UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf

上传人:feelhesitate105 文档编号:1068326 上传时间:2019-04-02 格式:PDF 页数:14 大小:567.70KB
下载 相关 举报
UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf_第1页
第1页 / 共14页
UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf_第2页
第2页 / 共14页
UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf_第3页
第3页 / 共14页
UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf_第4页
第4页 / 共14页
UL 586-2009 UL Standard for Safety High-Efficiency Particulate Air Filter Units (Ninth Edition Reprint with revisions through and including December 19 2017)《高效颗粒空气过滤器组件》.pdf_第5页
第5页 / 共14页
点击查看更多>>
资源描述

1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 586 High-Efficiency, Particulate, Air Filter UnitsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHOR

2、IZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for High-Efficiency, Particulate, Air Filter Units, UL 586 Ninth Edition, Dated August 14, 2009 SUMMARY OF TOPICS This revision of ANSI/UL 586 includes the following: 1. Reaffirmation of the Ninth Edition

3、 of the Standard for High-Efficiency, Particulate, Air Filter Units, UL 586, as an American National Standard. The requirements are substantially in accordance with Proposal(s) on this subject dated July 11, 2014. All rights reserved. No part of this publication may be reproduced, stored in a retrie

4、val system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchan

5、tability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an author

6、ized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and ho

7、ld UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. The requirements in this Standard are n

8、ow in effect, except for those paragraphs, sections, tables, gures, and/or other elements of the Standard having future effective dates as indicated in the note following the affected item. The prior text for requirements that have been revised and that have a future effective date are located after

9、 the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. SEPTEMBER 15, 2014 UL 586 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL SEPTEMBER 15, 2014 UL 586 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FU

10、RTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL SEPTEMBER 15, 2014 1 UL 586 Standard for High-Efficiency, Particulate, Air Filter Units The rst and second editions were titled “High Efficiency Air Filter Units” The third and fourth editions were titled “High Efficiency, Particulate, Ai

11、r Filter Units” The fth edition was titled “Test Performance of High Efficiency Particulate, Air Filter Units” First Edition September, 1959 Second Edition June, 1964 Third Edition July, 1971 Fourth Edition November, 1975 Fifth Edition June, 1977 Sixth Edition July, 1985 Seventh Edition October, 199

12、0 Eighth Edition December, 1996 Ninth Edition August 14, 2009 This ANSI/UL Standard for Safety consists of the Ninth Edition. The most recent designation of ANSI/UL 586 as a Reaffirmed American National Standard (ANS) occurred on September 12, 2014. ANSI approval for a standard does not include the

13、Cover Page, Transmittal Pages, Title Page, or effective date information. The Department of Defense (DoD) has adopted UL 586 on September 30, 1991. The publication of revised pages or a new edition of this Standard will not invalidate the DoD adoption. Comments or proposals for revisions on any part

14、 of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered

15、in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC. ANSI/UL 586-2009 (R2014)UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUT

16、ION WITHOUT PERMISSION FROM UL SEPTEMBER 15, 2014 HIGH-EFFICIENCY, PARTICULATE, AIR FILTER UNITS - UL 586 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 General 4 CONSTRUCTION 3 Frame

17、s and Separators 4 4 Filter Media 5 5 Gaskets 5 PERFORMANCE 6 General 5 7 Efficiency and Resistance Tests 6 7.1 General .6 7.2 Conrmation of results 6 8 Penetration Tests .6 8.1 Samples .6 8.2 Test equipment 7 8.3 Aerosol penetration test .8 8.4 Heated air test .8 8.5 Moist air test .8 8.6 Low tempe

18、rature test .9 9 Spot Flame Test 9 MANUFACTURING AND PRODUCTION TESTS 10 General .9 RATINGS 11 General 10 MARKING 12 General 10 AUGUST 14, 2009 HIGH-EFFICIENCY, PARTICULATE, AIR FILTER UNITS - UL 586 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION

19、FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover high-efficiency, particulate, air-lter units intended for the removal of very ne particulate matter (not less than 99.97 percent of 0.3 micron diameter particles) from the air of industrial and laboratory exhaust and ventilating systems. 1.2

