1、BSI Standards PublicationBS EN 50288-5-1:2013Multi-element metallic cablesused in analogue and digitalcommunication and control -Part 5-1: Sectional specification forscreened cables characterized up to 250MHz Horizontal and building backbonecablesCopyright British Standards Institution Provided by I
2、HS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN50288-5-1:2013. It supersedes BS EN 50288-5-1:2003 which iswithdr
3、awn.The UK participation in its preparation was entrusted to TechnicalCommittee EPL/46, Cables, wires and waveguides, radio frequencyconnectors and accessories for communication and signalling.A list of organizations represented on this committee can beobtained on request to its secretary.This publi
4、cation does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. The British Standards Institution 2014. Published by BSI StandardsLimited 2014ISBN 978 0 580 77100 2ICS 33.120.20Compliance with a British Standard cannot confer immunity f
5、romlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 28 February 2014.Amendments issued since publicationDate Text affectedCopyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not f
6、or ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013EUROPEAN STANDARD EN 50288-5-1 NORME EUROPENNE EUROPISCHE NORM May 2013 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komite
7、e fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50288-5-1:2013 E ICS 33.120.20 Supersedes EN 50288-5-1:2003 English version Multi-element m
8、etallic cables used in analogue and digital communication and control - Part 5-1: Sectional specification for screened cables characterized up to 250 MHz - Horizontal and building backbone cables Cbles mtalliques lments multiples utiliss pour les transmissions et les commandes analogiques et numriqu
9、es - Partie 5-1: Spcification intermdiaire pour les cbles blinds pour applications jusqu 250 MHz - Cbles horizontaux et cbles verticaux de btiment Mehradrige metallische Daten- und Kontrollkabel fr analoge und digitale bertragung - Teil 5-1: Rahmenspezifikation fr geschirmte Kabel bis 250 MHz - Kabe
10、l fr den Horizontal- und Steigbereich This European Standard was approved by CENELEC on 2013-03-18. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
11、 Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made b
12、y translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Repu
13、blic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
14、Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013EN 50288-5-1:2013 - 2 - Contents Page Foreword . 3 1 Scope . 4 2 Normative references 4 3 Terms, d
15、efinitions, symbols and abbreviations . 4 3.1 Terms and definitions . 4 3.2 Symbols and abbreviations . 4 4 Cable construction . 5 4.1 Conductor 5 4.2 Insulation . 5 4.3 Cabling elements . 5 4.4 Identification of cabling elements . 5 4.5 Screening of cabling elements 5 4.6 Cable make-up 5 4.7 Fillin
16、g compound 5 4.8 Interstitial fillers . 5 4.9 Screening of the cable core 5 4.10 Moisture barriers 5 4.11 Wrapping layers . 5 4.12 Sheath . 6 5 Tests and requirements for completed cables 6 5.1 Electrical tests . 6 5.2 Mechanical tests . 9 5.3 Environmental tests 10 5.4 Fire performance tests . 10 A
17、nnex A (informative) Maximum voltage, current and temperature rating for cables used for POE applications 12 Annex B (informative) Blank detail specification 13 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or network
18、ing permitted without license from IHS-,-,-BS EN 50288-5-1:2013- 3 - EN 50288-5-1:2013 Foreword This document (EN 50288-5-1:2013) has been prepared by CLC/SC 46XC “Multicore, Multipair and Quad Data communication cables,“ of CLC/TC 46X, “Communication cables“. The following dates are fixed: latest d
19、ate by which this document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2014-03-18 latest date by which the national standards conflicting with this document have to be withdrawn (dow) 2016-03-18 This document supersedes EN 50288-5-
20、1:2003. EN 50288-5-1:2013 includes the following significant technical changes with respect to EN 50288-5-1:2003: the addition of the Blank Detail Specification Annex; a number minor corrections and updating of references; the re-classification of ELFEXT to ACR-F. This Part 5-1 is to be read in conj
21、unction to EN 50288-1. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objec
