1、NEMA Standards PublicationNational Electrical Manufacturers AssociationANSI/NEMA WD 6-2016Wiring Devices - Dimensional SpecificationsApproved as an American National Standard ANSI Approval Date: February 11, 2016 ANSI/NEMA WD 6-2016 Wiring Devices - Dimensional Specifications Published by National E
2、lectrical Manufacturers Association 1300 North 17th Street, Suite 900 Rosslyn, Virginia 22209 www.nema.org 2016 National Electrical Manufacturers Association All rights reserved including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention for th
3、e Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions. NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was
4、 developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document. The National Electrical Manufacturers Association (NEMA) standards and guideline publications, of which the document contained herein is one, are de
5、veloped through a voluntary consensus standards development process. This process brings together volunteers and/or seeks out the views of persons who have an interest in the topic covered by this publication. While NEMA administers the process and establishes rules to promote fairness in the develo
6、pment of consensus, it does not write the document and it does not independently test, evaluate, or verify the accuracy or completeness of any information or the soundness of any judgments contained in its standards and guideline publications. NEMA disclaims liability for any personal injury, proper
7、ty, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or warranty, expressed or implied, as to the accura
8、cy or completeness of any information published herein, and disclaims and makes no warranty that the information in this document will fulfill any of your particular purposes or needs. NEMA does not undertake to guarantee the performance of any individual manufacturer or sellers products or services
9、 by virtue of this standard or guide. In publishing and making this document available, NEMA is not undertaking to render professional or other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed by any person or entity to someone else. Anyone using th
10、is document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. Information and other standards on the topic covered by this publication may be available from oth
11、er sources, which the user may wish to consult for additional views or information not covered by this publication. NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this document. NEMA does not certify, test, or inspect products, designs, or installations
12、 for safety or health purposes. Any certification or other statement of compliance with any health or safety-related information in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker of the statement. ANSijNEMA WD 6-2016 Page i TABLE OF CONTENT
13、S Foreword _ _ Scope _ _ Introduction -Marking symbol for automatically controlled receptacles _ _ Di mensiona I specifications for wa II plates -Dimensional specifications for wallplates used on 347V switch devices _ _ Wallplates mounting and cut-outs dimensions -Wallplate dimensions for round face
14、 devices. _ _ Wall plate dimensions for rectangular face devices _ _ Wall plate dimensions for telephone devices _ _ Wallplate dimensions for toggle switch devices. _ _ Yoke dimensions of receptacles and switches for box mounting _ _ Yoke dimensions for 2-gang receptacles mounting “on and off center
15、 face“ type _ _ Dimensions for flush mount duplex devices: receptacles, combo switches, etc _ _ Dimensions for rectangular face devices: receptacles, switches, excluding GFCI, etc _ _ Dimensions for rectangular face devices with protruding actuators, switch toggles _ _ Dimensions for round and recta
16、ngular face single devices _ _ Dimensions for interchangeable type: single, duplex, and triplex devices _ _ Wiring device maximum envelope dimension _ _ Dimensions for flanged inlets and connector bodies -Flat blade hole locations general information _ _ II Ill . IV v 1 2 3 4 5 6 7 8 9 10 11 12 13 1
17、4 15 16 17 Drawings of NEMA configurations for non-locking plugs and receptacles _ _ Drawings of NEMA configurations for locking plugs and receptacles _ _ 18 to 63 64 to 132 Drawings of NEMA configurations for specific purpose plugs and receptacles _ _ 133 to 142 Configurations Chart of NEMA non-loc
18、king plugs and receptacles _ _ Configurations Chart of NEMA locking plugs and receptacles _ _ Configurations Chart of NEMA specific purpose plugs and receptacles. _ _ 2016 National Electrical Manufacturers Association 143 144 145 ANSijNEMA WD 6-2016 Page ii FOREWORD The purpose of these Standard is
19、to present the dimensional requirements of wiring devices in order to assist the user in selecting and obtaining the proper product for a particular need and to minimize the possibility of unsafe interchangeability between configurations. In the preparation of this Standard Publication, input of use
20、rs and other interested parties has been sought and evaluated. User input will be formally sought by the canvas procedures of the American National Standards Institute. Proposed or recommended revision should be submitted to: Senior Technical Director, Operations National Electrical Manufacturers As
21、sociation 1300 North 17th Street Rosslyn, Virginia 22209 Publication ANSI/NEMA WD 6-2016 revises and supersedes previous publication: ANSI/NEMA WD 6-2002 (R2008), and ANSI/NEMA WD 6-2012. 2016 National Electrical Manufacturers Association SCOPE ANSijNEMA WD 6-2016 Page iii This standard covers dimen
22、sional requirements for plugs and receptacles rated up to 60 Ampere and 600 Volts. It also includes dimensions for wall plates. Also included is the recommended marking for automatically controlled receptacles. 2016 National Electrical Manufacturers Association ANSijNEMA WD 6-2016 Page iv INTRODUCTI
23、ON Throughout this publication the following shall apply: 1) All dimensions are in inches, unless otherwise specified. 2) Decimal dimensions without tolerances shall be subject to a 0.005 inch tolerance. 3) Angular dimensions without tolerances shall be subject to a 1 degree tolerance. 4) “G“ denote
24、s equipment ground. 5) “W“ denotes system ground. 6) Leading edges of plug blades shall be free of burrs and sharp edges. 7) All slots and slot tolerances are symmetrically located about centerlines. 8) Female contacts associated with plug blades that are 0.125 inch minimum longer than other blades,
25、 are engaged prior to the other female contacts. 9) Configurations utilized on alternating current systems, are limited to 50 or 60 Hertz, unless otherwise specified. 10) Dimensions shown in these standards are for the purpose of interchangeability, and do not preclude other designs. 11) The electri
26、cal ratings of the configurations in these standards are AC and DC, unless specifically stated “AC“ or “DC“. 2016 National Electrical Manufacturers Association ANSijNEMA WD 6-2016 Page v MARKING FOR AUTOMATICALLY CONTROLLED RECEPTACLES The following marking is recommended by NEMA to indicate recepta
27、cles or parts of multi-outlet receptacles that are controlled by a system, a device, or incorporate features that remove power from the outlet for the purpose of energy management or building automation. The control could be an energy management system, timer or sensor. The marking is not intended f
28、or other devices such as GFCI or a fused or temperature controlled device intended to interrupt power for safety reasons unless the device is also part of a control system. The marking is optional for receptacles controlled by a manually operated wall switch as permitted by code to provide the requi
29、red room lighting outlets. MARKING FOR CONTROLLED RECEPTACLES The purpose of the marking is to instruct the user that the outlet may be subject to unattended switching and to take this into consideration when attaching a plugged-in appliance or other load. Thus it is important to be able to readily
30、identify receptacle outlets that will be powered on and off. The mark may be located either on or close to the controlled receptacle. The mark shall be located such that it clearly identifies the controlled receptacles outlet after installation. The marking may be required by a product standard, an
31、installation code or a similar document. 2016 National Electrical Manufacturers Association This page intentionally left blank - -DIMENSIONAL SPECIFICATION FOR WALLPLATES 1-I I I -r -( B ) -t-I I I - - I ANSI/NEMA WD 6-2016 Page 1 -+-+-4- ( C ) See note 1 1.812 .010 NOTES: Single-gang wallplate over
32、all dimensions REFERENCE MATERIAL A ALL B ALL Multigang wallplate horizontal hole spacing (For vertical hole spacing see page 3) STANDARD DIMENSIONS MIN MAX 2.740 -4.490 -1. The depth is defined in accordance to the applicable installation code by the authority having jurisdiction. Decorative contou
33、rs should not preclude the flush seating of a plug into a receptacle. 2. Plate mounting holes to be counter-sunk for # 6-32 UNC, oval head machine screw. 3. Ribs are optional on non-metallic plates. Height, width, and location of ribs shall clear device for which the plate is designed or intended fo
34、r use. 2016 National Electrical Manufacturers Association ANSI/NEMA WD 6-2016 Page 2 - -DIMENSIONAL SPECIFICATIONS FOR WALLPLATES USED ON 347V SWITCH DEVICES I I 1-I I I I -r -( B ) -+-I I I - I I I I I ( C ) See note 1 1.812 .010 NOTES: Single-gang wallplate overall dimensions REFERENCE MATERIAL A
35、ALL B ALL Multigang wallplate horizontal hole spacing (For vertical hole spacing see page 3) STANDARD DIMENSIONS MIN MAX 3.120 -4.870 -1. The depth is defined in accordance to the applicable installation code by the authority having jurisdiction. Decorative contours should not preclude the flush sea
36、ting of a plug into a receptacle. 2. Plate mounting holes to be counter-sunk for # 6-32 UNC, oval head machine screw. 3. Ribs are optional on non-metallic plates. Height, width, and location of ribs shall clear device for which the plate is designed or intended for use. 2016 National Electrical Manu
37、facturers Association ! M Ltl . r-1 ANSI/NEMA WD 6-2016 Page 3 MOUNTING AND CUT-OUTS DIMENSIONS r 0 r-1 0 . -H r-1 CX) N . M l_ - I I - - -I I -+ I I Box mount blank plate (See note 3) Ltl N r-1 . r-1 X N -I -+-+- I I -+-1/ I I 2X 01.343 -_; Duplex device NOTES: 0 r-1 0 . -H N r-1 CX) . M L -1 v v C
38、X) . r-1 0 r-1 0 . -H Ltl “ M . N I - -I _ _j I I Yoke mount blank plate (See note 3) - - - r -t j r - -I -t- ) , I - j I - -qf -r- v “ 0 . X M 3X 0.916 Interchangeable device I _J 0 I -ffi-r-1 0 . -H N I N - -Ltl 01 r “ “ . -M . y N - I I 2X 0.515 MIN Two button push switch 1. Plate mounting holes
39、to be counter-sunk for # 6-32 UNC, oval head machine screw. 2. Ribs are optional on non-metallic plates. Height, width, and location of ribs shall clear device for which the plate is designed or intended for use. 3. Blank plates may be provided with knock-outs. 2016 National Electrical Manufacturers
40、 Association ANSI/NEMA WD 6-2016 Page 4 WALLPLATE DIMENSIONS FOR ROUND FACE DEVICES 0 T“IV CIJ +1 +I 0 c L/)CIJ “w U) N t -I I I u “I- co E ca II c -E Q ANSI/NEMA WD 6-2016 Page 17 FLAT BLADE HOLE LOCATIONS GENERAL INFORMATION 0.125 HOLE 45 CSK .156 DIA BOTH SIDES 0.156 HOLE Hole location 1 LJ) T“-1
41、 0 +I v 1.0 v . I H -./ I I I I I I Hole location 2 BLADE HOLE LOCATION CHART CONFIGURATIONS USING HOLE LOCATION 1 1-15, 2-15, 5-15, 6-15, 7-15, 11-15, 14-15, 15-15, 18-15, 24-15 LJ) T“-1 0 . +I (“) v 00 1-20, 2-20, 5-20, 5-20ALT, 6-20, 6-20ALT, 7-20, 10-20, 11-20, 14-20, 15-20, 18-20, 24-20 CONFIGU
42、RATIONS USING HOLE LOCATION 2 1-30, 2-30, 5-30, 6-30, 7-30, 10-30, 11-30 14-30, 15-30, 18-30, 24-30 5-50 6-50 7-50 10-50 11-50 14-50 15-50 18-50 24-50 , , , , , , , , 14-60, 15-60, 18-60 NOTE: Hole in flat blade is optional, and is intended for manufacturing purposes only. However if used it must be located as per dimensions shown above. 2016 National Electrical Manufacturers Association