20、These requirements cover single air lter units. 1.3 These requirements do not cover multiple assembly air lter units. 2 General 2.1 When a value for measurement is followed by a value in other units in parentheses, the rst stated value is the requirement. CONSTRUCTION 3 Frames and Separators 3.1 The

21、 frame of a lter unit shall be of metal or other inorganic material, or of wood treated to reduce combustibility by pressure impregnation or the equivalent (a coating is not acceptable as a means to reduce combustibility). 3.2 Treated wood, when employed, shall be not less than 3/4 inch (19 mm) thic

22、k and shall have a ame-spread index of 25 or less, determined in accordance with the requirements in the Standard for Test for Surface Burning Characteristics of Building Materials, UL 723. 3.3 A wood frame shall be assembled with butted or rabbeted corner joints that are fastened with screws or dou

23、ble-nailed. 3.4 Frame joints and the abutments of frame with the lter pack shall be impermeable to air owing at or below the manufacturers air-ow rating. AUGUST 14, 2009 HIGH-EFFICIENCY, PARTICULATE, AIR FILTER UNITS - UL 586 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRI

24、BUTION WITHOUT PERMISSION FROM UL 4 Filter Media 4.1 The lter medium shall be glass ber or other equivalent inorganic material and may include an organic binder material. 4.2 The lter medium shall not contain unbonded asbestos ber materials. 5 Gaskets 5.1 A gasket, when provided on a unit, shall be

25、securely attached to the frame and shall provide a continuous seal about the face. PERFORMANCE 6 General 6.1 Tests for efficiency and resistance are to be conducted by the manufacturer independently of other tests described herein, employing samples specied in 6.5, following test procedures, and at

26、locations described in Efficiency and Resistance Tests, Section 7. 6.2 Tests for aerosol penetration under ambient conditions and after exposure to heated air, moist air, and low temperatures are to be conducted as described in Penetration Tests, Section 8. 6.3 The Efficiency and Resistance Tests, S

27、ection 7, and the Penetration Tests, Section 8, are to be conducted with the aerosol of Henkel Corporation type Emery 3004 synthetic hydrocarbon or a suitable alternative. 6.4 A test for ame propagation is to be conducted as described in Spot Flame Test, Section 9. 6.5 One set of six samples is to b

28、e tested by the manufacturer in accordance with the Efficiency and Resistance Tests, Section 7, and one set of six samples is to be provided for conducting the Penetration Tests, Section 8, and Spot Flame Test, Section 9. An additional three samples are to be provided for conrmation testing, see 7.2

29、. Each sample is to be 24 by 24 inches (610 by 610 mm) by maximum depth available and is representative of smaller units of the same construction. AUGUST 14, 2009 HIGH-EFFICIENCY, PARTICULATE, AIR FILTER UNITS - UL 586 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION

30、WITHOUT PERMISSION FROM UL 7 Efficiency and Resistance Tests 7.1 General 7.1.1 When tested as described in 7.1.2 7.2.1, the efficiency of a lter unit shall be not less than 99.97 percent (the maximum penetration through the lter shall be not more than 0.03 percent of the particles introduced in the

31、air upstream of the test sample) and the resistance (pressure differential) across the lter unit at the specied air ow rate shall be not more than 1.3 inch water column (324 Pa) for units rated 25, 50, 125, 1500, and 2000 cfm. For units rated 500 and 1000 cfm, the resistance shall not be more than 1

32、.0 inch water column (249 Pa). 7.1.2 Samples of the lter unit are to be tested by the manufacturer in accordance with the Test Method in Section FC of the ASME AG-1, Code on Nuclear and Gas Treatment. For this test, a “penetrometer” is to be used. 7.1.3 In the penetrometer, air of controlled tempera

33、ture and humidity is to be circulated through a heated container of liquid Emery 3004 or a suitable alternative at a rate controlled to produce a constant number of uniform aerosol particles, 0.3 micron in diameter, per unit volume. The resultant aerosol is to be blown through the lter unit under te

34、st and the density of the aerosol downstream of the lter is to be measured by a light beam-photocell combination. A comparison of the downstream density readings with the known aerosol density upstream of the lter unit then is to serve as the basis for calculating the efficiency of the lter unit. 7.

