1、Designation: D2464 15Standard Specification forThreaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings,Schedule 801This standard is issued under the fixed designation D2464; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the yea
2、r of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope*1.1 This specification covers
3、poly(vinyl chloride) (PVC)threaded Schedule 80 pipe fittings. Included are requirementsfor materials, workmanship, dimensions, and burst pressure.NOTE 1Threaded CPVC plastic pipe fittings, Schedule 80, whichwere formerly included in this standard, are now covered by SpecificationF437.1.2 The product
4、s covered by this specification are intendedfor use with the distribution of pressurized liquids only, whichare chemically compatible with the piping materials. Due toinherent hazards associated with testing components and sys-tems with compressed air or other compressed gases somemanufacturers do n
5、ot allow pneumatic testing of their products.Consult with specific product/component manufacturers fortheir specific testing procedures prior to pneumatic testing.NOTE 2Pressurized (compressed) air or other compressed gasescontain large amounts of stored energy which present serious safetyhazards sh
6、ould a system fail for any reason.1.3 The text of this specification references notes, footnotes,and appendixes which provide explanatory material. Thesenotes and footnotes (excluding those in tables and figures) shallnot be considered as requirements of the specification.1.4 The values stated in in
7、ch-pound units are to be regardedas the standard. The values given in parentheses are providedfor information only.1.5 The following safety hazards caveat pertains only to thetest method portion, Section 8, of this specification. Thisstandard does not purport to address all of the safety concerns,if
8、 any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.2. Referenced Documents2.1 ASTM Standards:2D618 Practice for Conditioning Plastics for Testi
9、ngD1599 Test Method for Resistance to Short-Time HydraulicPressure of Plastic Pipe, Tubing, and FittingsD1600 Terminology forAbbreviated Terms Relating to Plas-ticsD1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)Compounds and Chlorinated Poly(Vinyl Chloride)(CPVC) CompoundsD2122 Test Method
10、for Determining Dimensions of Ther-moplastic Pipe and FittingsF412 Terminology Relating to Plastic Piping SystemsF437 Specification for Threaded Chlorinated Poly(VinylChloride) (CPVC) Plastic Pipe Fittings, Schedule 80F1498 Specification for Taper Pipe Threads 60 for Thermo-plastic Pipe and Fittings
11、2.2 Federal Standard:Fed. Std. No. 123 Marking for Shipment (Civil Agencies)32.3 Military Standard:MIL-STD-129 Marking for Shipment and Storage32.4 NSF Standard:Standard No. 14 for Plastic Piping Components and RelatedMaterials4Standard No. 61 for Drinking Water Systems ComponentsHealth Effects43. T
12、erminology3.1 GeneralDefinitions are in accordance with Terminol-ogy F412, and abbreviations are in accordance with Terminol-ogy D1600, unless otherwise indicated. The abbreviation forpoly(vinyl chloride) plastic is PVC.1This specification is under the jurisdiction of ASTM Committee F17 on PlasticPi
13、ping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings.Current edition approved March 1, 2015. Published July 2015. Originallyapproved in 1965. Last previous edition approved in 2013 as D2464 13. DOI:10.1520/D2464-15.2For referenced ASTM standards, visit the ASTM website, w
14、ww.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3DLA Document Services Building 4/D 700 Robbins Avenue Philadelphia, PA19111-5094 http:/quicksearch.dla.mil/4Available
