1、BRITISH STANDARDBS EN 15004-2:2008Fixed firefighting systems Gas extinguishing systems Part 2: Physical properties and system design of gas extinguishing systems for FK-5-1-12 extinguishantICS 13.220.20g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g
2、40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58BS EN 15004-2:2008This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 2008Novemer BSI 2008ISBN 978 0 580 59942 2National forewordThis British
3、 Standard is the UK implementation of EN 15004-2:2008. It supersedes BS ISO 14520-5:2006 which is withdrawn.The UK participation in its preparation was entrusted by Technical Committee FSH/18, Fixed fire fighting systems, to Subcommittee FSH/18/6, Gaseous extinguishing media and systems.A list of or
4、ganizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obliga
5、tions.Amendments/corrigenda issued since publicationDate CommentsEUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 15004-2June 2008ICS 13.220.20English VersionFixed firefighting systems - Gas extinguishing systems - Part 2:Physical properties and system design of gas extinguishingsystems for FK-5-1-
6、12 extinguishant (ISO 14520-5:2006,modified)Installations fixes de lutte contre lincendie - Installationsdextinction gaz - Partie 2 : Proprits physiques et conception des systmes pour agent extincteur FK-5-1-12 (ISO 14520-5:2006, modifie)Ortsfeste Brandbekmpfungsanlagen - Lschanlagen mitgasfrmigen L
7、schmitteln - Teil 2: PhysikalischeEigenschaften und Anlagenauslegung fr FeuerlschmittelFK-5-1-12 (ISO 14520-5:2006, modifiziert)This European Standard was approved by CEN on 26 April 2008.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giv
8、ing this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versi
9、ons (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bu
10、lgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDI
11、ZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2008 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15004-2:2008: EEN 15004-2:2008 (E) 2 Contents Page Foreword
12、3 Foreword of ISO 14520-5:2006 5 1 Scope 6 2 Normative references 6 3 Terms and definitions .6 4 Characteristics and uses 6 4.1 General6 4.2 Use of FK-5-1-12 systems .7 5 Safety of personnel9 6 System design10 6.1 Fill density 10 6.2 Superpressurization 12 6.3 Extinguishant quantity 12 BS EN 15004-2
13、:2008EN 15004-2:2008 (E) 3 Foreword This document (EN 15004-2:2008) has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting systems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identica
14、l text or by endorsement, at the latest by December 2008, and conflicting national standards shall be withdrawn at the latest by December 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held r
15、esponsible for identifying any or all such patent rights. The text of the International Standard ISO 14520-5:2006 from Technical Committee ISO/TC 21 “Equipment for fire protection and fire fighting“ of the International Organization for Standardization (ISO) has been taken over as a European Standar
16、d by Technical Committee CEN/TC 191 “Fixed firefighting systems“, the secretariat of which is held by BSI, with common modifications which are indicated by a straight line in the margin of the text. This European Standard will consist of the following parts, under the general title Fixed firefightin
17、g systems Gas extinguishing systems: Part 1: Design, installation and maintenance (ISO 14520-1, modified) Part 2: Physical properties and system design of gas extinguishing systems for FK-5-1-12 extinguishant (ISO 14520-5, modified) Part 3: Physical properties and system design of gas extinguishing
18、systems for HCFC Blend A extinguishant (ISO 14520-6, modified) Part 4: Physical properties and system design of gas extinguishing systems for HFC 125 extinguishant (ISO 14520-8, modified) Part 5: Physical properties and system design of gas extinguishing systems for HFC 227ea extinguishant (ISO 1452
19、0-9, modified) Part 6: Physical properties and system design of gas extinguishing systems for HFC 23 extinguishant (ISO 14520-10, modified) Part 7: Physical properties and system design of gas extinguishing systems for IG-01 extinguishant (ISO 14520-12, modified) Part 8: Physical properties and syst
