection and measurement.Table 27.7DV.1.2.1 Minimum size of protective conductorsRATED CURRENT of the equipment underconsiderationMinimum conductor sizes AWG(mm2)Amperes A BPROTECTIVE EARTHING CONDUCTOR AWG (mm2) PROTECTIVE BONDING CONDUCTOR AWG (
33、mm2)Up to and including 10 18 (0,82) 20 (0,52)Over 10 up to and including 13 16 (1,31) 18 (0,82)Over 13 up to and including 18 14 (2,08) 16 (1,31)Over 18 up to and including 25 12 (3,.31) 14 (2,08)Over 25 up to and including 30 10 (5,26) 12 (3,31)Over 30 up to and including 40 8 (8,36) 10 (5,26)Over
34、 40 up to and including 55 6 (13,29) 8 (8,36)Over 55 up to and including 70 4 (21,14) 6 (13,29)Over 70 up to and including 95 2 (33,61) 4 (21,14)27.7DV.1.3 PROTECTIVE BONDING CONDUCTORS shall comply with the following:a) Shall pass the resistance test of 27.5, andb) Shall be no smaller than the mini
35、mum conductor sizes in column B of Table27.7DV.1.2.1; or for components only, be no smaller than the conductors thatsupply power to the component.OCTOBER 31, 2011NATIONAL DIFFERENCES FOR UL UL 60335-114UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION
36、FROM UL27.7DV.1.4 If the PROTECTIVE BONDING CONDUCTOR is smaller than the conductor supplying powerto the component, or smaller than the conductor size in column B of Table 27.7DV.1.2.1, ora printed conductor on a printed circuit board, the protective bonding path shalldemonstrate the ability to wit
37、hstand a limited short circuit.27.7DV.1.5 Compliance is determined by conducting the limited short circuit test specifiedin 27.7DV.1.6 and 27.7DV.1.7.27.7DV.1.6 The protective earthing path is connected to the supply circuit having acapacity in accordance with Table 27.7DV.1.8.1. The capacity is det
38、ermined without theprotective earthing path in the circuit. The supply voltage is the nominal voltage of the a.c.mains supply. The specified over-current PROTECTIVE DEVICE rated no less than specified in27.7DV.1.8 is connected in series with the protective earthing path.27.7DV.1.7 During the test, t
39、he protective earthing path shall not open and there shall beno damage to any insulation, the failure of which would result in contact between the earthpath and a LIVE PART. The integrity of the insulation is checked by the electric strength testof 16.1 by applying the test between LIVE PART and ear
40、thed parts.27.7DV.1.8 The current rating of the overcurrent PROTECTIVE DEVICE shall be the smallest of thefollowing:a) The current rating of the attachment plug but not less than 20 A; orb) The rating of an overcurrent PROTECTIVE DEVICE which is specified by themanufacturer for installation in the f
41、ield to protect the equipment; orc) The rating of an overcurrent PROTECTIVE DEVICE in the equipment that protects thecircuit or part required to be earthed.Table 27.7DV.1.8.1 Short circuit capacity for the limited short circuit testMaximum rating of the applianceHorsepower (W)Volt-amperessingle-phas
42、eVolt-amperes3-phaseVolt-amperesdirect current VoltsCircuit capacity inamperes0 1 176 0 832 0 648 0,5 max (373) 0 250 2000 1 176 0 832 0 648 0,5 max (373) 251 600 1 0001 177 1 920 833 1 496 649 1 140 0,5 (373) to 1(746)0 600 1 0001 921 4 080 1 497 3 990 1 141 3 000 1 (746) to 3 (2200)0 250 2 0004 08
43、1 9 600 3 991 9 145 3 001 6 960 3 (2 200) to 7,5 (5600)0 250 3 5009 601 or higher 9 146 or higher 6 961 or higher 7,5 (5 600) 0 250 5 0001 921 or higher 1 497 or higher 1 141 or higher 1 (746) 251 600 5 00028.2DV D1 Modification:Delete the paragraph after the note and before the compliance statement
44、.OCTOBER 31, 2011 NATIONAL DIFFERENCES FOR UL UL 60335-1 15UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL28.5DV D1 Addition of 28.5DV.1 28.5DV.4:28.5DV.1 Pillar, stud, or screw type protective earthing and protective bonding terminalsshall c
45、omply with the minimum size requirements of Table 28.5DV.1.1.Table 28.5DV.1.1- Sizes of terminals for PROTECTIVE EARTHING CONDUCTORSRated Current of Equipment Minimum Nominal Thread Diameter mmA Pillar Type or Stud Screw TypeUp to and Including 10 3,0 3,5Over 10 up to and including 16 3,5 4,0Over 16
46、 up to and including 25 4,0 5,0Over 25 up to and including 32 4,0 5,0Over 32 up to and including 40 5,0 5,0Over 40 up to and including 63 6,0 6,028.5DV.2 Protective bonding terminals which do not comply with Table 28.5DV.1.1 areconsidered acceptable if they meet the requirements of 27.7DV.1.5.28.5DV
47、.3 The main protective earthing terminal for permanently connected equipmentshall be provided with factory installed studs, screws, or bolts, together with the necessaryhardware, if requiring a PROTECTIVE EARTHING CONDUCTOR larger than 10 AWG.28.5DV.4 Compliance is checked by inspection and measurem
48、ent.29.1DV.1 D1 Modification to add a 4th row to Table 15 with the following values:300 and 480,4000, 29.1DV.2 D1 Modification to add the following footnote “d” to Table 16:dThe clearances at terminals for the connection of field wiring are increased to 6,4 mm forrated impulse voltage of 1 500 V and
49、 9,5 mm for rated impulse voltages of 2 500 and 4 000V.29.1DV.3 D1 Modification to change the fourth line of Table 16 to the following:1 500, 1,2c,d29.1DV.4 D1 Modification to change the sixth line of Table 16 to the following:4 000, 3,529.2DV.1 D1 Modification to add superscript “b” to title of Table 17 and add thefollowing footnote:bThe creepage distances at terminals for the connection of field wiring are increased to9,5 mm for working voltages 250 volts, and 12,7 mm for vol