BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf

上传人:arrownail386 文档编号:574659 上传时间:2018-12-13 格式:PDF 页数:14 大小:250.70KB
下载 相关 举报
BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf_第1页
第1页 / 共14页
BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf_第2页
第2页 / 共14页
BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf_第3页
第3页 / 共14页
BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf_第4页
第4页 / 共14页
BS EN 50216-2-2002 Power transformers and reactor fittings - Gas and oil actuated relay for liquid immersed transformers and reactors with conservator《电力变压器和反应堆配件 液浸变压器和有存油器的反应堆用气体.pdf_第5页
第5页 / 共14页
点击查看更多>>
资源描述

1、BRITISH STANDARD BS EN 50216-2:2002 Incorporating Amendment No. 1 Power transformer and reactor fittings Part 2: Gas and oil actuated relay for liquid immersed transformers and reactors with conservator The European Standard EN 50216-2:2002, with the incorporation of amendment A1:2002, has the statu

2、s of a British Standard ICS 29.120.70; 29.180 BS EN 50216-2:2002 This British Standard, having been prepared under the direction of the Electrotechnical Sector Policy and Strategy Committee, was published under the authority of the Standards Policy and Strategy Committee on 12 April 2002 BSI 4 Novem

3、ber 2003 ISBN 0 580 39499 9 National foreword This British Standard is the official English language version of EN 50216-2:2002, including amendment A1:2002. The UK participation in its preparation was entrusted to Technical Committee PEL/14, Power transformers, which has the responsibility to: A li

4、st of organizations represented on this committee can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standa

5、rds Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard

6、does not of itself confer immunity from legal obligations. aid enquirers to understand the text; present to the responsible European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and

7、 promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 11 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No.

8、Date Comments 14729 4 November 2003 Changes to Table 6EUROPEAN STANDARD EN 50216-2 January 2002 NORME EUROPENNE + A1 December 2002 EUROPISCHE NORM CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische

9、Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2002 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50216-2:2002+A1:2002 E ICS 29.120.70; 29.180 English version Power transformer and reactor fittings Part 2: Ga

10、s and oil actuated relay for liquid immersed transformers and reactors with conservator (includes amendment A1:2002) Accessoires pour transformateurs de puissance et bobines dinductance Partie 2: Relais de protection (dgagement gazeux, niveau dhuile) pour transformateurs et ractance immergs dans un

11、dilectrique liquide quips dun conservateur (inclut lamendement A1:2002) Zubehr fr Transformatoren und Drosselspulen Teil 2: Buchholzrelais fr flssigkeitsgefllte Transformatoren und Drosselspulen mit Ausdehnungsgef (enthlt nderung A1:2002) This amendment A1 modifies the European Standard EN 50216-2:2

12、002; it was approved by CENELEC on 2002-11-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references conc

13、erning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into

14、 its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Ne

15、therlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom. EN 50216-2:2002 2 Foreword This European Standard was prepared by the Technical Committee CENELEC TC 14, Power transformers. The text of the draft was submitted to the formal vote and was approved by CENELEC as EN

16、50216-2 on 2001-09-25. The following dates were fixed: - latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2002-10-01 - latest date by which the national standards conflicting with the EN have to be withdrawn

17、(dow) 2004-10-01 EN 50216-2 is to be read in conjunction with EN 50216-1. Foreword to amendment A1 This amendment was prepared by the Technical Committee CENELEC TC 14, Power transformers. The text of the draft was submitted to the Unique Acceptance Procedure and was approved by CENELEC as amendment

18、 A1 to EN 50216-2:2002 on 2002-11-01. The following dates were fixed: - latest date by which the amendment has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2003-11-01 - latest date by which the national standards conflicting with the am

19、endment have to be withdrawn (dow) 2005-11-01 3 EN 50216-2:2002 Contents Page 1 Scope. 4 2 Normative references 4 3 Service conditions 4 3.1 Maximum inclination4 3.2 Operating pressure4 3.3 Sensitivity of the relay contacts to magnetic fields . 5 3.4 Special mechanical conditions. 5 4 Dimensions 5 5