22、tives for Electrical Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC). Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013
23、EN 50288-5-1:2013 - 4 - 1 Scope EN 50288-5-1 is a sectional specification for screened cables, characterised from 1 MHz up to 250 MHz, to be used in horizontal and building backbone wiring as defined in EN 50173. This sectional specification contains the electrical, mechanical, transmission and envi
24、ronmental performance characteristics of the cables, when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1 that contains the essential provisions for its application. The cables covered in this sectional specification ar
25、e intended to operate with voltages and currents normally encountered in communication systems. These cables are not intended to be used in conjunction with low impedance sources, for example, the electric power supplies of public utility mains. 2 Normative references The following documents, in who
26、le or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 50173 Series Information technology
27、 - Generic cabling systems EN 50288-1 Multi-element metallic cables used in analogue and digital communication and control - Part 1: Generic specification EN 50289 Series Communication cables - Specifications for test methods EN 50290 Series Communication cables EN 60811 Series Electric and optical
28、fibre cables - Test methods for non-metallic materials (IEC 60811 series) IEC 60189-2 Low-frequency cables and wires with PVC insulation and PVC sheath - Part 2: Cables in pairs, triples, quads and quintuples for inside installations 3 Terms, definitions, symbols and abbreviations 3.1 Terms and defi
29、nitions For the purposes of this document the terms and definitions given in EN 50288-1 and the following apply. 3.1.1 screening of cable a cable is considered screened when the cable core is covered by a continuous conductive layer forming part of the shielding and grounding system Note 1 to entry:
30、 d.c. continuity has to be given and minimum shielding requirements have to be met. 3.2 Symbols and abbreviations For the purposes of this document, the following abbreviations apply. EX Exogenous (derived or originating externally) POE Power Over Ethernet Copyright British Standards Institution Pro
31、vided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013- 5 - EN 50288-5-1:2013 4 Cable construction 4.1 Conductor The conductor shall be solid copper and meet the requirements of EN 50288-1, 4.1.
32、The conductor shall be plain or metal coated. The nominal conductor diameter shall be 0,5 mm and 0,8 mm. NOTE Constructions with copper clad conductors do not meet the requirements. 4.2 Insulation The insulation shall be of a suitable material according to the relevant part of EN 50290-2. 4.3 Cablin
33、g elements The cable element shall be a pair or a quad. 4.4 Identification of cabling elements Unless otherwise specified, the colour coding for identification is given in IEC 60189-2. The colours shall meet the requirements of EN 50288-1, 4.4. 4.5 Screening of cabling elements Where appropriate, sc
34、reening of the cabling elements shall be applied in accordance with 4.5 of EN 50288-1. Coverage is defined in EN 50290-2-1. 4.6 Cable make-up The cable elements shall be laid up in concentric layer(s) or units to form the cable core. 4.7 Filling compound Not applicable. 4.8 Interstitial fillers Wher
35、e fillers are used they shall meet the requirements of 4.8 of EN 50288-1. 4.9 Screening of the cable core The screening of the cable core shall be applied in accordance with EN 50288-1, 4.9. Coverage is defined in EN 50290-2-1. 4.10 Moisture barriers Not applicable. 4.11 Wrapping layers Where wrappi
36、ng layers are used they shall be in accordance with EN 50288-1, 4.11. Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013EN 50288-5-1:2013 - 6 - 4.12
37、 Sheath The sheath shall be of a suitable material according to the relevant part of EN 50290-2. 5 Tests and requirements for completed cables The following tables give the tests to be applied, together with the respective limits, in order to demonstrate compliance with this specification. 5.1 Elect
38、rical tests 5.1.1 Low-frequency and d.c. electrical measurements Table 1 -Low-frequency and d.c. electrical measurements EN 50288-1 sub-clause Parameter Requirement 5.1.1.1 Conductor loop resistance 19,0 /100 m 5.1.1.2 Conductor resistance unbalance 2,0 % 5.1.1.2.1 Pair resistance unbalance 4,0 % 5.
39、1.1.3 Dielectric strength conductor/conductor and conductor/screen 1,0 kV d.c. or 0,7 kV a.c. for 1 min or 2,5 kV d.c. or 1,7 kV a.c. for 2 s 5.1.1.4 Insulation resistance 5 000 M km when tested in accordance with EN 50289-1-4 5.1.1.5 Mutual capacitance No requirement specified 5.1.1.6 Capacitance u
40、nbalance to earth 1 200 pF/km Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013- 7 - EN 50288-5-1:2013 5.1.2 High-frequency electrical and transmis
41、sion measurements Table 2 - High-frequency electrical and transmission requirements EN 50288-1 sub-clause Parameter Requirement 5.1.2.1 Velocity of propagation Phase delay 534+36/f ns/100 m, 1 MHz f 250 MHz 5.1.2.2 Propagation delay difference (skew) 45 ns/100 m at 100 MHz 5.1.2.3 Longitudinal atten
42、uation 2) 3) 4)5.1.2.4 Near-end unbalance attenuation 40-10log(f) dB, 1 MHz f 250 MHz; 5.1.2.5 Near-end crosstalk (NEXT)1) 2)5.1.2.6 Attenuation to crosstalk ratio at the far end 2) 6) (ACR-F) 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 66,0 58,0 50,0 45,9 44,0 40,1 34,1 30,0 26,2 24,0 22,0 dB 70-20
43、log(f), 1 MHz f 250 MHz (maximum 66 dB), values referenced to 100 m 5.1.2.7.1 Power sum near-end crosstalk 2) (PSNEXT) 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 72.3 63,3 57,3 54,2 52,8 49,9 45,4 42,3 39,4 37,8 36,3 dB 72,3-15log(f), 1 MHz f 250 MHz 5.1.2.7.2 Power Sum Attenuation to crosstalk rat
44、io at the far end 2) 6) (PSACR-F) 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 64,0 55,0 47,0 43,0 41,0 37,1 31,1 27,0 23,2 21,0 19,0 dB 67-20log(f), 1 MHz f 250 MHz (maximum 64 dB), values referenced to 100 m 5.1.2.8 Mean characteristic impedance 100 5 , 120 5 , at 100 MHz 1 4 10 16 20 31,25 62,5 10
45、0 155 200 250 MHz 2,1 3,8 6,0 7,6 8,5 10,8 15,5 19,9 25,3 29,1 33,0 dB/100 m 1,82f+0,0169f+0,25 /f, 1 MHz f 250 MHz 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 75 66 60,3 57,2 55,8 52,9 48,4 45,3 42,4 40,8 39,3 dB 75-15log(f), 1 MHz f 250 MHz Copyright British Standards Institution Provided by IHS u
46、nder license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-5-1:2013EN 50288-5-1:2013 - 8 - 5.1.2.9 Return loss2) 5)4 8 10 16 20 31,25 62,5 100 155 200 250 MHz 23,1 24,5 25,0 25,0 25,0 23,6 21,5 20,1 18,8 18,0 17,3 dB 20+5l
47、og(f), 4 MHz f 10 MHz; 25,0dB, 10 MHz f 20 MHz; 25-7log(f/20), 20 MHz f 250 MHz; 5.1.2.10 Coupling attenuation Type I 85dB , 30 MHz f 100 MHz 85 - 20 log f/100 dB 100 MHz f 1000 MHz Type Ib 70dB , 30 MHz f 100 MHz 70 - 20 log f/100 dB 100 MHz f 1000 MHz Type II 55dB, 30 MHz f 100 MHz 55 - 20 log f/100 dB 100 MHz f 1000 MHz 5.1.2.11 Transfer impedance Grade 1 10 m/m at 1 MHz; 10 m/m at 10 MHz; 30 m/m at 30 MHz; 100 m/m at 100 MHz Grade 2 50 m/m at 1 MHz; 100 m/m at 10 MHz; 200 m/m at 30 MHz; 1000m/m at 100 MHz 1)For hybrid cables and multi-unit cabl