ASTM C90-2006b Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砖石设备的标准规范》.pdf

上传人:rimleave225 文档编号:508708 上传时间:2018-12-01 格式:PDF 页数:4 大小:80.41KB
下载 相关 举报
ASTM C90-2006b Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砖石设备的标准规范》.pdf_第1页
第1页 / 共4页
ASTM C90-2006b Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砖石设备的标准规范》.pdf_第2页
第2页 / 共4页
ASTM C90-2006b Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砖石设备的标准规范》.pdf_第3页
第3页 / 共4页
ASTM C90-2006b Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砖石设备的标准规范》.pdf_第4页
第4页 / 共4页
亲,该文档总共4页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: C 90 06bStandard Specification forLoadbearing Concrete Masonry Units1This standard is issued under the fixed designation C 90; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revision. A number in pare

2、ntheses indicates the year of last reapproval. A superscriptepsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope*1.1 This specification covers hollow and solid (see 5.3 and5.4) concre

3、te masonry units made from hydraulic cement,water, and mineral aggregates with or without the inclusion ofother materials. There are three classes of concrete masonryunits: (1) normal weight, (2) medium weight, and (3) light-weight. These units are suitable for both loadbearing andnonloadbearing app

4、lications.1.2 Concrete masonry units covered by this specification aremade from lightweight or normal weight aggregates, or both.1.3 The text of this specification references notes andfootnotes which provide explanatory material. These notes andfootnotes (excluding those in tables and figures) shall

5、 not beconsidered as requirements of the standard.1.4 The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are forinformation only.NOTE 1When particular features are desired such as surface texturesfor appearance or bond, finish, color, or particul

6、ar properties such asdensity classification, higher compressive strength, fire resistance, thermalperformance or acoustical performance, these features should be specifiedseparately by the purchaser. Suppliers should be consulted as to theavailability of units having the desired features.2. Referenc

7、ed Documents2.1 ASTM Standards:2C33 Specification for Concrete AggregatesC 140 Test Methods for Sampling and Testing ConcreteMasonry Units and Related UnitsC 150 Specification for Portland CementC 331 Specification for Lightweight Aggregates for Con-crete Masonry UnitsC 426 Test Method for Linear Dr

8、ying Shrinkage of Con-crete Masonry UnitsC 595 Specification for Blended Hydraulic CementsC 618 Specification for Coal Fly Ash and Raw or CalcinedNatural Pozzolan for Use in ConcreteC 989 Specification for Ground Granulated Blast-FurnaceSlag for Use in Concrete and MortarsC 1157 Performance Specific

9、ation for Hydraulic CementC 1209 Terminology of Concrete Masonry Units and Re-lated UnitsC 1232 Terminology of MasonryC 1314 Test Method for Compressive Strength of MasonryPrismsE 519 Test Method for Diagonal Tension (Shear) in Ma-sonry AssemblagesE72 Test Methods of Conducting Strength Tests of Pan

10、elsfor Building Construction3. Terminology3.1 Terminology defined in Terminology C 1209 and Ter-minology C 1232 shall apply for this specification.4. Materials4.1 Cementitious MaterialsMaterials shall conform to thefollowing applicable specifications:4.1.1 Portland CementSpecification C 150.4.1.2 Mo

11、dified Portland CementPortland cement con-forming to Specification C 150, modified as follows:(1) LimestoneIf calcium carbonate is added to thecement, the CaCO3content shall not be less than 85 %.(2) Limitation on Insoluble Residue1.5 %.(3) Limitation on Air Content of MortarVolume percent,22 % max.

12、(4) Limitation on Loss on Ignition7 %.4.1.3 Blended Hydraulic CementsSpecification C 595.4.1.4 Hydraulic CementSpecification C 1157.4.1.5 PozzolansSpecification C 618.4.1.6 Blast Furnace Slag CementSpecification C 989.4.2 AggregatesAggregates shall conform to the followingspecifications, except that

13、 grading requirements shall notnecessarily apply:4.2.1 Normal Weight AggregatesSpecification C33.1This specification is under the jurisdiction of ASTM Committee C15 onManufactured Masonry Units and is the direct responsibility of SubcommitteeC15.03 on Concrete Masonry Units and Related Units.Current

14、 edition approved Dec. 15, 2006. Published January 2007. Originallyapproved in 1931. Last previous edition approved in 2006 as C 90 06a.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume in

15、formation, refer to the standards Document Summary page onthe ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.2.2 Lightweight AggregatesSpecification C

16、331.4.3 Other ConstituentsAir-entraining agents, coloringpigments, integral water repellents, finely ground silica, andother constituents shall be previously established as suitable foruse in concrete masonry units and shall conform to applicableASTM standards or shall be shown by test or experience