20、 Operational performance7 5.1 Alarm and trip contacts 7 5.2 Oil loss from tank. 8 5.3 Latching of trip element . 8 6 Electrical characteristics of switch 8 6.1 Switch type 8 6.2 Rated currents. 8 6.3 Breaking and making capacity. 8 7 Mechanical requirements.9 7.1 Terminal box 9 7.2 Testing facility

21、9 7.3 Gas sampling. 9 7.4 Draining device 9 7.5 Presence of gas in the relay 9 7.6 Mounting arrangement. 9 7.7 Pressure and vacuum 9 8 Nameplate 10 9 Tests. 10 9.1 Routine tests 10 9.2 Type tests 10 EN 50216-2:2002 4 1 Scope EN 50216-2 covers the gas and oil actuated relay (Buchholz relay) for liqui

22、d immersed power transformers and reactors with conservator for indoor or outdoor installation. The device is intended to detect gas release from the unit to be protected, oil surge from the tank to the conservator, complete loss of oil in the conservator. This part of EN 50216 defines the operating

23、 limits, dimensions, operational performance, electrical characteristics, dynamic characteristics. It applies to relays with dry contacts. It is not applicable to flameproof relays. Should environmental conditions and dynamic stress requirements differ from those detailed in clause 3 of EN 50216-1,

24、EN 50216-2 may then be applied by agreement between purchaser and supplier for those parts which are not affected by such abnormal installation conditions. NOTE EN 50216-2 may be used as far as applicable for relays with mercury switches. Restrictions on the use of mercury devices may be imposed by

25、national regulations. 2 Normative references Addition to EN 50216-1: EN 60947-5-1 + A12 1997 1999 Low-voltage switchgear and controlgear - Part 5-1: Control circuit devices and switching elements - Electromechanical control circuit devices (IEC 60947-5-1:1997) ISO 228-1 1994 Pipe threads where press

26、ure-tight joints are not made on the threads - Part 1: Dimensions, tolerances and designation 3 Service conditions In addition to the service conditions specified in EN 50216-1, the relay shall meet the following conditions. 3.1 Maximum inclination The relay is intended to function in a horizontal p

27、osition; a positive inclination of up to 5 to the horizontal axis is admissible in the arrow direction (see 7.6). Other values may be agreed between purchaser and supplier. 3.2 Operating pressure The relay is subjected to a continuous internal gauge pressure of 50 kPa but shall be capable of withsta

28、nding an overpressure of 250 kPa for 2 min. 5 EN 50216-2:2002 3.3 Sensitivity of the relay contacts to magnetic fields The relay shall be able to withstand a d.c. magnetic field up to 25 mT, in any direction and any polarity, without inadvertent operations. NOTE During operation or in event of fault

29、s, the surroundings of the transformers or reactors are subjected to magnetic fields which could produce inadvertent operation of the relay equipped with magnetic contacts (reed type). 3.4 Special mechanical conditions The mechanical stresses according to the classification of EN 60721-3-4, which sh

30、all not produce inadvertent operation of the relay, are for stationary sinusoidal vibration: class 4M4 or, by agreement between purchaser and supplier, class 4M6, for non stationary vibration: a vertical shock of 100 m/s, with type 1 spectrum, shall apply for both classes. 4 Dimensions Tables 1 and

31、2 are to be read with Figures 1 and 2. Table 1 Preferred dimensions of relay in mm L Nominal diameter D nA max. B max. C max. D amin. Short type Long type E b25 c205 75 275 300 200 240 190 50 205 90 275 300 195 240 220 80 220 100 275 400 195 240 220 100 220 110 275 400 220 aMinimum clearance to remo

32、ve the mechanism from the body of the relay. bMinimum clearance for mounting and access to the relay. cFor nominal diameter 25 mm thread connections G1 A (ISO 228-1) are allowed with L = 185 mm (see Figure 2). Table 2 Flange dimensions of relay in mm N of bolt holes Nominal diameter D nd1 d2 d3 d4 S

33、hort type Long type d5 max. 25 25 115 85 14 4 4 16 50 50 165 125 18 4 4 18 80 80 200 160 18 8 4 18 100 100 220 180 18 8 18 EN 50216-2:2002 6 Figure 1 D n25 to 100 with round flanges Figure 2 D n25 with threaded connections Alternative dimensions following Tables 3 and 4 may be agreed between purchas

