1、Designation: F2536 17 An American National StandardStandard Guide forInstalling Plastic DWV Piping Suspended from On-GradeSlabs1This standard is issued under the fixed designation F2536; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisi
2、on, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This guide provides procedures for the installation ofDWV piping in buildings that are built where so
3、il conditionsrequire the use of pier or piling supported grade beamconstruction or in filled ground where the soil compaction isless than 95 %. These procedures are intended to ensure thatthe DWV piping suspended from the on grade concrete slabs isnot damaged or destroyed by movement of the soil or
4、fill underthe slab after the building is completed and occupied.1.2 In this type of construction, the area within the gradebeams is filled with soil up to a level that allows the concreteslab to be poured directly on the fill without a supporting form.In this process the sanitary waste piping is ins
5、talled bytrenching into the fill, and then putting hangers with supportrods on the pipes as they are installed. The hanger rodsextending upward must be long enough so that the top of therod will be embedded in and anchored in the concrete.1.3 The hanger rods are intended to provide adequatestrength
6、and corrosion resistance to assure long term service.1.4 The details of installation are intended to ensure that therods remain vertical, that they extend into the concrete anadequate amount and that the upper ends are terminated so thatthey have adequate “pull out” strength.1.5 The details of backf
7、ill are intended to limit or minimizethe loads on the a suspended piping. These loads result fromconsolidation or movement of the soil/fill beneath the slab.1.6 The values stated in inch-pound units are to be regardedas standard. No other units of measurement are included in thisstandard.1.7 This st
8、andard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limitations prior to use.1.8 This i
9、nternational standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TB
10、T) Committee.2. Referenced Documents2.1 ASTM Standards:2D653 Terminology Relating to Soil, Rock, and ContainedFluidsD2665 Specification for Poly(Vinyl Chloride) (PVC) PlasticDrain, Waste, and Vent Pipe and FittingsF412 Terminology Relating to Plastic Piping Systems3. Terminology3.1 GeneralDefinition
11、s used in this guide are in accor-dance with Terminologies in F412 and D653 unless otherwiseindicated.3.2 Definitions of Terms Specific to This Standard:3.2.1 grade beamsconcrete beams around the perimeter ofa building and within the building. They support the slabs, theexterior walls and interior b
12、earing walls.3.2.2 piers suspended DWV; underslabTABLE 1 Hanger RodsPipe Sizes Minimum Rod Size2 and smaller38 in.3 and 412 in.658 in.8 and larger34 in.F2536 172SUMMARY OF CHANGESCommittee F17 has identified the location of selected changes to this standard since the last issue (F2536 06b(2011) that
13、 may impact the use of this standard.(1) 7.2.2, reworded.(2) 8.1, reworded and removed verification procedure.(3) 8.2, reworded.ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are
14、 expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not r
15、evised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you
16、 may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United
17、States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http:/ 1 Load Limiting MethodsF2536 173