17、 not tobe detrimental to the durability of the concrete masonry unitsor any material customarily used in masonry construction.5. Physical Requirements5.1 At the time of delivery to the purchaser, units shallconform to the physical requirements prescribed in Table 1 andTable 2.NOTE 2Higher compressiv

18、e strengths than those listed in Table 2 maybe specified where required by design. Consult with suppliers to determineavailability of units of higher compressive strength.5.2 At the time of delivery to the purchaser, the linearshrinkage of units shall not exceed 0.065 %.NOTE 3The purchaser is the pu

19、blic body or authority, association,corporation, partnership, or individual entering into a contract or agree-ment to purchase or install, or both, concrete masonry units. The time ofdelivery to the purchaser is FOB plant when the purchaser or thepurchasers agent transports the concrete masonry unit

20、s, or at the timeunloaded at the worksite if the manufacturer or the manufacturers agenttransports the concrete masonry units.5.3 Hollow Units:5.3.1 Face shell thickness (tfs) and web thickness (tw) shallconform to the requirements prescribed in Table 1.NOTE 4Web thickness (tw) not conforming to the

21、 requirementsprescribed in Table 1 may be approved, provided equivalent structuralcapability has been established when tested in accordance with theapplicable provisions of Test Methods E72, C 1314, E 519, or otherapplicable tests and the appropriate design criteria developed is inaccordance with ap

22、plicable building codes.5.4 Solid Units:5.4.1 The net cross-sectional area of solid units in everyplane parallel to the bearing surface shall be not less than 75 %of the gross cross-sectional area measured in the same plane.5.5 End Flanges:5.5.1 For units having end flanges, the thickness of eachfla

23、nge shall not be less than the minimum face shell thickness.NOTE 5Flanges beveled at the ends for mortarless head joint appli-cations that will be filled with grout are exempt from this requirement.Flanges which are specially shaped for mortarless head joint applicationswhich have been shown by test

24、ing or field experience to provideequivalent performance are exempt from this requirement.6. Permissible Variations in Dimensions6.1 Standard UnitsFor standard units, no overall dimen-sion (width, height, and length) shall differ by more than 618in. (3.2 mm) from the specified dimensions.6.2 Particu

25、lar Feature UnitsFor particular feature units,dimensions shall be in accordance with the following:6.2.1 For molded face units, no overall dimension (width,height, and length) shall differ by more than 618 in. (3.2 mm)from the specified standard dimension. Dimensions of moldedfeatures shall be withi

26、n 6116 in. (1.6 mm) of the specifiedstandard dimensions and shall be within 6116 in. (1.6 mm) ofthe specified placement of the molded feature.NOTE 6Molded features include, but are not limited to: ribs, scores,hex-shapes, and patterns.6.2.2 For split-faced units, all non-split overall dimensionsshal

27、l differ by not more than 618 in. (3.2 mm) from thespecified standard dimensions.6.2.3 For slump units, no overall height dimension shalldiffer by more than 618 in. (3.2 mm) from the specifiedstandard dimension.NOTE 7On faces that are split or slumped, overall dimensions willvary. Consult with suppl

28、iers to determine achievable dimensional toler-ances for products including these features.7. Finish and Appearance7.1 All units shall be sound and free of cracks or otherdefects that interfere with the proper placement of the unit orsignificantly impair the strength or permanence of the construc-ti

29、on. Minor cracks, incidental to the usual method of manufac-ture or minor chipping resulting from customary methods ofhandling in shipment and delivery, are not grounds for rejec-tion.7.2 Where units are to be used in exposed wall construction,the face or faces that are to be exposed shall not show

30、chips orcracks, not otherwise permitted, or other imperfections whenviewed from a distance of not less than 20 ft (6.1 m) underdiffused lighting.7.2.1 Five percent of a shipment containing chips, not largerthan 1 in. (25.4 mm) in any dimension, or cracks not wider than0.02 in. (0.5 mm) and not longe

31、r than 25 % of the nominalheight of the unit, is permitted.7.3 The color and texture of units shall be specified by thepurchaser. The finished surfaces that will be exposed in placeshall conform to an approved sample, consisting of not lessthan four units, representing the range of texture and color

32、permitted.7.4 A shipment shall not contain more than 5 % of units,including broken units, that do not meet the requirements of6.1, 7.1, 7.2, and 7.2.1.TABLE 1 Minimum Thickness of Face Shells and WebsANominal Width (W) ofUnits, in. (mm)Face ShellThickness (tfs),min, in. (mm)B,CWeb Thickness (tw)Webs

33、B,D,Cmin, in.(mm)Equivalent WebThickness, min,in./linear ftE(mm/linear m)3 (76.2) and 4 (102)34 (19)34 (19) 158 (136)6 (152) 1 (25) 1 (25) 214 (188)8 (203) 114 (32) 1 (25) 214 (188)10 (254) and greater 114 (32) 118 (29) 212 (209)AAverage of measurements on a minimum of 3 units when measured asdescri