15、 from NSF International, P.O. Box 130140, 789 N. Dixboro Rd., AnnArbor, MI 48113-0140, http:/www.nsf.org.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States14. Classificatio
16、n4.1 GeneralThis specification covers threaded Schedule80 PVC pipe fittings, made from four PVC plastic compoundsand intended for use with threaded Iron Pipe Size (IPS)outside-diameter plastic pipe.4.1.1 Fittings covered by this specification are normallymolded. In-line fittings, such as couplings,
17、unions, bushings,caps, nipples, etc., shall be molded or machined from extrudedstock.4.1.2 Fittings fabricated by back welding or butt fusion arenot included in this specification.5. Materials and Manufacture5.1 This specification covers PVC pipe fittings made fromtwo PVC plastics as classified in S
18、pecification D1784. Theseare cell classifications 12454 and 14333.NOTE 3Mechanical strength, heat deflection temperature, and flam-mability requirements are covered in Specification D1784.5.2 Rework MaterialThe manufacturers shall use onlytheir own clean rework fitting material and the fittings pro-
19、duced shall meet all the requirements of this specification.6. Requirements6.1 Dimensions and Tolerances:6.1.1 The dimensions and tolerances of the fittings shall beas shown in Table 1 and Table 2 when measured in accordancewith Test Method D2122. Minimum dimensions have zeronegative tolerances. Bus
20、hings shall have thread lengths appli-cable to the corresponding sizes. Counterbore is optional, is notshown in Table 1, and is not included in the center-to-end orend-to-end dimensions.6.1.2 Fittings Not IllustratedAll fittings, whether illus-trated in Table 1 and Table 2 or not, shall have wall th
21、icknessesand thread dimensions conforming to 6.1 and 6.2.6.2 ThreadsFor all fittings having taper pipe threads,threads shall conform to Specification F1498 and be gaged inaccordance with 8.4.6.3 Burst Pressure:6.3.1 The burst strength of the fittings shall be not less thanthat calculated for the siz
22、e and wall thickness of the pipe withwhich it is to be used, when calculated from the followingequation:S 5 PDOt!/2t (1)where:S = hoop stress, psi (or MPa),P = internal pressure, psi (or MPa),DO= average outside diameter, in. (or mm), andt = minimum wall thickness, in. (or mm).Fittings tested in acc
23、ordance with 8.4 shall withstand theminimum burst pressure shown in Table 3.6.3.2 Pressures shown are minimum burst pressures and donot imply rated working pressures. The burst pressure shall beused only as an indication of quality.7. Workmanship, Finish, and Appearance7.1 The fittings shall be homo
24、geneous throughout and freeof cracks, holes, foreign inclusions, or other defects. TheTABLE 1 Dimensions of 90 Ells, Tees, Crosses, 45 Elbows and Couplings (Straight Sizes), in. (mm)ANominalPipe SizeCenter to ThreadEnd, 90 Elbows,Tees, Crosses,BH,minLength ofThread, T,minCenter to ThreadEnd, 45 Elbo
25、w,BK,minInside Diameterof Fitting, D,minNominal WallThickness, F,minOutside Diameterof Hub, M,minThread End toThread End ofCoupling, L,min18 0.688 (17.48) 0.38 (9.65) 0.625 (15.88) 0.171 (4.34) 0.108 (2.74) 0.645 (16.40) 0.813 (20.65)14 0.812 (20.63) 0.50 (12.70) 0.688 (17.48) 0.258 (6.55) 0.135 (3.
26、43) 0.840 (21.30) 1.063 (27.00)38 0.938 (23.83) 0.50 (12.70) 0.750 (19.05) 0.379 (9.63) 0.144 (3.66) 1.000 (25.40) 1.063 (27.00)12 1.125 (28.58) 0.64 (16.26) 0.750 (19.05) 0.502 (12.75) 0.198 (5.03) 1.280 (32.50) 1.344 (34.14)34 1.250 (31.75) 0.65 (16.51) 1.000 (25.40) 0.698 (17.73) 0.207 (5.26) 1.5
