1、 2015 ASHRAE. All Rights reserved. INTERPRETATION IC 15-2013-1 OF ANSI/ASHRAE STANDARD 15-2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS Date Approved: March 5, 2015 Request from: Eric Wilson (E), Harshaw Trane, 2350 Fortune Drive, Lexington, KY 40509. Reference: This request for interpretation refe

2、rs to the requirements presented in ANSI/ASHRAE Standard 15-2013, Sections 7.3.2.2 and 7.3.2.3, regarding plenums and ductwork in the calculation of volume for refrigerant concentration limit (RCL). Background: A VRF system in which indoor terminal units are installed in a variety of locations (ceil

3、ing, wall, or floor) is used to condition air in the occupied space. A separate, dedicated outdoor air system (DOAS) is used to deliver conditioned outside air to the same space. The DOAS has a ducted supply and plenum return. The VRF terminal units take air from the occupied space and return condit

4、ioned air to the occupied space, but are not directly connected to the plenum or other ductwork. The DOAS system is not operated continuously. Since the VRF terminal units are not in the supply ductwork or plenum return, refrigerant could potentially leak directly into the occupied space without tra

5、veling through ductwork or plenum. Interpretation: Section 7.3.2.3 specifically states that supply and return ducts and plenums shall be included when calculating refrigerant quantity limits. This means these volumes can be used in the calculation even if the leak potential components are not locate

6、d within these specific ducts/plenums. Question: Is this Interpretation correct? Answer: No Comment: The Background describes two independent refrigerating systems, namely a DOAS system and a VRF system employing multiple indoor terminal units. The refrigerant concentration in the occupied space is

7、computed separately for each system and compared to the RCL. The Background states that the DOAS system is not operated continuously and may be off. The DOAS system is therefore controlled in such a way that it would not always act to disperse refrigerant that may leak from VRF indoor terminal units

8、 into the plenum or ductwork. If the refrigerant concentration is based on these additional volumes, leaking refrigerant from the indoor terminal units could concentrate in the occupied space alone, and could rise to a level that poses a danger to occupants who may be present. Please note that there is an editorial error in Sections 7.3.2.2 and 7.3.2.3; “refrigerant quantity limit” should read “refrigerant concentration limit” or RCL.

展开阅读全文
相关资源
猜你喜欢
  • BS PD IEC TS 62763-2013_5284 Pilot function through a control pilot circuit using PWM (pulse width modulation) and a control pilot wire《通过控制导向线使用PWM (脉冲宽度调制) 的导向功能和控制导向线》.pdf BS PD IEC TS 62763-2013_5284 Pilot function through a control pilot circuit using PWM (pulse width modulation) and a control pilot wire《通过控制导向线使用PWM (脉冲宽度调制) 的导向功能和控制导向线》.pdf
  • BS ISO 8070-2007 Milk and milk products - Determination of calcium sodium potassium and magnesium contents - Atomic absorption spectrometric method《牛奶和奶制品 钙、钠、钾和镁含量的测定 原子吸.pdf BS ISO 8070-2007 Milk and milk products - Determination of calcium sodium potassium and magnesium contents - Atomic absorption spectrometric method《牛奶和奶制品 钙、钠、钾和镁含量的测定 原子吸.pdf
  • BS ISO 8082-1-2009 Self-propelled machinery for forestry - Laboratory tests and performance requirements for roll-over protective structures - General machines《林业用自推进机械 防倾.pdf BS ISO 8082-1-2009 Self-propelled machinery for forestry - Laboratory tests and performance requirements for roll-over protective structures - General machines《林业用自推进机械 防倾.pdf
  • BS ISO 8082-2-2011 Self-propelled machinery for forestry Laboratory tests and performance requirements for roll-over protective structures Machines having a rotating platf.pdf BS ISO 8082-2-2011 Self-propelled machinery for forestry Laboratory tests and performance requirements for roll-over protective structures Machines having a rotating platf.pdf
  • BS ISO 8083-2006 Machinery for forestry - Falling-object protective structures (FOPS) - Laboratory tests and performance requirements《林业机械 落体防护装置(FOPS) 实验室试验和性能要求》.pdf BS ISO 8083-2006 Machinery for forestry - Falling-object protective structures (FOPS) - Laboratory tests and performance requirements《林业机械 落体防护装置(FOPS) 实验室试验和性能要求》.pdf
  • BS ISO 8086-2004 Dairy plant - Hygiene conditions - General guidance on inspection and sampling procedures《乳品厂 卫生条件 检验和取样程序通用指南》.pdf BS ISO 8086-2004 Dairy plant - Hygiene conditions - General guidance on inspection and sampling procedures《乳品厂 卫生条件 检验和取样程序通用指南》.pdf
  • BS ISO 8096-2005 Rubber- or plastics-coated fabrics for water resistant clothing - Specification《雨衣用橡胶或塑料涂覆织物 规范》.pdf BS ISO 8096-2005 Rubber- or plastics-coated fabrics for water resistant clothing - Specification《雨衣用橡胶或塑料涂覆织物 规范》.pdf
  • BS ISO 8097-2001 Aircraft Minimum airworthiness requirements and test conditions for certified air cargo unit load devices《航空器 经认证的航空货运集装单元装置最低适航性要求和试验条件》.pdf BS ISO 8097-2001 Aircraft Minimum airworthiness requirements and test conditions for certified air cargo unit load devices《航空器 经认证的航空货运集装单元装置最低适航性要求和试验条件》.pdf
  • BS ISO 8114-1993 Textile machinery and accessories - Spindles for ring-spinning and doubling machines - List of equivalent terms《纺织机械和附件 环锭纺纱机和并线机用锭子 同义术语表》.pdf BS ISO 8114-1993 Textile machinery and accessories - Spindles for ring-spinning and doubling machines - List of equivalent terms《纺织机械和附件 环锭纺纱机和并线机用锭子 同义术语表》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1