34、bed in Test Methods C 140.BWhen this standard is used for units having split surfaces, a maximum of 10 %of the split surface is permitted to have thickness less than those shown, but notless than34 in. (19.1 mm). When the units are to be solid grouted, the 10 % limitdoes not apply and Footnote C est

35、ablishes a thickness requirement for the entirefaceshell.CWhen the units are to be solid grouted, minimum face shell and web thicknessshall be not less than58 in. (16 mm).DThe minimum web thickness for units with webs closer than 1 in. (25.4 mm)apart shall be34 in. (19.1 mm).EEquivalent web thicknes

36、s does not apply to the portion of the unit to be filledwith grout. The length of that portion shall be deducted from the overall length ofthe unit for the calculation of the equivalent web thickness.C9006b28. Sampling and Testing8.1 The purchaser or authorized representative shall beaccorded proper

37、 facilities to inspect and sample the units at theplace of manufacture from the lots ready for delivery.8.2 Sample and test units in accordance with Test MethodsC 140.8.3 Total linear drying shrinkage shall be based on tests ofconcrete masonry units made with the same materials, concretemix design,

38、manufacturing process, and curing method, con-ducted in accordance with Test Method C 426 and not morethan 24 months prior to delivery.9. Compliance9.1 If a sample fails to conform to the specified require-ments, the manufacturer shall be permitted to remove unitsfrom the shipment. A new sample shal

39、l be selected by thepurchaser from remaining units from the shipment with asimilar configuration and dimension and tested at the expenseof the manufacturer. If the second sample meets the specifiedrequirements, the remaining portion of the shipment repre-sented by the sample meets the specified requ

40、irements. If thesecond sample fails to meet the specified requirements, theremaining portion of the shipment represented by the samplefails to meet the specified requirements.NOTE 8Unless otherwise specified in the purchase order, the cost oftests is typically borne as follows: (1) if the results of

41、 the tests show thatthe units do not conform to the requirements of this specification, the costis typically borne by the seller; (2) if the results of the tests show that theunits conform to the specification requirements, the cost is typically borneby the purchaser.10. Keywords10.1 absorption; con

42、crete masonry units; equivalent webthickness; face shell; flange; lightweight; linear shrinkage;loadbearing; medium weight; normal weight; websAPPENDIXES(Nonmandatory Information)X1. WATER PENETRATION RESISTANCEX1.1 Exterior walls are often subjected to moisture pen-etration from one or more sources

43、. For example, basementwalls may be exposed to water from saturated soil. Above-grade exterior walls are usually exposed to wind-driven rain.To prevent water penetration, proper detailing, construction,flashing, and drainage should be provided. Proper waterpenetration resistant treatments should be

44、applied to the walls.While it is not within the scope of Specification C 90 to includeinformation on resistance to water penetration, such informa-tion and guidelines are available from other organizations.X2. CRACK CONTROLX2.1 Restrained or differential movement in buildingelements and building mat

45、erials can result in cracking. Somecommon causes of movement are: loads created by wind, soilpressure, seismic forces, or other external sources; settlementof foundations; or volume changes in materials. For example,volume changes in concrete masonry units can be caused bymoisture gain and loss, the

46、rmal expansion and contraction, andcarbonation. To limit and control cracking due to these andother causes, proper design, detailing, construction, and mate-rials are necessary. Specification C 90 provides a maximumlimitation on the total linear drying shrinkage potential of theunits, but it is not

47、within the scope of this specification toaddress other design, detailing, construction, or material rec-ommendations. This type of information and related guidelinesfor crack control are available from other organizations.TABLE 2 Strength, Absorption, and Density Classification RequirementsADensity

48、Classification Oven-Dry Densityof Concrete, lb/ft3(kg/m3)Maximum WaterAbsorption, lb/ft3(kg/m3)Minimum Net AreaCompressive Strength, lb/in2(MPa)Average of 3 Units Average of 3 Units Individual Units Average of 3 Units Individual UnitsLightweight Less than 105 (1680) 18 (288) 20 (320) 1900 (13.1) 170

49、0 (11.7)Medium Weight 105 to less than 125 (16802000) 15 (240) 17 (272) 1900 (13.1) 1700 (11.7)Normal Weight 125 (2000) or more 13 (208) 15 (240) 1900 (13.1) 1700 (11.7)AConsult manufacturers for available densities.C9006b3SUMMARY OF CHANGESCommittee C15 has identified the location of selected changes to this standard since the last issue (C 90 06a)that may impact the use of this standard. (Approved Dec. 15, 2006.)(1) Nonmandatory information previously appearing in sub-sections 6.2.2 and 6.2.3 directing users to consult suppliers forac

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1