27、00 (38.10) 1.500 (38.10)1 1.500 (38.10) 0.81 (20.57) 1.125 (28.58) 0.911 (23.14) 0.225 (5.72) 1.810 (45.97) 1.688 (42.88)114 1.750 (44.45) 0.85 (21.59) 1.313 (33.35) 1.227 (31.17) 0.261 (6.63) 2.200 (55.88) 1.750 (44.45)112 1.938 (49.23) 0.85 (21.54) 1.438 (36.53) 1.446 (36.73) 0.270 (6.86) 2.500 (6
28、3.50) 2.000 (50.80)2 2.250 (57.15) 0.90 (22.86) 1.625 (41.28) 1.881 (47.78) 0.297 (7.54) 3.000 (76.20) 2.063 (52.40)212 2.688 (68.28) 1.21 (30.73) 1.938 (49.23) 2.250 (57.15) 0.315 (8.00) 3.580 (90.42) 2.625 (66.68)3 3.063 (77.80) 1.30 (33.02) 2.125 (53.48) 2.820 (71.65) 0.405 (10.29) 4.300 (104.22)
29、 2.750 (69.85)4 3.625 (92.08) 1.38 (35.05) 2.625 (66.68) 3.737 (94.92) 0.450 (11.43) 5.430 (137.92) 3.000 (76.20)6 5.125 (130.18) 1.50 (38.10) 3.250 (82.55) 5.646 (143.41) 0.504 (12.80) 7.625 (193.68) 3.250 (82.55)AThe sketches and designs of fittings shown are illustrative only.BThis dimension loca
30、tes the end of the fitting.D2464 152fittings shall be as uniform as commercially practicable incolor, opacity, density, and other physical properties.8. Test Methods8.1 ConditioningCondition the test specimens at 73.4 63.6F (23 6 2C) and 50 6 10 % relative humidity for not lessthan 40 h prior to tes
31、t in accordance with Procedure A ofPractice D618, for those tests where conditioning is required.8.2 Test ConditionsConduct tests in the Standard Labora-tory Atmosphere of 73 6 3.6F (23 6 2C) and 50 6 10 %relative humidity, unless otherwise specified in the test meth-ods or in this specification.8.3
32、 SamplingA sufficient quantity of fittings as agreedupon between the seller and the purchaser shall be selected atrandom from each lot or shipment and tested to determine thatthe basic design is in conformance with this specification.NOTE 4For individual orders or specifications where supplementalte
33、sts are required, only those tests and numbers of tests specifically agreedupon between purchaser and supplier need be conducted.8.4 Burst PressureDetermine the minimum burst pressurewith at least five specimens in accordance with Test MethodD1599. Join the fittings to the pipe sufficiently strong a
34、nd insuch a manner that no failures shall occur in the assembly at apressure less than the pressure requirement given in Table 3.The time of testing each assembly shall be between 60 and 70s.9. Retest and Rejection9.1 If the results of any test(s) do not meet the requirementsof this specification, t
35、he test(s) shall be conducted again onlyby agreement between the purchaser and seller. Under suchagreement, minimum requirements shall not be lowered,changed or modified, nor shall specification limits be changed.If upon retest, failure occurs, the quantity of product repre-sented by the test(s) doe
36、s not meet the requirements of thisspecification.10. Product Marking10.1 Quality of MarkingThe marking shall be applied tothe fittings in such a manner that they remain legible undernormal handling and installation practices.10.2 Content of Marking:10.2.1 Fittings shall be marked with the following:
37、10.2.1.1 Manufacturers name or trademark,TABLE 2 Dimensions of Plugs and Caps, in.ANominalPipe SizeLength ofMale Thread,S,minLength ofFemale Thread,T,minWidth ofFlats,BQ,minNominal WallThickness,F,minHeight of Head,R,minCap Height,W,minOutside Diameterof Hub,M,min18 0.31 (7.87) 0.38 (9.65) 0.469 (11
38、.19) 0.108 (2.74) 0.188 (4.76) 0.625 (15.88) 0.645 (16.38)14 0.44 (11.18) 0.50 (12.70) 0.625 (15.88) 0.135 (3.43) 0.188 (4.76) 0.688 (17.48) 0.840 (21.34)38 0.44 (11.18) 0.50 (12.70) 0.750 (14.05) 0.144 (3.66) 0.188 (4.76) 0.688 (17.48) 1.000 (25.40)12 0.53 (13.45) 0.64 (16.26) 0.938 (23.83) 0.198 (