20、em design of gas extinguishing systems for IG-100 extinguishant (ISO 14520-13, modified) Part 9: Physical properties and system design of gas extinguishing systems for IG-55 extinguishant (ISO 14520-14, modified) Part 10: Physical properties and system design of gas extinguishing systems for IG-541
21、extinguishant (ISO 14520-15, modified) The International Standards ISO 14520-2 and ISO 14520-11, which dealt with CF3I and HFC 236fa extinguishants, respectively, have not been implemented by CEN, as CF3I extinguishant is only valid for local BS EN 15004-2:2008EN 15004-2:2008 (E) 4 application and H
22、FC 236fa extinguishant is only applicable for portable fire extinguishers and local application, respectively, which is not covered by the scope. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European St
23、andard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdo
24、m. BS EN 15004-2:2008EN 15004-2:2008 (E) 5 Foreword of ISO 14520-5:2006 ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies (ISO member bodies). The work of preparing International Standards is normally carried out through ISO technical com
25、mittees. Each member body interested in a subject for which a technical committee has been established, has the right to be represented on that committee. International organizations, governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with th
26、e International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization. International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2. The main task of technical committees is to prepare International Standards. Draft Internati
27、onal Standards adopted by the technical committees are circulated to the member bodies for voting. Publication as an International Standard requires approval by at least 75 % of the member bodies casting a vote. Attention is drawn to the possibility that some of the elements of this document may be
28、the subject of patent rights. ISO shall not be held responsible for identifying any or all such patent rights. ISO 14520-5 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting, Subcommittee SC 8, Gaseous media and firefighting systems using gas. ISO 14520 co
29、nsists of the following parts, under the general title Gaseous media fire extinguishing systems Physical properties and system design: Part 1: General requirements Part 2: CF3I extinguishant Part 5: FK-5-1-12 extinguishant Part 6: HCFC Blend A extinguishant Part 8: HFC 125 extinguishant Part 9: HFC
30、227ea extinguishant Part 10: HFC 23 extinguishant Part 11: HFC 236fa extinguishant Part 12 IG-01 extinguishant Part 13: IG-100 extinguishant Part 14: IG-55 extinguishant Part 15: IG-541 extinguishant Parts 3, 4 and 7, which dealt with FC-2-1-8, FC-3-1-10 and HCFC 124 extinguishants, respectively, ha
31、ve been withdrawn, as these types are no longer manufactured. BS EN 15004-2:2008EN 15004-2:2008 (E) 6 1 Scope This document gives specific requirements for gaseous fire-extinguishing systems, with respect to the FK-5-1-12 extinguishant. It includes details of physical properties, specification, usag
32、e and safety aspects and is applicable to systems operating at nominal pressures of 25 bar and 42 bar with nitrogen propellant. This does not preclude the use of other systems. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated
33、 references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 15004-1:2008, Fixed firefighting systems Gas extinguishing systems Part 1: Design, installation and maintenance (ISO 14520-1, modified) 3 Terms an
34、d definitions For the purposes of this document, the terms and definitions given in EN 15004-1:2008 apply. 4 Characteristics and uses 4.1 General Extinguishant FK-5-1-12 shall comply with the specification according to Table 1. FK-5-1-12 is a clear, colourless, almost odourless, electrically non-con
35、ductive gas with a density approximately 11 times that of air. The physical properties are given in Table 2. FK-5-1-12 extinguishes fires mainly by physical means, but also by some chemical means. Table 1 Specification for FK-5-1-12 Property Requirement Purity 99,6 % (mol/mol), min. Acidity 3 106by