34、er and supplier. Table 3 Other dimensions of relay in mm Nominal diameter D nA max. B max. C max. D1 amin. L E b25 180 140 320 200 127 315 50 170 150 320 200 184 315 80 170 150 320 200 184 315 aMinimum clearance for access of petcocks. bMinimum clearance for mounting and access to the relay. 7 EN 50

35、216-2:2002 Table 4 Alternative flange dimensions of the relay in mm Nominal diameter D nd1 d2 d3 d4 N of bolt holes d5 max. 25 25,4 76-sq 72 M10 4 N/A 50 50,8 139 110 11,1 6 14 80 76,2 160 130 11,1 6 14 Dimensions for rectangular flanges are given in Figure 3. Figure 3 Gas and oil operated relay wit

36、h rectangular flanges for nominal diameter of 80 mm 5 Operational performance 5.1 Alarm and trip contacts This device shall be provided with two electrical contacts. The alarm contact shall operate due to a gas displacement (volume of gas collected between 100 cm and 300 cm or 400 cm). Gas shall not

37、 freely pass from the relay body and escape into the pipework before the contact has operated. The trip contact shall operate at a steady oil flow as indicated in Table 5. This operation shall not be adversely affected when the alarm contact has already closed and gas is escaping freely. EN 50216-2:

38、2002 8 Table 5 Steady oil flow for relay operation Oil pipe connection internal diameter mm Steady oil flow for relay operation m/s Tolerance % 25 1 15 50 1 15 80 1 or 1,5 or 2 15 100 1,5 or 2 15 Other values may be agreed between purchaser and supplier. The relay shall be insensitive to oil flow fr

39、om conservator to tank. The relay shall be insensitive to the oil flow generated when the transformer is submitted to an external short circuit. The relay shall operate within 0,5 s. 5.2 Oil loss from tank The alarm element shall operate if the oil level in the relay drops by the same volume as for

40、gas collection. Further oil loss shall cause the trip element to operate before the relay pipework is free of oil. 5.3 Latching of trip element By agreement between purchaser and supplier, a device can be provided which holds the trip element in the position after an oil flow operation until it is r

41、eset. 6 Electrical characteristics of switch This device is based on EN 60947-5-1. 6.1 Switch type The purchaser shall specify whether the switch shall have normally open, normally closed or change over contacts (normally means the relay filled with oil and without any fault on the protected equipme

42、nt). 6.2 Rated currents The rated current shall be 2 A r.m.s. and the short time current 10 A r.m.s. for 30 ms. Other values may be agreed between purchaser and supplier. 6.3 Breaking and making capacity Table 6 Breaking capacity (NO and NC contacts) Voltage Current Breaking capacity 24 V d.c. to 22

43、0 V d.c. 2 A 250 W L/R 0,5 9 EN 50216-2:2002 Other values may be agreed between purchaser and supplier. The minimum contact life shall be 1 000 operations. The switch shall also be able to make a low current down to 10 mA for any value of voltage defined in Table 6 even after one year of non-operati

44、on. 7 Mechanical requirements 7.1 Terminal box A terminal box shall be provided with a minimum of four terminals and one earth terminal. The terminals shall be designed to accept cables having a cross sectional area of between 1,5 mm to 4 mm. The thread shall be minimum M5. It shall be possible to f

45、it two cable glands on the connection box. The thread for the cable glands should be either Pg 16 or M20 x 1,5 (to be agreed between supplier and purchaser). A minimum of one cable gland and a threaded hole for mounting the second cable gland shall be provided unless otherwise agreed. The marking in

46、 the terminal box shall comply with that on the connection diagram. 7.2 Testing facility The relay shall be provided with a device to check the operation of alarm and trip contacts independently (without damaging the contacts or their operating mechanism). 7.3 Gas sampling The relay shall be fitted

47、with a gas sampling petcock. A facility shall be provided for the connection of a 3,17 mm (1/8) tube for sampling at ground level. 7.4 Draining device A draining device shall be provided. If required, a provision shall be allowed to permit draining at ground level. 7.5 Presence of gas in the relay I