39、5.03) 0.188 (4.76) 0.875 (22.23) 1.280 (32.51)34 0.55 (13.97) 0.65 (16.51) 1.125 (28.58) 0.207 (5.26) 0.219 (5.56) 1.000 (25.40) 1.450 (36.80)1 0.68 (17.27) 0.81 (20.57) 1.375 (34.93) 0.225 (5.72) 0.219 (5.56) 1.188 (30.18) 1.810 (45.97)114 0.71 (18.03) 0.85 (21.59) 1.750 (44.45) 0.261 (6.63) 0.281
40、(7.14) 1.250 (31.75) 2.200 (55.88)112 0.72 (18.29) 0.85 (21.59) 1.875 (47.63) 0.270 (6.86) 0.313 (7.95) 1.250 (31.75) 2.450 (62.23)2 0.76 (19.30) 0.90 (22.86) 1.875 (47.63) 0.297 (7.54) 0.313 (7.45) 1.375 (34.93) 3.000 (76.20)212 1.14 (28.96) 1.21 (30.73) 1.875 (47.63) 0.369 (9.37) 0.375 (9.53) 1.62
41、5 (41.28) 3.560 (90.42)3 1.20 (30.48) 1.30 (33.02) 2.000 (50.80) 0.405 (10.29) 0.375 (9.53) 1.750 (44.45) 4.250 (107.90)4 1.30 (33.02) 1.38 (35.05) 2.000 (50.80) 0.450 (11.43) 0.375 (9.53) 2.000 (50.80) 5.350 (134.62)6 1.44 (36.58) 1.50 (38.10) 2.000 (50.80) 0.504 (12.80) 0.500 (12.70) 2.125 (53.98)
42、 7.625 (193.00)AThe sketches and designs of fittings shown are illustrative only.BAt the manufacturers option the head of the plug shall be hexagonal, octagonal, square, or round.TABLE 3 Burst Pressure Requirements for Water at 73F (23C)for PVC Threaded Pipe Fittings, Schedule 80NominalSize, in.Mini
43、mum Burst StrengthAClass 12454 Class 14333psi MPa psi MPa14 3620 (24.96) 2830 (19.51)38 2940 (20.27) 2300 (15.86)12 2720 (18.75) 2120 (14.62)34 2200 (15.17) 1720 (11.86)1 2020 (13.93) 1580 (10.89)114 1660 (11.44) 1300 (8.96)112 1510 (10.41) 1180 (8.14)2 1290 (8.89) 1010 (6.96)212 1360 (8.38) 1060 (7
44、.31)3 1200 (8.27) 940 (6.48)4 1040 (7.17) 810 (5.51)6 890 (6.19) 700 (4.83)AThis table was calculated for Schedule 80 pipe using the ISO formula and thestress levels for materials as follows:psi MPaClass 12454Class 143336400500044.134.5D2464 15310.2.1.2 Material identification PVC I for cell classif
45、ication12454 or PVC II for cell classification 14333,10.2.1.3 The seal or mark of the laboratory making theevaluation for potable water contact.10.2.1.4 Size, and10.2.1.5 This designation, D2464, with which this fittingcomplies.10.3 Where the size of the fittings does not allow completemarking, omit
46、 identification marking in the following se-quence: size, material designation, D2464, manufacturersname or trademark.10.4 Markings or symbols shall be molded, hot-stamped, orapplied to fittings by any other suitable method, such asprinting.10.5 Where recessed marking is used, care shall be taken to
47、see that in no case marking causes cracks or reduces the wallthickness below the minimum specified.11. Quality Assurance11.1 When the product is marked with this designation,D2464, the manufacturer affirms that the product wasmanufactured, inspected, sampled, and tested in accordancewith this specif
48、ication and has been found to meet therequirements of this specification.SUPPLEMENTARY REQUIREMENTSGOVERNMENT/MILITARY PROCUREMENTThe following requirements apply only to federal/military procurement, not domestic sales ortransfers.S1. Responsibility for Inspection Unless otherwise speci-fied in the
49、 contract or purchase order, the producer is respon-sible for the performance of all inspection and test require-ments specified herein. The producer may use his own or anyother suitable facilities for performance of the inspection andtest requirements specified herein, unless the purchaser disap-proves. The purchaser shall have the right to perform any of theinspections and tests set forth in this specification where suchinspections are deemed necessary to ensure that materialconforms to prescribed requirements.NOTE S1.1In