35、1.4 During the test, the air ow through the lter unit is to be maintained at the manufacturers air-ow rating. 7.2 Conrmation of results 7.2.1 As a conrmation of results of tests by the manufacturer, three samples from each line of lter units having similar design and construction are to be tested at

36、 Air Techniques International, 1708 Whitehead Road, Suite 104, Baltimore, Maryland for compliance with the requirements in 7.1.1: 8 Penetration Tests 8.1 Samples 8.1.1 Samples selected for testing are to be representative of other sizes of similar design and construction. 8.1.2 Initially, six sample

37、s are to be tested in the as-received condition for percent of aerosol penetration as specied in 8.3.1 and 8.3.2. Of these six samples, three then are to be subjected to the heated air test described in 8.4.1 8.4.3, one to the moist air test described in 8.5.1 8.5.3, one to the low temperature test

38、described in 8.6.1 8.6.3, and one to the Spot Flame Test, Section 9. AUGUST 14, 2009 HIGH-EFFICIENCY, PARTICULATE, AIR FILTER UNITS - UL 586 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 8.2 Test equipment 8.2.1 These tests and the Spot F

39、lame Test, Section 9, are to be conducted in a horizontal duct 27 by 27 inches (686 by 686 mm) in cross section and 13-1/2 feet (4.12 m) long. The duct is to be made of stainless steel reinforced with angle iron. One end of the duct is to be tapered and attached to the discharge of a constant-speed

40、blower that, in turn, has an adjustable air-intake opening preceded by a calibrated venturi or similar ow meter. 8.2.2 Instrumentation for measuring the resistance (pressure differential across the test specimen) and air temperature is to be provided. 8.2.3 A portable air-operated generator for prod

41、ucing an aerosol of Emery 3004, or a suitable alternative, a forward light-scattering cell, and a percent penetration indicator are to be provided for making percent penetration determinations. 8.2.4 This generator is to consist of an unheated container of liquid Emery 3004, or a suitable alternativ

42、e and a set of aspirator nozzles connected to a building service air line. 8.2.5 The discharge end of the duct is to be unobstructed for all tests except the aerosol penetration test described in 8.3.2. For this test, an adapter and a exible 18-inch (457-mm) diameter, 25-foot (7.62-m) long duct are

43、to be provided to produce a uniform mixture of air and aerosol particles at the duct exit. 8.2.6 A metal frame is to be provided at the center of the duct to receive the lter unit. The duct is to be provided with tight-tting doors and windows to permit lter units to be mounted and observed during th

44、e test. 8.2.7 The upstream section of the duct is to be equipped with facilities for heating the air to be passed through the lter unit as required for the heated air test described in 8.4.2. 8.2.8 The size of the constant-speed blower and the design of the adjustable air intake are to permit delive

45、ry of the required ow of air. 8.2.9 Equipment is to be provided for conditioning test samples in atmospheres of 50 5 and 90 5 percent relative humidity at 77F (25C) and at normal atmospheric pressure, and for reducing the temperature of test samples to 27 4F (minus 3 2C). AUGUST 14, 2009 HIGH-EFFICI

46、ENCY, PARTICULATE, AIR FILTER UNITS - UL 586 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 8.3 Aerosol penetration test 8.3.1 When tested as specied in 8.3.2, the percent aerosol penetration through a lter unit shall be not more than 0.05

47、. 8.3.2 Each sample is to be mounted in the test duct and the air ow is to be adjusted to the manufacturers air-ow rating. The aerosol portable generator a is to be used to introduce aerosol particles into the inlet of the calibrated venturi ow meter. The aerosol penetration is to be measured downst

48、ream of the unit by means of the forward light-scattering cell and percent penetration indicator. The test is to be conducted at room temperature 70 10F (25 6C). a It should be recognized that the percent aerosol penetration value obtained when using this aerosol portable generator is generally lowe

49、r than that determined at the factory when using the hot aerosol machine. 8.4 Heated air test 8.4.1 When tested as specied in 8.4.2 and 8.4.3, the percent aerosol penetration through a lter unit shall be not more than 3.0. 8.4.2 Each sample (see 8.1.2) is to be installed in the test duct and subjected to the ow of heated air for 5 minutes. The temperature of the heated air is to be 700 50F (371 27C), as measured at each of six points