1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 13141-2:2010Ventilation for buildings Performance testing ofcomponents/products forresidential ventilationPart 2: Exhaust and supply air terminaldevicesBS EN 13141-2:2010 B
2、RITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 13141-2:2010.It supersedes BS EN 13141-2:2004 which is withdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee RHE/2, Ventilation for buildings, heating and hot waterservices.A list of
3、organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2010ISBN 978 0 580 61453 8ICS 91.140.30Compliance with a British Standa
4、rd cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2010.Amendments issued since publicationDate Text affectedBS EN 13141-2:2010EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13141
5、-2 July 2010 ICS 91.140.30 Supersedes EN 13141-2:2004English Version Ventilation for buildings - Performance testing of components/products for residential ventilation - Part 2: Exhaust and supply air terminal devices Ventilation des btiments - Essais des performances des composants/produits pour la
6、 ventilation des logements - Partie 2: Bouches dair dvacuation et dalimentation Lftung von Gebuden - Leistungprfungen von Bauteilen/Produkten fr die Lftung von Wohnungen - Teil 2: Abluft- und Zuluftdurchlsse This European Standard was approved by CEN on 22 April 2010. CEN members are bound to comply
7、 with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Managemen
8、t Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the o
9、fficial versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
10、Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved world
11、wide for CEN national Members. Ref. No. EN 13141-2:2010: EBS EN 13141-2:2010EN 13141-2:2010 (E) 2 Contents Page Foreword 31 Scope 62 Normative references 63 Terms and definitions . 74 Performance testing of aerodynamic characteristics 74.1 Flow rate/pressure . 74.1.1 Principle 74.1.2 Test installati
12、on, conditions and uncertainty of measurement 74.1.3 Test procedure . 94.1.4 Analysis of results . 104.1.5 Presentation of results 104.2 Air diffusion characteristics for supply air terminal devices 105 Performance testing of acoustic characteristics . 105.1 Noise production for components of system
13、s . 105.1.1 General 105.1.2 Test installation 105.1.3 Test procedure . 125.1.4 Acoustic measurement . 135.1.5 Presentation of results 145.2 Insertion loss of component of systems . 145.2.1 General 145.2.2 Test procedure . 145.2.3 Preparation and mounting of the test samples 165.2.4 Procedure . 165.2
14、.5 Control of the limiting insertion loss . 185.2.6 Calculations 185.2.7 Expression of results 195.3 Sound insulation characteristics of a pair of air terminal devices . 195.3.1 General 195.3.2 Testing without airflow 215.3.3 Testing with airflow . 215.3.4 Conditions for measuring background noise .
15、 215.3.5 Presentation of the results . 22Bibliography 23BS EN 13141-2:2010EN 13141-2:2010 (E) 3 Foreword This document (EN 13141-2:2010) has been prepared by Technical Committee CEN/TC 156 “Ventilation for buildings”, the secretariat of which is held by BSI. This European Standard shall be given the
16、 status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2011, and conflicting national standards shall be withdrawn at the latest by January 2011. Attention is drawn to the possibility that some of the elements of this document may be th
17、e subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 13141-2:2004. The position of this European Standard in the field of the mechanical building services is shown in Figure 1. BS EN 13141-2:2010EN 131
18、41-2:2010 (E) 4 Mechanical Building Services Control systems Ventilation and air conditioning systems Heating systems Ductwork Air terminal devices Air handling units Mechanical and natural residential ventilation Design criteria for the indoor environment System performance Installation Components/
19、products for residential ventilation Required and optional performance characteristics Performance testing of components/products for residential ventilation Simplified calculation methods for residential ventilation systems Design and dimensioning for residential ventilation systems Performance tes
20、ting and installation checks for residential ventilation systems Part 1: Externally and internally mounted air transfer devices Part 2: Exhaust and supply air terminal devices Part 3: Range hoods for residential use Part 4: Fans used in residential ventilation systems Part 5: Cowls and roof outlet t
21、erminal devices Part 6: Exhaust ventilation system packages used in a single dwelling Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation systems intended for single family dwellings Part 8: Performance testing of un-d
22、ucted mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation systems intended for a single room Part 9: Externally mounted humidity controlled air transfer device Part 10: Humidity controlled extract air terminal device Figure 1 Position of EN 13141-2 in
23、 the field of the mechanical building services BS EN 13141-2:2010EN 13141-2:2010 (E) 5 According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
24、Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 13141-2:2010EN 13141-2:2010 (E) 6 1 Scope
25、 This European Standard specifies laboratory methods for testing exhaust and supply air terminal devices operating under pressure differences. It applies to devices used in mechanical and natural residential ventilation systems, of the following types: device with a manually adjustable opening; or d
26、evice with a fixed opening; or pressure difference controlled device. It describes tests intended to characterize: flow rate/pressure; air diffusion characteristics (for supply air terminal devices); noise production for components of systems; insertion loss of component of systems; sound insulation
27、. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1506, Ventilation for
28、 buildings Sheet metal air ducts and fittings with circular cross-section Dimensions EN 12238, Ventilation for buildings Air terminal devices Aerodynamic testing and rating for mixed flow application EN 12792:2003, Ventilation for buildings Symbols, terminology and graphical symbols EN 13141-1:2004,