48、t shall be possible to visually check the presence of any gas in the relay from both sides. If required, the sight glass shall be calibrated to indicate the volume of gas collected. 7.6 Mounting arrangement An arrow on the relay shall indicate the oil flow direction from the transformer tank to the

49、conservator. 7.7 Pressure and vacuum The relay shall withstand all pressure and vacuum test stresses (see 9.1.1 and 9.2). EN 50216-2:2002 10 8 Nameplate The nameplate shall contain the following information: name of supplier; number of this standard and year of edition; type of relay; connection diagram (it may be incorporated on the nameplate or included in the terminal box); state o

展开阅读全文
相关资源
  • BS ISO IEC 29150-2011 Information technology Security techniques Signcryption《信息技术 安全技术 签密》.pdfBS ISO IEC 29150-2011 Information technology Security techniques Signcryption《信息技术 安全技术 签密》.pdf
  • BS ISO IEC 15408-1-2009 Information technology - Security techniques - Evaluation criteria for IT Security - Introduction and general model《信息技术 安全技术 IT安全评价准则 一.pdfBS ISO IEC 15408-1-2009 Information technology - Security techniques - Evaluation criteria for IT Security - Introduction and general model《信息技术 安全技术 IT安全评价准则 一.pdf
  • BS ISO 7295-1988+A1-2014 Tyre valves for aircraft Interchangeability dimensions《飞机轮胎汽门嘴 互换性尺寸》.pdfBS ISO 7295-1988+A1-2014 Tyre valves for aircraft Interchangeability dimensions《飞机轮胎汽门嘴 互换性尺寸》.pdf
  • BS ISO 15118-1-2013 Road vehicles Vehicle to grid communication interface General information and use-case definition《道路车辆 车辆到电力通讯接口 通用信息和使用案例定义》.pdfBS ISO 15118-1-2013 Road vehicles Vehicle to grid communication interface General information and use-case definition《道路车辆 车辆到电力通讯接口 通用信息和使用案例定义》.pdf
  • BS ISO 13765-2-2004 Refractory mortars - Determination of consistency using the reciprocating flow table method《耐熔灰浆 使用往复流动表法测定一致性》.pdfBS ISO 13765-2-2004 Refractory mortars - Determination of consistency using the reciprocating flow table method《耐熔灰浆 使用往复流动表法测定一致性》.pdf
  • BS ISO 10998-2008+A1-2014 Agricultural tractors Requirements for steering《农业拖拉机 操纵要求》.pdfBS ISO 10998-2008+A1-2014 Agricultural tractors Requirements for steering《农业拖拉机 操纵要求》.pdf
  • BS Z 9-1998 Space data and information transfer systems - Advanced orbiting systems - Networks and data links - Architectural specification《空间数据和信息传输系统 高级轨道系统 网络和数据链接 结构规范》.pdfBS Z 9-1998 Space data and information transfer systems - Advanced orbiting systems - Networks and data links - Architectural specification《空间数据和信息传输系统 高级轨道系统 网络和数据链接 结构规范》.pdf
  • BS Z 7-1998 Space data and information transfer systems - ASCII encoded English《空间数据和信息传输系统 ASCII 编码英语》.pdfBS Z 7-1998 Space data and information transfer systems - ASCII encoded English《空间数据和信息传输系统 ASCII 编码英语》.pdf
  • BS Z 5-1997 Space data and information transfer systems - Standard formatted data units - Control authority procedures《航天数据和信息发送系统 标准格式数据单元 控制授权程序》.pdfBS Z 5-1997 Space data and information transfer systems - Standard formatted data units - Control authority procedures《航天数据和信息发送系统 标准格式数据单元 控制授权程序》.pdf
  • BS Z 4-1997 Space data and information transfer systems - Standard formatted data units - Structure and construction rules《航天数据和信息传输系统 标准格式数据单元 结构和构造规则》.pdfBS Z 4-1997 Space data and information transfer systems - Standard formatted data units - Structure and construction rules《航天数据和信息传输系统 标准格式数据单元 结构和构造规则》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > BS

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1