36、mass, max. Water content 0,001 % by mass, max. Non-volatile residue 0,03 % by mass, max. Suspended matter or sediment None visible BS EN 15004-2:2008EN 15004-2:2008 (E) 7 Table 2 Physical properties of FK-5-1-12 Property Unit Value Molecular mass 316,04 Boiling point at 1,013 bar (absolute) C 49,2 F
37、reezing point C 108,0 Critical temperature C 168,66 Critical pressure bar a18,646 Critical volume cc/mol 494,5 Critical density kg/m3639,1 Vapour pressure 20 C bar abs a0,3260 Liquid density 20 C g/ml 1,616 Saturated vapour density 20 C kg/m34,3305 Specific volume of superheated vapour at 1,013 bar
38、and 20 C m3/kg 0,0719 Heat of vaporization at boiling point kJ/kg 88,0 Chemical formula CF3CF2C(O)CF(CF3)2 Chemical name Dodecafluoro-2-methylpentan-3-one a1 bar = 0,1 MPa = 105Pa; 1 MPa = 1 N/mm2. 4.2 Use of FK-5-1-12 systems FK-5-1-12 total flooding systems may be used for extinguishing fires of a
39、ll classes within the limits specified in EN 15004-1:2008, Clause 4. The extinguishant requirements per volume of protected space are given in Table 3 for various levels of concentration. These are based on methods given in EN 15004-1:2008, 7.6. The extinguishing concentrations and design concentrat
40、ions for heptane and Surface Class A hazards are given in Table 4. BS EN 15004-2:2008EN 15004-2:2008 (E) 8 Table 3 FK-5-1-12 total flooding quantity FK-5-1-12 mass requirements per unit volume of protected space, m/V (kg/m3) This information refers only to FK-5-1-12, and may not represent any other
41、products containing Dodecafluoromethylpentan-3-one as a component. Temperature T Specific vapour volume S Design concentration (by volume) C m3/kg 3 % 4 % 5 % 6 % 7 % 8 % 9 % 10 % 20 0,0609 0,5077 0,6840 0,8640 1,0407 1,2357 1,4275 1,6236 1,8241 15 0,0623 0,4965 0,6690 0,8450 1,0248 1,2084 1,3961 1,
42、5879 1,7839 10 0,0637 0,4859 0,6545 0,8268 1,0027 1,1824 1,3660 1,5537 1,7455 5 0,0650 0,4756 0,6407 0,8094 0,9816 1,1575 1,3372 1,5209 1,7087 0 0,0664 0,4658 0,6275 0,7926 0,9613 1,1336 1,3096 1,4895 1,6734 5 0,0678 0,4564 0,6148 0,7766 0,9418 1,1106 1,2831 1,4593 1,6395 10 0,0691 0,4473 0,6026 0,7
43、612 0,9232 1,0886 1,2576 1,4304 1,6070 15 0,0705 0,4386 0,5909 0,7464 0,9052 1,0674 1,2332 1,4026 1,5757 20 0,0719 0,4302 0,5796 0,7322 0,8879 1,0471 1,2096 1,3758 1,5457 25 0,0733 0,4222 0,5688 0,7184 0,8713 1,0275 1,1870 1,3500 1,5167 30 0,0746 0,4144 0,5583 0,7052 0,8553 1,0086 1,1652 1,3252 1,48
44、88 35 0,0760 0,4069 0,5482 0,6925 0,8399 0,9904 1,1442 1,3013 1,4620 40 0,0774 0,3997 0,5385 0,6802 0,8250 0,9728 1,1239 1,2783 1,4361 45 0,0787 0,3928 0,5291 0,6684 0,8106 0,9559 1,1043 1,2560 1,4111 50 0,0801 0,3860 0,5201 0,6570 0,7967 0,9395 1,0854 1,2345 1,3869 55 0,0815 0,3795 0,5113 0,6459 0,
45、7833 0,9237 1,0671 1,2137 1,3636 60 0,0829 0,3733 0,5029 0,6352 0,7704 0,9084 1,0495 1,1936 1,3410 65 0,0842 0,3672 0,4947 0,6247 0,7578 0,8936 1,0324 1,1742 1,3191 70 0,0856 0,3613 0,4868 0,6148 0,7457 0,8793 1,0158 1,1554 1,2980 75 0,0870 0,3556 0,4791 0,6052 0,7339 0,8654 0,9998 1,1372 1,2775 80
46、0,0883 0,3501 0,4716 0,5958 0,7225 0,8520 0,9843 1,1195 1,2577 85 0,0897 0,3447 0,4644 0,5866 0,7115 0,8390 0,9692 1,1024 1,2385 90 0,0911 0,3395 0,4574 0,5778 0,7008 0,8263 0,9547 1,0858 1,2198 95 0,0925 0,3345 0,4507 0,5692 0,6904 0,8141 0,9405 1,0697 1,2014 100 0,0938 0,3296 0,4441 0,5609 0,6803
47、0,8022 0,9267 1,0540 1,1842 m/V is the agent mass requirement (in kilograms per cubic metre); i.e. mass, m, in kilograms of agent required per cubic metre of protected volume V to produce the indicated concentration at the temperature specified. V is the net volume of hazard (in cubic metres); i.e.
48、the enclosed volume minus the fixed structures impervious to extinguishant. 100cVmcS=T is the temperature (in degrees Celsius); i.e. the design temperature in the hazard area. S is the specific volume (in cubic metres per kilogram); the specific volume of superheated FK-5-1-2 vapour at a pressure of
49、 1,013 bar may be approximated by 12Sk kT=+ where k1= 0,0664; k2= 0,000274. c is the concentration (in percent); i.e. the volumetric concentration of FK-5-1-12 in air at the temperature indicated, and a pressure of 1,013 bar absolute. BS EN 15004-2:2008EN 15004-2:2008 (E) 9 Table 4 FK-5-1-12 reference extinguishing and design concentrations Fuel Extinguishment % by volume Minimum design % by volume Class B Heptane (cup burner) Heptane (room test) 4,5 4,4 5,9 Surface Class A Woo