29、 Ventilation for buildings Performance testing of components/products for residential ventilation Part 1: Externally and internally mounted air transfer devices EN ISO 140-3, Acoustics Measurement of sound insulation in buildings and of building elements Part 3: Laboratory measurements of airborne s
30、ound insulation of building elements (ISO 140-3:1995) EN ISO 3741, Acoustics Determination of sound power levels of noise sources using sound pressure Precision methods for reverberation rooms (ISO 3741:1999, including Cor 1:2001) EN ISO 5135, Acoustics Determination of sound power levels of noise f
31、rom air-terminal devices, air-terminal units, dampers and valves by measurement in a reverberation room (ISO 5135:1997) EN ISO 11691:2009, Acoustics Measurement of insertion loss of ducted silencers without flow Laboratory survey method (ISO 11691:1995) EN ISO 7235:2009, Acoustics Laboratory measure
32、ment procedures for ducted silencers and air-terminal units Insertion loss, flow noise and total pressure loss (ISO 7235:2003) BS EN 13141-2:2010EN 13141-2:2010 (E) 7 ISO 5221, Air distribution and air diffusion Rules to methods of measuring air flow rate in an air handling duct 3 Terms and definiti
33、ons For the purposes of this document, the terms and definitions given in EN 12792:2003 and the following apply. 3.1 insertion loss reduction in sound pressure level in the reverberation room due to the mounting of the air terminal device 3.2 test duct straight, rigid hard-walled duct of constant cr
34、oss section between sound source and air terminal device 3.3 reverberation room room specially designed to facilitate the production of approximately diffuse sound fields 3.4 background noise noise emitted by the whole sources other than the source under testing 4 Performance testing of aerodynamic
35、characteristics 4.1 Flow rate/pressure 4.1.1 Principle This test consists of measuring several volume flow rates induced through a device by the applied static pressure difference to define the flow rate/pressure characteristic curve in the operating range specified by the manufacturer. In the case
36、of manually adjustable devices this test shall be carried out at maximum and minimum opening conditions specified by the manufacturer. Some exhaust ATD are of the bi-function type, i.e. they are designed to work under both natural and mechanical ventilation system. In that case the manufacturer may
37、have to specify two operational ranges, and the device shall be tested for each of them according the standard procedure. 4.1.2 Test installation, conditions and uncertainty of measurement 4.1.2.1 Test installation and conditions The device to be tested shall be installed in accordance with Figure 2
38、a) for exhaust air terminal device or Figure 2b) for supply air terminal device. The test installation shown in Figure 2a) and Figure 2b) comprises: a test duct with an airflow meter, a static pressure gauge and an airflow straightener in accordance with ISO 5221. Other measurement devices may be us
39、ed, provided they allow measurements with an uncertainty in accordance with 4.1.2.2; a fan with means to vary the pressure difference across the device, covering the range of Table 1 given in 4.1.3. NOTE In order to avoid pumping effect, an adequate device may be added after the airflow meter. BS EN
40、 13141-2:2010EN 13141-2:2010 (E) 8 The test facilities shall have a range: for extraction: 300 Pa to 0 Pa; for supply: 0 Pa to + 300 Pa. The air terminal device shall be mounted in a test duct with cross-sectional dimensions equal to the nominal size of the device or to the duct dimensions normally
41、recommended by the manufacturer. For supply only, the duct shall be straight and at least 20 Delong to guarantee a uniform velocity profile or shall include an efficient flow straightener located at a position at least 3 Defrom any part of the air terminal device. It is recommended that straightener
42、 cells have an axial length at least equal to six times the hydraulic diameter of their cross-section. a) For exhaust air terminal device b) For supply air terminal device Key 1 airflow 7 flow straightener 2 airflow meter 8 connection to fan, flowrate control and airflow meter 3 plane of temperature
43、 measurement 9 transition to test duct size 4 plane of pressure measurement 10 plane of pressure measurement 5 air terminal device 11 signal to display or computer 6 test duct, diameter De12 with flow straightener 13 without flow straightener Figure 2 Test installation for exhaust air terminal devic
44、e (Figure 2a) and supply air terminal device (Figure 2b) 4.1.2.2 Uncertainty of measurement In the case of air terminal devices with pressure difference controlled openings: the pressure shall be measured with an uncertainty lower than: (Pa) value)(measured 0,03 0,2 + (1) the volume flow rate shall
45、be measured with an uncertainty lower than: BS EN 13141-2:2010EN 13141-2:2010 (E) 9 )(l value)(measured 0,03 0,31+ s (2) For other air terminal devices: the pressure shall be measured with an uncertainty lower than: (Pa) value)(measured 0,03 0,5 + (3) the volume flow rate shall be measured with an u
46、ncertainty lower than: )(l value)(measured 0,03 0,31+ s (4) NOTE The combined uncertainties of measurement will result in a total accuracy of the test method in the range of 3 % to 5 %. 4.1.3 Test procedure The measurements shall be taken for six points, each taken within one of the pressure differe
47、nce ranges (bands) given in Table 1 so as to match with / cover the operational range of the device as stated by the manufacturer. Table 1 Pressure difference ranges Pressure difference p Pa 3 to 4 4 to 6 6 to 8 8 to 10 13 to 18 18 to 24 24 to 32 32 to 42 42 to 55 55 to75 75 to 100 100 to 130 130 to
48、 170 170 to 225 225 to 300 The environmental conditions existing during the tests such as temperature, barometric pressure shall be recorded. Air temperature ashall be (20 5) C. During the test, temperature ashall not vary more than 2 C. The test shall be carried out by continuously increasing the p
49、ressure difference across the device. BS EN 13141-2:2010EN 13141-2:2010 (E) 10 For pressure difference controlled devices, a first series of measurement shall be made with continuously increasing the pressure difference, then a second with continuously decreasing it. At each point the couple (pressure difference p, volume flow rate