1、 Errata NFPA 30 Flammable and Combustible Liquids Code 2015 Edition Reference: Figure 16.4.1(b), Table 16.5.2.1 and Note 4; and Table 16.5.2.3, Note 5 Errata No.: 30-15-1 The Correlating Committee on Flammable and Combustible Liquids notes the following errors in the 2015 edition of NFPA 30, Flammab
2、le and Combustible Liquids Code. 1. Revise Figure 16.4.1(b) to read as follows: 2. In Table 16.5.2.1, under section headings “Relieving-Style Containers-Liquid Classes IB, IC, II, IIIA” and “Relieving-Style Containers Liquid Class IIIB”, change the data in columns 11 and 12 to read as follows 3. Rev
3、ise Table 16.5.2.1, Note 4 to read as follows: Notes: (1) (4) Double-row racks limited to maximum 6 ft (1.8 m) width depth 4. In Table 16.5.2.3, precede the last line of the Notes with “(5)”, to read as follows: (5) The minimum in-rack sprinkler discharge pressure shall not be less than a gauge pres
4、sure of 10 psi. Issue Date: December 11, 2014 (Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/codelist) Copyright 2014 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION