NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf

上传人:dealItalian200 文档编号:978639 上传时间:2019-03-13 格式:PDF 页数:5 大小:30.48KB
下载 相关 举报
NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf_第1页
第1页 / 共5页
NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf_第2页
第2页 / 共5页
NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf_第3页
第3页 / 共5页
NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf_第4页
第4页 / 共5页
NAVY MIL-DTL-24643 15 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +105 DEGREE C 1000 VOLTS TYPE LSDSGU《LSDSGU型1000 V -20 ℃~+105 ℃电缆》.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、 INCH-POUND MIL-DTL-24643/15F 1 October 2009 SUPERSEDING MIL-DTL-24643/15E 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSDSGU This specification is approved for use by all Departments and Agencies of the Department of Defense. The requirements for a

2、cquiring the product described herein shall consist of this specification sheet and MIL-DTL-24643. Construction, Watertight with Circuit Integrity First - Copper conductor, coated or uncoated (see table I for size). Second - Thermoset insulation, extruded or taped (see table I for thickness). Third

3、- Optional glass braid. Fourth - Optional covering (unless required by 3.3.5 of MIL-DTL-24643). Fifth - The two conductors shall be cabled together in accordance with 3.4.4 of MIL-DTL-24643. Fillers may be used as necessary to form a firm well-rounded assembly. Standard identification code applied b

4、y Method 1, 3, or letter identification code applied by Method 5. If identification Method 1 is used, outer surface to be printed shall appear black. Sixth - An optional binder. Seventh - Cross-linked polyolefin jacket (see table I for thickness). AMSC N/A FSC 6145 Provided by IHSNot for ResaleNo re

5、production or networking permitted without license from IHS-,-,-MIL-DTL-24643/15F 2TABLE I. Details. Conductor size Military part no. M24643/15 Type and size Navy std AWG Cable overall diameter max. (inch) Insulation thickness min. avg. (inch) Jacket thickness min. avg. (inch) Conductor resistance (

6、ohms) Insulation resistance (megohms) Accelerated service loading ampere -01UN LSDSGU-3 16 (Class B) 0.391 0.018 0.030 4.3 500 -02UN LSDSGU-4 14 (Class B) 0.427 0.018 0.030 2.68 500 -03UN LSDSGU-9 10 (Class B) 0.544 0.015 0.040 1.08 500 -04UN LSDSGU-14 9 (Class B) 0.670 0.018 0.040 0.859 500 100 -05

7、UN LSDSGU-23 7 (Class B) 0.781 0.035 0.050 0.543 500 130 -06UN LSDSGU-50 3 (Class C) 0.911 0.035 0.050 0.210 200 215 -07UN LSDSGU-75 1 (Class C) 1.074 0.035 0.050 0.134 175 285 -08UN LSDSGU-100 0 (Class D) 1.167 0.035 0.050 0.106 160 335 -09UN LSDSGU-200 0000 (Class D) 1.583 0.050 0.060 0.053 125 52

8、5 -10UN LSDSGU-300 300 MCM (Class D) 1.841 0.050 0.075 0.0377 110 700 -11UN LSDSGU-400 400 (127) 2.069 0.050 0.075 0.0273 100 835 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24643/15F REQUIREMENTS: Qualification required. INSPECTION: Basi

9、c Electricals: Conductor resistance (ohms/1000 feet at 25 C, max.) See table I Voltage withstand (volts, root mean square, min.) Conductor to conductor Sizes 3 through 9 3000 Sizes 14 and larger 5000 Insulation resistance (megohms/1000 feet, min.) Conductor to conductor See table I Conductor continu

10、ity No failure Group A: Visual and dimensional No failure Watertightness (see MIL-DTL-24643 for limits of water leakage) No failure Abrasion resistance scrapes minimum No damage (Sizes 40 and smaller) (extruded insulation only) Crack resistance (Sizes 3 through 100) (extruded insulation only) No dam

11、age Group B: Cold bending cable No failure Thermoset proof test (percent, max.) Insulation (extruded insulations only) 50 Jacket (when tested at 200 C) 50 Drip (951 C) Zero Physicals (unaged) Insulation (extruded insulation only) Tensile strength (lb/in2, min.) 700 Elongation (percent, min.) 150 Jac

12、ket (cable) Tensile strength (lb/in2, min.) 1300 Elongation (percent, min.) 160 Tear (lb/in2thickness, min.) 35 Gas flame (1 hour) No failure 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24643/15F Group C: Physicals (aged) air oven Jacke

13、t (cable) Tensile strength (percent of unaged, min.) 60 Elongation (percent of unaged, min.) 60 Permanence of printing (insulation, Method 1 only) (cycles, min.) 25 Permanence of printing (jacket) (cycles, min.) 125 Heat distortion (percent of unaged, max.) 30 Cable fill (sealant) removability No fa

14、ilure Shrinkage No failure Group D: Flame propagation (cable) No failure Qualification Inspection: Qualification inspection shall include basic electricals; groups A, B, C, and D; plus the following: Cold working (minus 202 C) No damage Gas flame (3 hours) No failure Accelerated service (Sizes 14 an

15、d larger) (see table I for load current) No failure Aging and compatibility (cable) (1255 C) No failure Abrasion resistance (jacket) (scrapes, min.) 75 Acid gas equivalent (percent, max.) Jacket 2 Fillers 2 Insulation 18Halogen content (percent, max.) Jacket 0.2 Fillers 0.2Insulation 0.2 Immersion (

16、jacket) Tensile strength (percent of unaged, min.) 50 Elongation (percent of unaged, min.) 50 Smoke index (max.) Jacket 25 Fillers 454 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24643/15F 5 Insulation 45 Toxicity index (max.) Jacket 5 Fi

17、llers 5Insulation 1.5Durometer (jacket) - Type A (hardness, min.) 80 Weathering (jacket) No failure Electrical moisture absorption (extruded insulations only) No failure UNIT ORDERING LENGTHS: Type Size Feet (nominal) LSDSG 3 2500 LSDSGU 4 through 23 2000 LSDSGU 50 1500 LSDSGU 75 and 100 1000 LSDSGU

18、 200 through 400 800 CHANGES FROM PREVIOUS ISSUE: Marginal notations are not used in this revision to identify changes with respect to the previous issue due to the extent of the changes. Custodians: Preparing Activity: Army MI Navy SH Navy SH (Project 6145-2008-018) Review Activities: Army AR, AV,

19、CR Navy CG, EC DLA CC NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at http:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1